Appendix A.
Troubleshooting
Appendix A.1.
Connection Tips & Hints
Appendix A.1.1.
An error message displays when trying to download the Profibus database
Ensure that the correct serial port has been selected in the configure path setting.
Ensure that the X30 is powered up with a valid configuration file declaring all the Slaves to be
communicated with.
Confirm that the Run Led is flashing.
The following message on the E screen of Ruinet is shown when the X30 detects a request for new database
download:
Detected New Profibus Database!
Restarting FieldServer in 10 seconds...
Appendix A.1.2.
A Configuration Error is reported
Ensure that the correct Map Descriptor function has been used. Refer to Sections 4.5.2 and 4.7
Ensure that the number of configured bytes on the card has not been exceeded. A maximum of 1536
bytes can be accessed.