Select the first slave device, right-click on the Slot 1 line and choose Module selection. Now add I/O modules up to
the total number of bytes or words that will be transferred with this Slave as set up in the config.csv file. For
Example, for the Map Descriptor for Slave1 using 50 Words In and Out, you would choose the following modules:
Continue selecting other Slaves and adding modules for them as well.
Important Note:
Changing of Input and Output Addresses are not allowed. All addresses must be contiguous for
the X30 Profibus to work correctly.
Select Online-> Driver selection and on the serial Tab, choose the serial port on the PC connected to the X30 by
clicking on Configure-> Configure path.
Ensure that the X30 FieldServer is running and that a matching configuration file with Node and Map Descriptors
for each slave configured has been downloaded to the X-30.
The table below shows the map descriptor function that should be used in the config.csv with a specific module.
Module Map Descriptor Function
In
Wrbc
Out
Rdbc
In/Out
Wrbc/Rdbc
4
Make sure you can connect with Ruinet to the X30 and there are no configuration errors.
4
2 Map Descriptors need to be configured, one for the input module and one for the output