Page 7 of 36
2A
Number of Bedrooms
Sq Ft
1
2
3
4
5
6
500
20
28
35
43
50
58
600
21
29
36
44
51
59
700
22
30
37
45
52
60
800
23
31
38
46
53
61
900
24
32
39
47
54
62
1000
25
33
40
48
55
63
1100
26
34
41
49
56
64
1200
27
35
42
50
57
65
1300
28
36
43
51
58
66
1400
29
37
44
52
59
67
1500
30
38
45
53
60
68
1600
31
39
46
54
61
69
1700
32
40
47
55
62
70
1800
33
41
48
56
63
71
1900
34
42
49
57
64
72
2000
35
43
50
58
65
73
2100
36
44
51
59
66
74
2200
37
45
52
60
67
75
2300
38
46
53
61
68
76
2400
39
47
54
62
69
77
2500
40
48
55
63
70
78
2600
41
49
56
64
71
79
2700
42
50
57
65
72
80
2800
43
51
58
66
73
81
2900
44
52
59
67
74
82
3000
45
53
60
68
75
83
3100
46
54
61
69
76
84
3200
47
55
62
70
77
85
3300
48
56
63
71
78
86
3400
49
57
64
72
79
87
3500
50
58
65
73
80
88
2B
Number of Bedrooms
Sq Ft
1
2
3
4
5
6
500
30
38
45
53
60
68
600
33
41
48
56
63
71
700
36
44
51
59
66
74
800
39
47
54
62
69
77
900
42
50
57
65
72
80
1000
45
53
60
68
75
83
1100
48
56
63
71
78
86
1200
51
59
66
74
81
89
1300
54
62
69
77
84
92
1400
57
65
72
80
87
95
1500
60
68
75
83
90
98
1600
63
71
78
86
93
101
1700
66
74
81
89
96
104
1800
69
77
84
92
99
107
1900
72
80
87
95
102
110
2000
75
83
90
98
105
113
2100
78
86
93
101
108
116
2200
81
89
96
104
111
119
2300
84
92
99
107
114
122
2400
87
95
102
110
117
125
2500
90
98
105
113
120
128
2600
93
101
108
116
123
131
2700
96
104
111
119
126
134
2800
99
107
114
122
129
137
2900
102
110
117
125
132
140
3000
105
113
120
128
135
143
3100
108
116
123
131
138
146
3200
111
119
126
134
141
149
3300
114
122
129
137
144
152
3400
117
125
132
140
147
155
3500
120
128
135
143
150
158
Table 2A: Continuous Ventilation Rate in CFM
per ASHRAE 62.2-2010 Standard
Table 2B: Continuous Ventilation Rate in CFM
per ASHRAE 62.2-2013/2016 Standard
P/N 780100700 07/18 Rev F
Continuous Calculation