MULTIPLE VENTING SYSTEMS

1.  To vent a 24 VAC controlled boiler or furnace and a 

30 millivolt residential water heater using one PVG 
power venter refer to the following.

a.  Follow the instructions for safe and proper 

venting previously specifi ed in this manual. 
Make sure that the combined gross BTU/HR 
input and equivalent vent pipe length does not 
exceed the maximum venting capacity of the 
venter selected.

b.  A CK-20FV or CK-20FG control kit MUST be 

added to the system to properly control the 
venter during operation of the water heater. 
Refer to Figure 10 and Diagrams C and D for 
vent pipe arrangement and wiring information.

2.  To vent two 24 VAC appliances using one PVG 

power venter refer to the following.

a.  Follow the instructions for safe and 

proper venting previously specifi ed in 
this manual. Make sure that the combined 
gross BTU/HR input and equivalent vent pipe length does not exceed the maximum venting capacity of 
the venter selected.

b.  A CK-41 Control Kit must be added to the system to properly control the venter when common venting an 

additional 24 VAC furnace or boiler. Tee the draft tube on the PVG unit to connect to the air pressure switch 
on the Control Kit. Refer to Diagram D for wiring instructions. 

PV SERIES POWER VENTER: VERTICAL VENTING OPTION

Diagram C illustrates correct and incorrect installation of PV series venter in vertical vent confi guration (except 
PVE-1200). The correct installation maintains the required vertical position of the pressure switch; the incorrect 
installation does not. The following conditions must also be observed:

• 

Natural gas, LP gas or #2 fuel oil appliance rated at 75% or greater non-condensing type of appliance

• 

Maximum input temperature at power venter:  575°F

Figure 10

REPLACEMENT PARTS LIST
The following items are available for replacement, if necessary.

REPLACEMENT PARTS LIST

DESCRIPTION

PVG-100

PVG-300

PVG-600

Motor

46032000

46032000

46083300

Blower Wheel

46080100

46033400

46089400

24 VAC Relay

46282800

46282800

46282800

Pressure Switch

602602001

602602002

602602003

P/N 46246300 Rev M 04/20

Содержание PVG-100

Страница 1: ... with pre wired integral 24 VAC Relay Timer factory set Draft Proving Switch and direct access Terminal Blocks 1 Installation Instruction Sheet OPTIONAL SYSTEM COMPONENTS NOT INCLUDED Side Wall Vent Hood Spill Switches Barometric Draft Control CONTENTS PAGE System Operation 2 Power Venter Sizing 3 4 Installation Safety Instructions 4 5 Installation of Power Venter 5 6 General Wiring Instructions 7...

Страница 2: ...run the power venter for a period of time after the burner has shut off to purge remaining flue gases UNIT SPECIFICATIONS Table 1 UNIT DIMENSIONS INCHES ELECTRICAL RATINGS MODEL H W D I O VAC Hz RPM WATT AMP TP PVG 100 7 5 10 0 7 0 4 4 115 60 3000 145 2 1 YES PVG 300 7 5 11 5 7 0 4 4 115 60 3000 145 2 1 YES PVG 600 8 75 12 0 8 5 5 5 115 60 3000 167 1 5 YES Inlet and outlet diameter Thermally prote...

Страница 3: ...H IN FEET 1 Calculate the total equivalent feet for each type of fitting used in the venting system from the following chart 2 Calculate the total amount of feet for the straight lengths of vent pipe 3 Add the equivalent feet for the fittings with the total amount of feet of straight lengths Table 3 Reducer or increaser ratio d D small diameter divided by the larger diameter See Figure 3 Example 4...

Страница 4: ...nded by the National Fuel Gas Code ANSI Z223 1 or refer to the General Installation Inspection section of this manual 3 Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls 4 Single wall vent pipe may be used to join an appliance to the venting system but if proper clearances cannot be maintained from combusti...

Страница 5: ...stems shall not be less than 7 above grade when located adjacent to public walkways b A venting system shall terminate at least 3 above any forced air inlet located within 10 c The venting system of other than a direct vent appliance shall terminate at least 4 below 4 horizontally from or 1 above any door window or gravity air inlet into the building d The vent termination of a direct vent applian...

Страница 6: ...regulate any draft fluctuations during operation 1 Use approved vent connectors to join the heating appliance outlet to the venter inlet securing each joint with sheet metal screws or equivalent means of fastening when required 2 Seal all pipe joints on the outlet side of the venter with a high temperature silicone adhesive or equivalent Test the vent connections for leaks by using a soap solution...

Страница 7: ...r circuit breaker rated at 15 amperes Prevent wiring contact with any heat source Wire the venter in accordance with the National Electrical Code and applicable local codes Refer to Diagram B for proper wiring specifications Diagram B 3 Wire the switch into the low voltage thermostat circuit Refer to the appropriate wiring diagram in this manual 4 After installation check the amperage through the ...

Страница 8: ...a heating appliance in accordance with the National Fuel Gas Code ANSI Z223 1 The following procedure will help in evaluation of the venting system It is intended as a guide to aid in determining that the appliance is properly installed and is in a safe condition for continuous use This is a generalized procedure which cannot anticipate all situations Accordingly in some cases deviation from this ...

Страница 9: ...nce a year motor should rotate freely To prolong the life of the PVG 600 motor it must be lubricated with six drops of SWG Superlube Part 46226200 annually The PVG 100 and PVG 300 have sealed ball bearings and therefore do not need to be oiled Blower Wheel Inspect the blower wheel annually to clear any soot ash or coating which inhibits either rotation or air flow Remove all foreign materials befo...

Страница 10: ...city of the venter selected b A CK 41 Control Kit must be added to the system to properly control the venter when common venting an additional 24 VAC furnace or boiler Tee the draft tube on the PVG unit to connect to the air pressure switch on the Control Kit Refer to Diagram D for wiring instructions PV SERIES POWER VENTER VERTICAL VENTING OPTION Diagram C illustrates correct and incorrect instal...

Страница 11: ...L1 L2 TERMINAL STRIP IN 24VAC CONTROL KIT ON SECOND APPLIANCE APPLIANCE CONNECTIONS L1 L2 GAS PRESSURE SWITCH ON MILLIVOLT APPLIANCE PVG WIRING FOR MULTIPLE 24VAC APPLIANCES PVG WIRING FOR MULTIPLE 24VAC APPLIANCES VENTING SYSTEM OPERATIONAL INFORMATION Date Heating appliance BTU HR input Gas valve operation pressure Vent system draft above draft hood or below barometric draft control CO2 measurem...

Страница 12: ...m ventCool Field Controls Technical Support Field Controls Technical Support 1 800 742 8368 1 800 742 8368 fieldtec fieldcontrols com fieldtec fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information abou...

Отзывы: