WARNING:

 

Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.

Never operate the UV-Aire Air Purifying System out of the plenum

. Avoid touching the glass portion of the lamp with your hands.

INSTALLATION

Determine a suitable location on either the supply or 

1. 

return for the unit as shown in Figure 1. The unit must be 

mounted at least 3 feet from any flex duct type material.

NOTE:

 Unit can only be mounted in a vertical position as 

noted on inside cover label.

Apply mounting template to air duct. (See Figure 2)

2. 

Drill 

3. 

1

8

" diameter mounting holes at positions indicated on 

template. (See Figure 2)
Using a 2" hole saw, drill out lamp hole as shown on 

4. 

template. (See Figure 2)
Drill a 

5. 

7

8

" inspection hole as shown on template.  

(See Figure 2)
Remove template.

6. 

Mount unit to duct using the 4 supplied sheet metal screws. 

7. 

(See Figure 3)

Lamp Length

Minimum

Duct

Width

Volts

Amps

Hz Watts

Max Air

Temp ºF

Lamp Intensity at 

1 meter

Recommended

Max Sq. Feet

12"

9

120/240

.5

60

30

150º

37µW/cm

2

1500

18"

14

120/240

.5

60

30

150º

73µW/cm

2

2000

28"

22

120/240

1.1

60

60

150º

105µW/cm

2

3000

Figure 1

Figure 3

Figure 2

GENERAL INFORMATION

This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or 

condition, nor for use in the mitigation, treatment, or prevention of any disease or condition.

There are different size units available, depending on the square footage of your home.  See chart below for 

determining your home’s needs.

WARNING:

 Before installing or servicing a humidifier, air filter, heat system, or this unit, etc., always 

turn all power OFF and have units unplugged. Electrical shock can cause personal injury or death. 

Never expose eyes or skin to direct UVC light from any source.

Содержание UV-AIRE UV-E

Страница 1: ...fying System out of the plenum WARNING UV light will break down plastic materials not rated for UV exposure Examples wire insulation flex duct drain pans and humidifiers The unit must be mounted at least 30 from the above stated type of materials If it is necessary to mount the unit in direct line of sight of these types of materials they must be shielded with aluminum foil aluminum foil tape or s...

Страница 2: ...on template See Figure 2 Remove template 6 Mount unit to duct using the 4 supplied sheet metal screws 7 See Figure 3 Lamp Length Minimum Duct Width Volts Amps Hz Watts Max Air Temp ºF Lamp Intensity at 1 meter Recommended Max Sq Feet 12 9 120 240 5 60 30 150º 37µW cm2 1500 18 14 120 240 5 60 30 150º 73µW cm2 2000 28 22 120 240 1 1 60 60 150º 105µW cm2 3000 Figure 1 Figure 3 Figure 2 GENERAL INFORM...

Страница 3: ...etermine length of wire and conduit 9 necessary according to power connection and install wiring conduit and water tight connector as shown in example figure 4 Supplied by installer Remove wiring access cover to expose 10 terminal block Figure 5 Push power source wires through bushing in access 11 cover then begin securing wires according to the wiring diagram in figure 8 See Figures 6 7 Replace a...

Страница 4: ...g Bracket Specifications Remove the two hex nuts and angled bracket from included bagged 1 hardware Install the angled bracket and secure to the unit base with the hex nuts 2 provided See Figure 11 The angle bracket may be mounted in 4 positions allowing the bulb to either be angled up and down or left to right depending upon duct design Figures A D NOTE Be sure to note location of lamp hole in br...

Страница 5: ...d 21 that the ballast is plugged in securely to lamp If lamp still does not glow contact technical support at 1 252 522 3031 for further assistance After unit has been found to be working properly note date of 22 installation on inside cover close cover and engage latch Apply supplied wire tie to latch or other locking mechanism to provide safety Figure 13 Figure 14 BULB MOUNTING BRACKET SELECTION...

Страница 6: ... IMPORTANT Turn switch on unit to OFF position and disconnect from power source Remove wire tie or locking mechanism from latch on unit 1 Unplug ballast plug from end of lamp 2 Remove the wing nut on securing bracket Swing out securing bracket to clear lamp 3 Slide lamp out carefully 4 NOTE When replacing the lamp always wipe off lamp before installing Replace lamp following the appropriate proced...

Страница 7: ...eld Controls Part Number 12 46365401 46365506 18 46365402 46365506 28 46365403 46365506 REPLACEMENT PARTS LIST For replacement parts contact your local heating service company Any questions please contact Field Controls at Phone 252 522 3031 Fax 252 522 0214 Email sales fieldcontrols com FLEX DUCT INSTALLATION For installations on duct systems with a metallic main duct and flex duct branches follo...

Страница 8: ...roof of purchase sales receipt identifying the Product purchased Product model or accurate date code information and the date the Product s was purchased 3 Product whose warranty quality stickers Product serial number plates or electronic serial numbers have been removed altered or rendered illegible shall not be covered under the limited warranty 4 Defective Product must be returned to Company po...

Отзывы: