3.  BACNET/LONWORKS 

SETUP FOR 

PROTOCESSOR 

PROTONODE RER/LER

Connects only to a master unit, not a follower. Follow these 

instructions step-by-step for successful commissioning of 

the device.

Installation steps for the customer

1.  Record identification data. (See page 5)
2.  Set  the  Raypak  VERSA  IC  Modbus  RTU  serial 

settings (i.e. baud rate, parity, stop bits) and Modbus 

Node-ID’s  for  each  VERSA  IC  Master  that  will  be 

connected to the ProtoNode FPC-N34 or FPC-N35. 

(See 

Table A

)

3.  Select  the  Field  Protocol  (BACnet  MS/TP,  BACnet 

IP, Modbus TCP or Metasys N2) on the S Bank Dip 

Switches on the FPC-N34-0636. (See 

Figure 2

)

4.  Set BACnet device address for the ProtoNode RER 

(FPC-N34).  (See  "Setting  the  MAC  Address  for 

BACnet MS/TP for the ProtoNode RER (FPC-N34)" 

on page 8)

5.  Set 

Metasys 

N2 

Node-ID. 

(See 

"Configure 

Raypak 

VERSA 

IC 

Modbus 

COM Settings" on page 6)

6.  If using BACnet MS/TP, Set B bank of DIP switches 

to set the baud rate on ProtoNode RER (FPC-N34). 

(See 

Figure 4

 & 

Table D

7.  Connect the ProtoNode’s 3 pin RS-485 port to the 

Field Protocol cabling. (See 

Figure 8

8.  Connect  each  of  the  Raypak  devices  to  the  RS-

485  Modbus  RTU  port  to  the  ProtoNode’s  RS-485 

interface which is located on the 6 pin connector of 

the ProtoNode (FPC-N34 and FPC-35). (See 

Figure 

through 

Figure 7

)

9.  Connect  Power  to  the  ProtoNode  RER  or  LER.  

(See 

Figure 11

) Raypak recommends a dedicated 

power supply be used to power the ProtoNode.

10. Follow  instructions  on  page 

12

  to  use  web 

configurator.

11.  Use  Web-Configurator  to  select  the  Raypak 

products  that  will  be  attached  to  the  ProtoNode 

and set the current Modbus Node-ID for each these 

products. Once the Raypak products are selected, 

the ProtoNode Automatically builds and downloads 

the  Configuration  for  the  specific  application.  (See 

"Selecting the Raypak profiles that will be connected 

the ProtoNode" on page 13).

12. Where  the  Field  protocol  is  BACnet/IP  or  Modbus 

TCP,  run  the  ProtoNode  web  GUI  utility  program 

to  change  the  IP  address.  No  changes  to  the 

configuration file are necessary. (See "Set IP Address 

for BACnet/IP via GUI" on page 15)

13. Commission  the  ProtoNode  on  the  LonWorks 

Network. This  needs  to  be  done  by  the  LonWorks 

administrator  using  a  LonWorks  Commissioning 

tool. (See "Commissioning the ProtoNode LER on a 

LonWorks network" on page 16)

Record Identification Data

Each ProtoNode has a unique part number located on the 

underside of the unit. The numbers are as follows: 
•  FieldServer  part  #  FPC-N34-0636:VERSA  IC 

to  BACnet  MS/TP,  BACnet/IP,  Modbus  TCP, 

Metasys N2. 

•  FieldServer  part  #  FPC-N35-0637:  VERSA  IC  to 

LonWorks.

This number should be recorded, as it may be required for 

technical support.

Configure Raypak VERSA IC Modbus

 

COM Settings

•  All Raypak VERSA IC Master units connected to the 

ProtoNode  MUST ALL  have  the  same  Baud  Rate, 

Data  Bits,  Stop  Bits,  and  Parity.  (See 

Figure  2

These settings have no impact on the BMS portion 

of the Protonode communication and only are used 

to  connect  between  the  Versa  IC  Master  and  the 

Protonode.

•  Set  Modbus  Node-ID’s  (Address)  for  each  of  the 

Raypak  VERSA  IC  Master  units  attached  to  the 

ProtoNode.  The  Modbus  Node-ID’s  need  to  be 

uniquely assigned between 1 and 127.
•  The  Modbus  Node-ID’s  that  are  assigned  for 

each Raypak VERSA IC Master unit needs to be 

noted for later use when assigning Node-ID’s in 

the web configurator. (See 

Figure 18

)

•  The  Metasys  N2  and  Modbus  TCP  Node-ID 

will be set to same value as the Node-ID of the 

Modbus RTU device.

Serial Port Setting

VERSA IC

Baud Rate

19K2 (19200)

Data Bits

8

Stop Bits

1

Parity

Even

Table B.  Modbus RTU COM settings for the Raypak 

VERSA IC control platform

APPROVED 

UNCONTROLLED DOCUMENT IF PRINTED 

 

Содержание FPC-N34: FPC-N35

Страница 1: ...TRUCTIONS ProtoNode RER and ProtoNode LER For Interfacing Raypak heating products equipped with the VERSA IC control platform to Building Automation Systems BACnet MS TP BACnet IP Modbus TCP Metasys N2 and LonWorks FPC N34 B 85 FPC N35 B 86 APPROVED UNCONTROLLED DOCUMENT IF PRINTED ...

Страница 2: ... of page 4 Figures 1 6 7 9 revised Text revised following Figure 8 Section 4 verbiage and figures revised Figures 14 15 16 19 24 revised Instructions to Upload XIF section revised Appendix A Troubleshooting section revised Appendix B table Point Name descriptions updated APPROVED UNCONTROLLED DOCUMENT IF PRINTED ...

Страница 3: ...e ProtoNode RER FPC N34 BACnet or ProtoNode LER FPC N35 LonWorks 12 4 CONNECT TO THE PROTONODE S WEB CONFIGURATOR TO SETUP THE RAYPAK PRODUCTS PROFILES CONNECTED TO THE PROTONODE RER OR LER 12 Connect the PC to the ProtoNode via the Ethernet port 12 Configure Profiles in the ProtoNode s Web Configurator 13 Selecting the Raypak profiles that will be connected the ProtoNode 13 Changing BN_Node_Offse...

Страница 4: ...l Raypak products using VERSAIC control platform support ProtoNode Through the ProtoNode Web GUI Configurator the user selects how many VERSA IC Master units are connected to the ProtoNode as well as sets the Modbus Node ID for each VERSA IC Master A Versa IC Master Unit can have up to 169 Modbus points for up to 4 connected Versa IC equipped units Once the Raypak products are selected the ProtoNo...

Страница 5: ...orts Figure 1 ProtoNode BACnet RER BACnet and ProtoNode LER LonWorks RER Configuration B 85 BACnet Modbus Metasys To Controller To Controller LER Configuration B 86 LonWorks 2 INTERFACING THE PROTONODE TO RAYPAK PRODUCTS APPROVED UNCONTROLLED DOCUMENT IF PRINTED ...

Страница 6: ...figuration for the specific application See Selecting the Raypak profiles that will be connected the ProtoNode on page 13 12 Where the Field protocol is BACnet IP or Modbus TCP run the ProtoNode web GUI utility program to change the IP address No changes to the configuration file are necessary See Set IPAddress for BACnet IP via GUI on page 15 13 Commission the ProtoNode on the LonWorks Network Th...

Страница 7: ... S Bank DIP Switch Settings Setting the Device Instance Node ID for BACnet MS TP and BACnet IP on ProtoNode RER FPC N34 BACnet IP BACnet MSTP addressing The BACnet device instances will be set by taking the BN_ Node_Offset found in the Web Configurator See page 13 and added to each Modbus RTU device address set on the Raypak VERSA IC Master units attached to the ProtoNode 50000 is the default If o...

Страница 8: ...sure that power to the board is OFF Set Field RS 485 Baud Rate for BACnet MS TP on ProtoNode RER FPC N34 The serial baud rate setting between the BMS and the Protonode has no impact on the communication baud rate between the Versa IC Master and the Protonode The serial baud rate and Versa IC baud rate are not required to match for communication to take place The Versa IC Master baud rate must alwa...

Страница 9: ...nnector Connect VERSA IC Modbus pin B RS485 to the ProtoNode s pin 2 RS485 on the Phoenix 6 pin connector Connect VERSA IC Modbus pin GND Ground and the ProtoNode s pin 3 Signal Ground on the Phoenix 6 pin connector Figure 6 VERSA IC Modbus RS485 pin outs to the ProtoNode s Modbus port Raypak Pin ProtoNode Pin Assignment MODBUS A Pin 1 RS 485 MODBUS B Pin 2 RS 485 MODBUS GND Pin 3 RS 485 GND Power...

Страница 10: ...ypak VERSA Master Unit 1 Master Unit 2 Raypak VERSA Tx Rx Tx Rx Figure 7 Multiple VERSA IC Masters NOTE Multiple Master configuration requires each Master to have different ID s APPROVED UNCONTROLLED DOCUMENT IF PRINTED ...

Страница 11: ... setting from the factory is OFF switch position right side To enable the EOL termination turn the EOL switch ON switch position left side Figure 9 End of line termination on from ProtoNode to RS 485 Field Protocol BACnet MS TP Figure 10 LonWorks Terminal Wiring the ProtoNode LER FPC N35 Field Port to a LonWorks network Connect the ProtoNode to the field network with the LonWorks terminal using a ...

Страница 12: ...e PC and ProtoNode The default IP Address for the ProtoNode is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and ProtoNode are on different IP networks assign a static IP Address to the PC on the 192 168 1 xxx network For Windows 10 Find the search field in the local computer s taskbar usually to the right of the windows icon and type in Control Panel Power to the ProtoNode ProtoNode Pin Pin...

Страница 13: ... will list all the profiles available to select from To add an active profile to the ProtoNode select Add under Active Profiles For every Raypak VERSA IC Master Unit that will be added to the ProtoNode you will need to add the Active Profile on the left of the screen and the Modbus Node Address that the device is assigned to Each Versa IC Master unit must have a unique Modbus Node Address selected...

Страница 14: ...nfigurator showing a profile selected Figure 16 Web Configurator showing a completed profile added Continue this process until all the Raypak VERSA IC Master units have been added APPROVED UNCONTROLLED DOCUMENT IF PRINTED ...

Страница 15: ...iagnostics and Debugging button at the bottom right corner of the page to go to FSGUI utility Figure 17 Web Configurator showing multiple completed profiles added Click on setup and then Network Settings to enter the Edit IP Address Settings menu Figure 18 ProtoNode Network Settings Tab Type in a new Subnet Mask If necessary change the IP Gateway Default Gateway field Type in a new IP Gateway Note...

Страница 16: ...rks assign a static IP Address to the PC on the 192 168 1 xxx network For Windows 10 Find the search field in the local computer s taskbar usually to the right of the windows icon and type in Control Panel Click Control Panel click Network and Internet and then click Network and Sharing Center Click Change adapter settings on the left side of the window Right click on Local Area Connection and sel...

Страница 17: ...To request a 2 week complementary BACnet CAS key go to http app chipkin com activation twoweek and fill in all the information Enter Vendor Code Raypak2012 Once completed the key will be sent to the email address that was submitted From this email from Chipkin Automation the long key will need to be copied and pasted into the CAS key activation page Go to Chipkin Automation s web site download and...

Страница 18: ...re is a COM issue To fix this check the following o Visual observations of LEDs on ProtoNode Section 8 o Check baud rate parity data bits stop bits o Check device address o Verify wiring o Verify the device was listed in the Web Configurator Section 6 Field COM problems o Visual observations of LEDs on the ProtoNode o Verify IP Address setting o Verify wiring NOTE If the problem persists a Diagnos...

Страница 19: ...re will accelerate diagnosis of the problem Ensure that FieldServer Toolbox is loaded onto the local PC Otherwise download the FieldServer Toolbox zip via the MSA Safety website Extract the executable file and complete the installation Figure 24 Ethernet Port Location Connect a standard Cat 5 Ethernet cable between the PC and ProtoNode Double click on the FS Toolbox Utility Step 1 Take a Log Click...

Страница 20: ...wer indicating normal operation ERR The SYS ERR LED will go on solid 15 seconds after power up It will turn off after 5 seconds A steady red light will indicate there is a system error on the ProtoNode If this occurs immediately report the related system error shown in the error screen of the GUI interface to FieldServer Technologies for evaluation RX The RX LED will flash when a message is receiv...

Страница 21: ...X SNVT_count_f Boiler1 Error History 1 AI 31 AI 31 nvoLdErHt1_XXX SNVT_count_f Boiler1 Error History 2 AI 32 AI 32 nvoLdErHt2_XXX SNVT_count_f Boiler1 Error History 3 AI 33 AI 33 nvoLdErHt3_XXX SNVT_count_f Boiler1 Error History 4 AI 34 AI 34 nvoLdErHt4_XXX SNVT_count_f Boiler1 Error History 5 AI 35 AI 35 nvoLdErHt5_XXX SNVT_count_f Boiler1 Error History 6 AI 36 AI 36 nvoLdErHt6_XXX SNVT_count_f B...

Страница 22: ...y 1 AI 89 AI 89 nvoFl2ErHt1_XXX SNVT_count_f Boiler3 Error History 2 AI 90 AI 90 nvoFl2ErHt2_XXX SNVT_count_f Boiler3 Error History 3 AI 91 AI 91 nvoFl2ErHt3_XXX SNVT_count_f Boiler3 Error History 4 AI 92 AI 92 nvoFl2ErHt4_XXX SNVT_count_f Boiler3 Error History 5 AI 93 AI 93 nvoFl2ErHt5_XXX SNVT_count_f Boiler3 Error History 6 AI 94 AI 94 nvoFl2ErHt6_XXX SNVT_count_f Boiler3 Error History 7 AI 95 ...

Страница 23: ...viDHWDiff_XXX SNVT_temp_p DHW Priority BV 144 DO 144 nviDHWPrio_XXX SNVT_switch DHW During UnOcc BV 145 DO 145 nviDHWUnOc_XXX SNVT_switch WWSD During Occ AV 146 AO 146 nviWWSDOcc_XXX SNVT_temp_p WWSD During UnOcc AV 147 AO 147 nviWWSDUnOc_XXX SNVT_temp_p Tank Setpoint AV 148 AO 148 nviTnkSP_XXX SNVT_temp_p Tank Differential AV 149 AO 149 nviTnkDiff_XXX SNVT_temp_p Tank During UnOcc BV 150 DO 150 n...

Страница 24: ...f On Off Off 36 Off Off On Off Off On Off On 37 Off Off On Off Off On On Off 38 A7 A6 A5 A4 A3 A2 A1 A0 Address Off Off On Off Off On On On 39 Off Off On Off On Off Off Off 40 Off Off On Off On Off Off On 41 Off Off On Off On Off On Off 42 Off Off On Off On Off On On 43 Off Off On Off On On Off Off 44 Off Off On Off On On Off On 45 Off Off On Off On On On Off 46 Off Off On Off On On On On 47 Off O...

Страница 25: ... 101 Off On On Off Off On On Off 102 Off On On Off Off On On On 103 Off On On Off On Off Off Off 104 Off On On Off On Off Off On 105 Off On On Off On Off On Off 106 Off On On Off On Off On On 107 Off On On Off On On Off Off 108 Off On On Off On On Off On 109 Off On On Off On On On Off 110 Off On On Off On On On On 111 Off On On On Off Off Off Off 112 Off On On On Off Off Off On 113 Off On On On Of...

Страница 26: ...evice must not be connected to a LAN segment with outdoor wiring Specification ProtoNode RER ProtoNode LER Electrical Connections One 6 pin Phoenix connector one RS 485 ground port power frame ground port One 3 pin RS 485 Phoenix connector one RS 485 ground port One Ethernet 10 100 Ethernet port One 6 pin Phoenix connector one RS 485 ground port power frame ground port One Ethernet 10 100 BaseT po...

Страница 27: ...ave been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage In all cases FieldServer Technology s responsibility and liability under this warranty shall be limited to the cost of the equipment The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty...

Страница 28: ...28 Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 NOTES APPROVED UNCONTROLLED DOCUMENT IF PRINTED ...

Отзывы: