POWER VENTER SIZING
In order to choose the correct size power venter for a particular installation, the total input fi ring rate and 
total equivalent length of vent pipe to be used must be known. Refer to Table 2 to determine the maximum 
allowable equivalent feet of pipe for each model used with the pipe diameters shown. When venting 
multiple appliances, add the input of each appliance to determine the total input. Always choose a power 
venter that is capable of handling more than the system requires. The choke plate can be adjusted to 
compensate for the diff erence.

MAXIMUM EQUIVALENT HORIZONTAL PIPE LENGTH (FEET)

BTU/HR INPUT

VENTER MODEL NUMBER AND VENT PIPE DIAMETER

PVG-100

 PVG-300

PVG-600

3"

4"

4"

5"

6"

5"

6"

8"

25,000

270

455

--

--

--

--

--

--

55,000

100

169

--

--

--

--

--

--

70,000

--

144

--

--

--

--

--

--

100,000

--

100

305

--

--

--

--

--

145,000

--

--

145

247

334

413

--

--

220,000

--

--

64

100

147

181

--

--

310,000

--

--

--

54

74

91

146

216

400,000

--

--

--

--

--

54

87

134

520,000

--

--

--

--

--

--

52

86

610,000

--

--

--

--

--

--

--

66

Table 2

PROCEDURE FOR CALCULATING TOTAL EQUIVALENT PIPE LENGTH IN FEET

1.  Calculate the total equivalent feet for each type of fi tting used in the venting system from the following chart.

2.  Calculate the total amount of feet for the straight lengths of vent pipe.

3.  Add the equivalent feet for the fi ttings with the total amount of feet of straight lengths.

Table 3

*Reducer or increaser ratio (d/D) small diameter divided by the larger diameter. (See Figure 3)

Example: 4" to 8" reducer, the reducer ratio is d/D = 

4

8

 = 

1

2

. To estimate the 

equivalent foot length for the fi tting, use the smaller pipe diameter for the equivalent 
length fi gure. Example: 4" to 8" reducer; the reducer ratio is 

1

2

 and the smaller pipe 

diameter is 4". So, from the chart, the equivalent feet would be 7 feet.

Example: System Pipe Size = 4"
Step 1  2 – 90° Elbows (4") = 14 Ft.
Step 2  10 - 2 Ft. Lengths of 4" Pipe = 20 Ft.
Step 3  Total Equivalent Feet = 14 Ft. + 20 Ft. = 34 Ft.

Figure 3

EQUIVALENT LENGTH (FEET) OF VENT PIPE FOR VENT PIPE FITTINGS

VENT PIPE FITTINGS

 

VENT PIPE DIAMETER

3"

4"

5"

6"

7"

8"

9"

10"

TEE

19

25

31

38

44

50

56

63

90° ELBOW

5

7

9

11

12

14

16

18

45°  ELBOW

3

4

4

5

6

7

8

9

REDUCER

(d/D)*

1

4

8

11

14

17

19

22

25

28

1

2

5

7

8

10

12

13

15

17

3

4

2

3

3

4

4

5

6

6

P/N 46246300 Rev M 04/20

Содержание PVG-100

Страница 1: ... with pre wired integral 24 VAC Relay Timer factory set Draft Proving Switch and direct access Terminal Blocks 1 Installation Instruction Sheet OPTIONAL SYSTEM COMPONENTS NOT INCLUDED Side Wall Vent Hood Spill Switches Barometric Draft Control CONTENTS PAGE System Operation 2 Power Venter Sizing 3 4 Installation Safety Instructions 4 5 Installation of Power Venter 5 6 General Wiring Instructions 7...

Страница 2: ...run the power venter for a period of time after the burner has shut off to purge remaining flue gases UNIT SPECIFICATIONS Table 1 UNIT DIMENSIONS INCHES ELECTRICAL RATINGS MODEL H W D I O VAC Hz RPM WATT AMP TP PVG 100 7 5 10 0 7 0 4 4 115 60 3000 145 2 1 YES PVG 300 7 5 11 5 7 0 4 4 115 60 3000 145 2 1 YES PVG 600 8 75 12 0 8 5 5 5 115 60 3000 167 1 5 YES Inlet and outlet diameter Thermally prote...

Страница 3: ...H IN FEET 1 Calculate the total equivalent feet for each type of fitting used in the venting system from the following chart 2 Calculate the total amount of feet for the straight lengths of vent pipe 3 Add the equivalent feet for the fittings with the total amount of feet of straight lengths Table 3 Reducer or increaser ratio d D small diameter divided by the larger diameter See Figure 3 Example 4...

Страница 4: ...nded by the National Fuel Gas Code ANSI Z223 1 or refer to the General Installation Inspection section of this manual 3 Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls 4 Single wall vent pipe may be used to join an appliance to the venting system but if proper clearances cannot be maintained from combusti...

Страница 5: ...stems shall not be less than 7 above grade when located adjacent to public walkways b A venting system shall terminate at least 3 above any forced air inlet located within 10 c The venting system of other than a direct vent appliance shall terminate at least 4 below 4 horizontally from or 1 above any door window or gravity air inlet into the building d The vent termination of a direct vent applian...

Страница 6: ...regulate any draft fluctuations during operation 1 Use approved vent connectors to join the heating appliance outlet to the venter inlet securing each joint with sheet metal screws or equivalent means of fastening when required 2 Seal all pipe joints on the outlet side of the venter with a high temperature silicone adhesive or equivalent Test the vent connections for leaks by using a soap solution...

Страница 7: ...r circuit breaker rated at 15 amperes Prevent wiring contact with any heat source Wire the venter in accordance with the National Electrical Code and applicable local codes Refer to Diagram B for proper wiring specifications Diagram B 3 Wire the switch into the low voltage thermostat circuit Refer to the appropriate wiring diagram in this manual 4 After installation check the amperage through the ...

Страница 8: ...a heating appliance in accordance with the National Fuel Gas Code ANSI Z223 1 The following procedure will help in evaluation of the venting system It is intended as a guide to aid in determining that the appliance is properly installed and is in a safe condition for continuous use This is a generalized procedure which cannot anticipate all situations Accordingly in some cases deviation from this ...

Страница 9: ...nce a year motor should rotate freely To prolong the life of the PVG 600 motor it must be lubricated with six drops of SWG Superlube Part 46226200 annually The PVG 100 and PVG 300 have sealed ball bearings and therefore do not need to be oiled Blower Wheel Inspect the blower wheel annually to clear any soot ash or coating which inhibits either rotation or air flow Remove all foreign materials befo...

Страница 10: ...city of the venter selected b A CK 41 Control Kit must be added to the system to properly control the venter when common venting an additional 24 VAC furnace or boiler Tee the draft tube on the PVG unit to connect to the air pressure switch on the Control Kit Refer to Diagram D for wiring instructions PV SERIES POWER VENTER VERTICAL VENTING OPTION Diagram C illustrates correct and incorrect instal...

Страница 11: ...L1 L2 TERMINAL STRIP IN 24VAC CONTROL KIT ON SECOND APPLIANCE APPLIANCE CONNECTIONS L1 L2 GAS PRESSURE SWITCH ON MILLIVOLT APPLIANCE PVG WIRING FOR MULTIPLE 24VAC APPLIANCES PVG WIRING FOR MULTIPLE 24VAC APPLIANCES VENTING SYSTEM OPERATIONAL INFORMATION Date Heating appliance BTU HR input Gas valve operation pressure Vent system draft above draft hood or below barometric draft control CO2 measurem...

Страница 12: ...m ventCool Field Controls Technical Support Field Controls Technical Support 1 800 742 8368 1 800 742 8368 fieldtec fieldcontrols com fieldtec fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information abou...

Отзывы: