Troubleshooting

Status Messages

Tank 80% Full

Overfill sensor indicated the recovery cylinder is full.  Replace 

recovery cylinder. 

Input Closed

Cannot zero the displayed pressure because pressure sensor not 

open to atmosphere. Open input port.

Output Closed

Cannot zero the displayed pressure because pressure sensor not 

open to atmosphere. Open output port.

High Voltage Warning

Voltage was above 250 VAC. Motor stopped. Ensure power network 

voltage is between 200 and 250 VAC @ 50 Hz.

Low Voltage Warning

Voltage was below 200 VAC. Motor stopped. Check power network 

to ensure voltage is between 200 and 250 VAC @ 50 Hz.

High Pressure Cutoff

Output (cylinder) reached dangerous pressure. Motor stopped. 

Ensure all valves after the output port are open. The cylinder may need 

to be cooled or replaced to reduce pressure.

Low Pressure Cutoff

Input reached final recovery vacuum. Motor stopped. It’s normal 

to see this after RECOVERY or SELF PURGE is complete. Ensure valves 

before the input port are open and the knob is not set to CLOSED.

Motor Fault 1

Motor temperature above operating range. Motor stopped. 

Extremely high ambient temperature, extended liquid recovery time, 

or high cylinder pressure can be the cause. Allow time for the motor to 

cool down before resuming, and throttle the RECOVERY (page 21).

Motor Fault 2 

(“throttle” shows on display)

Motor current (amps) rose above operating range. Motor stopped. 

Extremely high ambient temperature, harsh liquid slugging, extended 

recovery time, or high cylinder pressure can be the cause. Throttle 

RECOVERY and start the motor. If fault occurs again, throttle even more 

and start the motor (page 19).

Motor Fault 3

Motor stopped for unknown reason. If this occurs repeatedly, there 

may be something wrong with MR45INT.

Fault 3 

(“PLug O F S” shows on display)

80% overfill Sensor not detected. Plug sensor cable into cylinder.

Other Symptoms

MR45INT never reaches 25 cmHg or 50 cmHg.

Check for a leakage before the input port. 

Recovery cylinder should be below 3200 kPa for 25 cmHg vacuum.

Recovery cylinder should be below 1600 kPa for 50 cmHg vacuum.

Input port shows frost or signs of leakage.

Ensure the grooved input fitting is hand tight before tightening the 

hex nut (page 32). 

Recovery is slower than normal.

There could be an input blockage. Check mesh screen filter for 

blockage. Ensure knob is set to RECOVER.

Display does not turn on when plugged in.
 

Ensure power cord and outlet are okay. 

Ensure power switch is flipped ON after plugging into power.

Excessive noise during liquid recovery.

MR45INT is experiencing a high load. Rotate the knob of MR45INT 

to throttle the refrigerant flow.

Overfill sensor not working correctly. 

Check for loose connection. Overfill sensor may be broken. Verify 

overfill with scale. If overfill sensor is bad, mark tank for disposal. 

Содержание MR45INT

Страница 1: ...Fieldpiece Refrigerant Recovery Machine OPERATOR S MANUAL Model MR45INT ...

Страница 2: ...ion Setup Operational Class A2L Refrigerants Tech Tips 14 General Setup Operational Controls 16 Display and Buttons Status Icons and Messages Port Routing Control MR45INT Refrigerant Flow Dynamic Pressure Measurement Functions 24 Self Test Self Purge Purging a Recovery Cylinder 80 Overfill Sensor Cable Port Direct Liquid Vapor Recovery Push Pull Recovery Troubleshooting 30 Status Messages Other Sy...

Страница 3: ... Screens for Input Port 3 Extra O ring for Input Port 65 cm IEC Power Cord Operator s Manual 1 Year Warranty WARNINGS Do not use to pump hydrocarbons explosion risk Do not use to pump flammable media explosion risk Do not connect MR45INT to power unless the local environment has been verified to be clear of combustible gas with a trusted leak detector explosion risk Inhalation of high concentratio...

Страница 4: ...reuseofmaterialresources Toreturnyouruseddevice please use the return and collection systems or contact the retailer where the product was purchased They can take this product for environmental safe recycling Description The MR45INT is the first variable speed DC motor recovery machine with a digital display Recover refrigerant easier and quieter than ever before Connect your hoses to the convenie...

Страница 5: ...d Power Source 190 to 255VAC 50 60 Hz 1 phase Nominal Current Draw 7 0 A Valve Single dual route ball valve Input Port Filtration 9 mm mesh screen stainless Noise Sound pressure level 70 db A Dimensions 376 mm x 250 mm x 344 mm 14 8 x 9 8 x 13 5 Weight 10 kg 22 lbs Operating Environment 0 C to 43 C 32 F to 109 F Storage Environment 20 C to 60 C 4 F to 140 F Approved Refrigerants 12 22 32 134A 143A...

Страница 6: ... as backup MR45INT Protection 1 Use only on approved list of refrigerants page 8 2 Do not use with hydrocarbons 3 Ensure mesh screen filter is installed and clean page 32 4 Use a filter drier on the input port and change it often to protect machine from contaminated refrigerants Setup 1 Ensure power switch is OFF before plugging into power 2 Repair any damaged parts before using 3 Disconnect power...

Страница 7: ...e power to nearby equipment is disconnected before opening the system 6 Ensure there are no flames or sparks in the area including cigarettes 7 Ensure the power switch is OFF 0 before plugging into power A Turn switch OFF B Plug into power C Turn switch ON D Perform and complete recovery operation E Turn switch OFF F Unplug from power 8 Always open valves of A2L refrigerant equipment slow enough t...

Страница 8: ...y for recovery but can make it more convenient and increase speed by having 2 system hook ups 4 Use a Schrader valve core removal tool to temporarily remove valve cores from service ports 5 Use the push pull method if recovering over 14 kg 30 lbs 6 Evacuate your empty recovery cylinders to 75 cmHg 29 6 Hg before use for fastest recovery 7 Know how much refrigerant you expect to recover before star...

Страница 9: ...l Knob Input Port Mesh Screen Filter Backlit Digital Dual Display and Buttons Output Port 80 Overfill Sensor Port Cable Not Included Power Switch Shown ON IEC Power Cord Storage IEC Power Cord Port and Plug 17 16 Controls ...

Страница 10: ...or 10 sec Tank 80 Full Motor stopped Overfill sensor triggered by liquid level of refrigerant in the recovery cylinder Input Closed Cannot zero pressures Open input port Output Closed Cannot zero pressures Open output port High Voltage Warning Motor stopped Voltage was above 250VAC Low Voltage Warning Motor stopped Voltage was below 200VAC High Pressure Cutoff Motor stopped Output cylinder approac...

Страница 11: ... close the IN port before you START the purge OR RECOVER Input and Output fully open Set to this fully open position for most of the recovery process OR RECOVER throttled Input and Output partially open Rotate away from RECOVER in either direction to reduce liquid slugging if knocking occurs This slows the flow of refrigerant so the machine operates more smoothly Only throttle as much as needed fo...

Страница 12: ... typically System typically Manifold knob control Condenser microchannel Dynamic Pressure Measurement MR45INT pressure readings are designed only formonitoringpressures DonotuseMR45INTfor diagnostic pressure measurements If a system s pressure is stable MR45INT pressure readings will be close to your other pressure gauges If a system s pressure is changing pressure measurements at different locati...

Страница 13: ...nder When the cylinder pressure is higher than expectedyoumayhavenon condensablesatthe topofthecylinder Useaseconddeeplyevacuated cylinder to pull out the non condensables 1 Leave pressurized cylinder undisturbed overnight 2 Use a vacuum pump to evacuate another cylinder 3 Use your manifold gauges to connect the closed vapor ports of the two cylinders 4 Measure the vapor temperature of the pressur...

Страница 14: ...e fitting at cylinder until vapor is seen Unseat hose fitting at low side of manifold to purge low side hose 9 Fully open vapor valve of recovery cylinder 10 Press START to begin recovery 11 Adjust the knob as needed to throttle refrigerant flow if liquid slugging knocking occurs 12 When liquid recovery is complete open low side of manifold for vapor recovery 13 MR45INT stops automatically after v...

Страница 15: ...own in the diagram 5 Open valves of liquid hose and removal tool at liquid system port 6 To purge air from system liquid hose briefly unseat hose fitting at cylinder s liquid port until vapor is seen 7 Fully open liquid valve of recovery cylinder and allow to pressurize 8 Set MR45INT to RECOVER 9 Press START to begin recovery 10 Fully open vapor valve of recovery cylinder 11 To purge air from hose...

Страница 16: ... 21 Motor Fault 2 throttle shows on display Motor current amps rose above operating range Motor stopped Extremely high ambient temperature harsh liquid slugging extended recovery time or high cylinder pressure can be the cause Throttle RECOVERY and start the motor If fault occurs again throttle even more and start the motor page 19 Motor Fault 3 Motor stopped for unknown reason If this occurs repe...

Страница 17: ...filter becomes dirty and clogged it means it s working to keep your MR45INT working well for a long time You need to clean or replace this screen often Visit our website for information on obtaining extra mesh screens 1 Loosen counter clockwise the securing hex nut on the IN port 2 Unscrew counter clockwise the grooved input fitting 3 Clean or replace the mesh screen 4 Hand tighten clockwise the g...

Страница 18: ... implied warranties arising from the sale of a Fieldpiece product including but not limited to impliedwarrantiesofmerchantabilityandfitness for a particular purpose are limited to the above Fieldpiece shall not be liable for loss of use of the machine or other incidental or consequential damages expenses or economic loss or for any claim of such damage expenses or economic loss Local laws vary The...

Страница 19: ...MR45INT Fieldpiece Instruments Inc 2018 v31 ...

Отзывы: