WARNING:

 

Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.

Never operate the UV-Aire

 Air Purifying System out of the plenum

. Avoid touching the glass portion of the lamp with your hands.

SAFETY CONSIDERATIONS
WARNING:

  Never expose eyes or skin to UVC light from any source.

 • Looking directly at the UVC light may cause permanent eye damage or blindness. 

 • Never operate the UV-Aire Air Purifying System out of the plenum.

• Designed for a closed duct system. Do not mount near a supply or a return air opening.

• All duct openings in direct line of site of the UV light must be sealed with aluminum tape or equivalent  

   sealing methods.

WARNING:

 UV light will break down plastic materials not rated for UV exposure:

(Examples: wire insulation, flex duct, drain pans and humidifiers)

 • The unit must be mounted at least 30" from the above stated type of materials.

 • If it is necessary to mount the unit in direct line of site of these types of materials, they must be    

   shielded with aluminum foil, aluminum foil tape, or sheet metal.

WARNING:

 DO NOT mount this unit outdoors.

 • This product is designed for indoor installation only (i.e. attics, crawl spaces, basements, etc.).

WARNING:

 Never touch broken lamp or internal contents of lamp.  The lamp contains mercury.

 • After opening the carton, unpack and inspect the unit and lamp for damage.  Do not install this unit  

   if any damage is noticeable. If lamp is damaged, cracked or broken, do not touch lamp or other  

   contents in carton. Close carton and return to seller immediately.

 • In case of accidental exposure to internal contents of lamp, wash hands and any other affected   

   skin area with mild detergent.  Remove affected clothing immediately.  If skin surface is pierced, seek  

   medical attention immediately.

 

NOTE:

 If you touch the glass of the lamp, you should wipe the glass clean with isopropyl alcohol and  

 a lint free wipe. If the lamp is not cleaned, the film of hand oils causes a reduction in the light intensity.

WARNING:

 Before installing or servicing a humidifier, air filter, HVAC system, or this unit, etc., always 

turn all power OFF and have unit unplugged. Electrical shock can cause personal injury or death. Never 

expose eyes or skin to direct UVC light from any source.

WARNING:

 To prevent water damage or electric shock, do not mount unit under a humidifier.

WARNING: 

This product is designed for indoor installation only (i.e. attics, crawl spaces, basements, 

etc.).  For use on gas fired, oil fired, electric and split system heat pump forced air systems.*  This 

product is NOT designed to be mounted outside on gas fired or heat pump packaged units.**

*Split system heat pumps are systems where the air handler and the air conditioning compressor are 

separate units.

**Packaged units are systems where the air handler and the air conditioning compressor are built 

together and are installed outside of the building.

GENERAL INFORMATION

The UV-Aire unit uses technology that is recommended by doctors who state 

that "ultraviolet radiation, properly integrated with heating, ventilating, and air 

conditioning systems, shows the most promise as a widely applicable means of 

air disinfection".

1

Optional UVC-Light Shield:

Designed to mount at virtually any angle to guard or shield certain plastics, 

wiring or air filters that may be affected by UVC light.

Optional UVC-Light Shield

Содержание UV-16/24

Страница 1: ...hone UV AIRE AIR PURIFYING SYSTEM Model UV 16 24 The UV Aire unit is designed to emit powerful UVC Band light rays which sterilize and reduce airborne microorganisms as they pass through a heating or air conditioning system It is installed in the main supply or return duct and operates continuously to automatically purify the air in the home 24 hours a day This product is not sold as a medical dev...

Страница 2: ...In case of accidental exposure to internal contents of lamp wash hands and any other affected skin area with mild detergent Remove affected clothing immediately If skin surface is pierced seek medical attention immediately NOTE If you touch the glass of the lamp you should wipe the glass clean with isopropyl alcohol and a lint free wipe If the lamp is not cleaned the film of hand oils causes a red...

Страница 3: ...a vertical or horizontal position See Figure 2 Leave template mounted to duct for future reference Drill 3 1 8 diameter mounting holes at positions indicated on template See Figure 3 Cut out the large opening 1 4 1 2 hole on the template See Figure 3 Using a 5 1 4 to 1 2 drill bit drill a viewport hole as indicated on the template Figure 3 Optional Light Shield The light shield may be mounted 6 at...

Страница 4: ...e mounting base With the ballast pressed against the mounting base 11 rotate the ballast clockwise 90 Do not wire the unit into the appliance s 24 volt fan or thermostat circuit Premature failure of the ballast 12 and lamp will occur The warranty will be voided Do not wire into a standard 120VAC electric supply Wire according to Diagram A or Diagram B Unit is designed to be wired to a 24V 40VA pow...

Страница 5: ...ormer before commencing inspection and cleaning NOTE Wear disposable non absorbent protective gloves prior to inspection procedure in case of accidental breakage of glass We recommend inspecting and cleaning the lamp at least every 6 months Frequency depends upon the 1 environment Such as the type of air filter duration of use and replacement cycle To maintain maximum output intensity replace the ...

Страница 6: ...nst the mounting base Rotate the ballast assembly 8 clockwise until it stops and is locked in place See Figure 10 After assembly is firmly in place reconnect power to transformer and plug 9 the power supply cord back into the standard electrical outlet Check lamp operation by looking through the viewport hole A blue glow should be seen in the duct After replacing the lamp make sure to install the ...

Страница 7: ... that the safety switch is fully engaged If lamp does not light up rotate ballast slightly clockwise or counter clockwise 4 If lamp does not light up after rotating ballast replace lamp 5 If unit still does not light up after replacing lamp replace unit 6 REPLACEMENT PARTS LIST For replacement parts contact Field Controls at Phone 252 522 3031 Fax 252 522 0214 Email sales fieldcontrols com CLEAN U...

Страница 8: ...roof of purchase sales receipt identifying the Product purchased Product model or accurate date code information and the date the Product s was purchased 3 Product whose warranty quality stickers Product serial number plates or electronic serial numbers have been removed altered or rendered illegible shall not be covered under the limited warranty 4 Defective Product must be returned to Company po...

Отзывы: