Field Controls FAVC Скачать руководство пользователя страница 21

Page 21 of 36

7B. WIRING AND CONNECTIONS

This area is used to fi ne tune actual operating conditions by manually setting DIALS to match actual
appliance or operational condition to provide fresh air ventilation all year round to meet ASHRAE 62.2
Ventilation Standards while providing energy conservation, better indoor air quality and keeping
comfort in mind.  Refer to TABLE 1 for Air Flow Dial ranges and Factory Settings. 
The fi rst three dial settings (CFM Continuous, CFM Cool Vent and CFM Heat Vent) on the FAVC 
are used for computing the continuous ventilation run time and dwell time based on ASHRAE 62.2 
Standard. The cycle rate is fi xed at 30 minutes. Refer to Figure 2 for ventilation only required dials. 
Adjust the setting on the FAVC for the CFM Continuous dial to match the continuous ventilation rate 
for your dwelling per VENTILATION SETTINGS section, starting on page 5.  

The CFM Continuous 

rate is initially factory set at 100 CFM.

The 

Cool Vent and Heat Vent 

dial settings allows for two different settings if the air handler is equipped

with an ECM blower that may operate at different fan speeds for cooling and for heating modes.
If the system is a heat pump, the FAVC will automatically detect if the system is operating in cooling 
or heating based on the outdoor air temperature and the return air temperature. Each heating and 
cooling cycle is monitored; minimum and maximum temperatures are also recorded to anticipate 
the next call for heating or cooling. Conventional systems or heat pumps with auxiliary heat, the W 
terminal will indicate if the system is in heating mode of operation. 

The CFM Cool Vent and CFM Heat 

Vent rates are initially factory set at 400 CFM each.

Refer to Wiring Diagrams 1 and 2 for basic ventilation wire requirements using Fresh Air Damper 

or HRV/ERV devices. Refer to wiring diagrams 3 and 4 when adding optional appliance monitoring 
and/or control features.

7Bi. Ventilation Control Connectors

The FAVC has two isolated outputs for control of a fresh air damper and a remote relay to
control an exhaust fan (auxiliary fan for balanced ventilation or a bath fan). The Vent and
Exhaust Fan terminal block is in the VENT AND EXHAUST VENTILATION CONTROL CONNECTION
area of the FAVC as shown in Figure 1 and Figure 21. The terminals for the ventilation
damper are labeled with a V; and the terminals for the exhaust fan are labeled with an E.  Both sets of
terminals are compatible with all types of ERV/HRV systems that use dry contact or DC signals.  The 
V terminals can be used to activate an ERV/HRV unit if placed into intermittent fan operation.  Some 
ERV/HRV units can be confi gured to operate as two speed where the low speed will run continuously 
and the high speed is activated by dry contacts.  If the fl ow rate of the low speed operation is measured, 
it can be subtracted from the required continuous cfm rate on the primary control.  The high-speed
rating can be used for both Cool and Heat vent CFM values if a fresh air damper is not used.  Both, 
the V and E terminals are isolated from the 24 VAC supply (dry contact form), one terminal of the 
pair must be connected to the R (24VAC) power side of the supply transformer to control the fresh air
damper or the remote relay to operate a fan.  Both V and E terminals will be active during
ventilation calls.

FIGURE 21:  Vent and Exhaust Control Connections (Rotated 90°)

WARNING:   Under no circumstances shall line voltage be wired to these terminals. This product
     

is rated for Class 2 low voltage use. Ratings: 24VAC (3A max load). Dry

   

 

contact compliant, and suitable for up to 24VDC (3A max load).

P/N 780100700 07/18  Rev F

Содержание FAVC

Страница 1: ...OMPLETELY READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION BEFORE PROCEEDING WITH THE INSTALLATION Meets the requirements of the ASHRAE 62 2 standard for ventil...

Страница 2: ...Page 2 of 36 THIS PAGE LEFT INTENTIONALLY BLANK P N 780100700 07 18 Rev F...

Страница 3: ...itch 4 15 7 INSTALLATION 16 7A Installation Locations 16 i FAVC location 16 17 ii FAVC Mounting 18 iii Intake Air Connection Duct Installation 19 iv Fresh Air Damper or HRV ERV location 20 7B Wiring a...

Страница 4: ...ventilation controller in an outdoor location and or wet location Do not obstruct or cover the fresh air intake or air outlet of the ventilation system Provisions should be made for make up air requi...

Страница 5: ...Page 5 of 36 P N 780100700 07 18 Rev F 1 FAVC LAYOUT OVERVIEW FIGURE 1 FAVC Functional Product Layout shown with cover removed...

Страница 6: ...ect the number of bedrooms associated with your application 6 Locate where the square footage row and bedroom column intersect This determines the CFM continuous ventilation dial setting 7 Record and...

Страница 7: ...5 6 500 30 38 45 53 60 68 600 33 41 48 56 63 71 700 36 44 51 59 66 74 800 39 47 54 62 69 77 900 42 50 57 65 72 80 1000 45 53 60 68 75 83 1100 48 56 63 71 78 86 1200 51 59 66 74 81 89 1300 54 62 69 77...

Страница 8: ...heating and cooling cycle 4 Determine the fresh air intake internal round duct size and type If square or rectangular duct convert free area to the nearest round duct size 5 Determine the fresh air in...

Страница 9: ...fully adjust the CFM Cool Vent dial Use the recorded volume that was determined from using one of the previous methods and Recorded in Section 2B Note Locate arrow on the dial stem Align to the desire...

Страница 10: ...door temperatures During the summer months when outdoor temperatures summer months when outdoor temperatures are at 85 F or higher the FAVC will prohibit are at 85 F or higher the FAVC will prohibit v...

Страница 11: ...e is between 100 F and 17 F depending on if the HVAC system is in heating or cooling mode and depending on indoor relative humidity change during the ventilation cycle Below 25 F outside temperature a...

Страница 12: ...entilation is limited to prevent induct condensation from occurring FIGURE 7 Cold Climate Operation 3C COLD CLIMATE ZONE In Climate Mode HOT The FAVC will provide fresh outside ventilation if the outs...

Страница 13: ...lectrically isolated from the other pairs Unused input pairs should be left unconnected The associated control setting does not matter if the input is not used The optional inputs are not required for...

Страница 14: ...A3C terminal should be connected to common 24VAC power This input is typically used to monitor a clothes dryer or other medium CFM suitable exhaust fan appliance The control setting represents the air...

Страница 15: ...13 for DIP Switch 4 setting to configure FAVC central fan control during a call for ventilation function This is ideal for use with an ERV HRV system or to remote control a bathroom fan or exhaust fa...

Страница 16: ...VAC system when the small room is designed to act as a return air plenum using the optional FAVC mounting bracket Field Controls P N 602600150 refer to Figure 16 for return air closet installation inf...

Страница 17: ...CE AIR HANDLER FILTER TRIO 1200 2000 FRESH AIR DAMPER FRESH AIR OUTSIDE WALL FRESH AIR INTAKE HOOD W SCREEN OUTDOOR TEMPERATURE SENSOR R A VENT FROM HOME FAVC ON WALL MOUNT BRACKET INSIDE WALL OPTIONA...

Страница 18: ...h square hole in ductwork to allow the controller s Humidity Temperature Sensor to sense actual return air duct environmental conditions The Humidity Temperature sensor extends out from the back of th...

Страница 19: ...sh air inlets 7Aiii Intake Air Connection and Duct Installation Ductwork Specification All flexible ducts must meet UL safety standards for Class I air ducts and connectors All ducting must be install...

Страница 20: ...nd Fresh Air Intake location The HRV ERV unit should be installed in an area where the air is tempered to avoid freezing of the condensate line The contractor should install the unit in an area that i...

Страница 21: ...iring Diagrams 1 and 2 for basic ventilation wire requirements using Fresh Air Damper or HRV ERV devices Refer to wiring diagrams 3 and 4 when adding optional appliance monitoring and or control featu...

Страница 22: ...andler R is the 24VAC hot The FAVC does not need to be connected to the Y compressor or cooling as the GT thermostat fan signal will suffice for all applications including heat pumps There may be func...

Страница 23: ...Page 23 of 36 DIAGRAM 1 Conventional Wiring Diagram Thermostat Air Handler FAVC ODT Sensor and Fresh Air Damper P N 780300901 P N 780100700 07 18 Rev F...

Страница 24: ...Page 24 of 36 DIAGRAM 2 Conventional Wiring Diagram Thermostat Air Handler FAVC ODT Sensor and HRV ERV Device P N 780300902 P N 780100700 07 18 Rev F...

Страница 25: ...he ODT sensor is supplied with the FAVC and MUST BE INSTALLED for the FAVC to operate properly The best loca tion to mount the ODT sensor is next to the fresh air damper on the side wall of the duct L...

Страница 26: ...iance can be monitored if its air flow is within the appliance dial setting range The appliance monitoring features are based on the following equipment devices Appliance 1 HRV ERV or Bathroom Fan or...

Страница 27: ...RAM 3 Appliances 1 thru 4 Monitoring Connections using Current or Pressure Sensors P N 780300903 NOTE HVAC Thermostat Outdoor Sensor Wiring and FAD HRV ERV Connections not shown for simplicity P N 780...

Страница 28: ...ntrol and Monitoring Appliances using Current or Pressure Sensors and External Aube Relay NOTE HVAC Thermostat Outdoor Sensor Wiring and FAD HRV ERV Connections not shown for simplicity P N 780300904...

Страница 29: ...Blue Red No Color Green LED indicates outside air meets ventilation requirements without restrictions This is normal system will function normally Blue LED indicates the outside air temperature or re...

Страница 30: ...OOR TEMPERATURE SENSOR 620000102 C SENSOR CURRENT SENSOR 24VAC 46676600 P SENSOR PRESSURE SENSOR 24VAC 46679400 40XFMR TRANSFORMER UV 16 24 PLUG IN 46524800 50XFMR TRANSFORMER 24VAC 50VA 46638800 24VA...

Страница 31: ...fittings installed with a total of 30 foot equivalent duct length or less Long Run Length section is for 15 28 foot duct runs with 2 or less elbows or reducing fittings installed with a total of 30 f...

Страница 32: ...able 8 to select fresh air damper size based on measuring static pressure at the return intake multiple the continuous ventilation CFM value by 3 for fresh air damper CFM and calculated total equivale...

Страница 33: ...sh air damper size Step 2 Static pressure in the return is 0 15 inches WC measured Step 3 Ductwork system design consists of i Two 6 diameter 45 Elbow 10 equivalent feet ii 10 feet of straight 6 smoot...

Страница 34: ...____ CFM CFM Appliance 4 __________________________ CFM 100 400 400 75 75 200 850 Damper Size ________________________________ Inches or HRV Model _________________________________ CFM ___________ or...

Страница 35: ...Page 35 of 36 THIS PAGE LEFT INTENTIONALLY BLANK P N 780100700 07 18 Rev F...

Страница 36: ...ted from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information about this or any Field Controls product visit For warranty information about this or any Field Con...

Отзывы: