INSTALLATION OF GAS PRESSURE SWITCH
CAUTION: Check gas control valve pressure.
Pressure must not exceed 14” WC pressure.

1. 

Remove pressure tap plug in gas valve. 
(See Figure 3) 

NOTE:

 If installing on an existing 

appliance, shut off gas supply to gas valve before 
plug removal.

2. 

Replace the pressure tap plug with the 

1

8

” pipe 

nipple and pipe tee. Install pressure tap plug at the 
bottom of the pipe tee. (See Figure 4)

3. 

Install the gas pressure switch into the side of the 
pipe tee. The gas pressure switch is supplied with 
a restrictor orifi ce in the inlet and outlet ports. With 
these orifi ces in place, the switch does not need to 
be vented. This feature complies with current ANSI 
standards for gas regulators. (See Figure 5)

CAUTION: If for any reason the system has shut down 
during operation, the cause of the system failure should 
be investigated and corrected before resetting the 
safety switch and restarting the system.

Figure 4

Figure 3

Figure 5

P/N 

46285000 

Rev K 01/18

Содержание CK-20FV

Страница 1: ...CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION Installation Date Installed By Phone SYSTEM CONTROL KIT Model CK 20FV ITEMS INCLUDED IN KIT 1 Junction box 1 Fan control gas pressure s...

Страница 2: ...ning nut If remote mounting the CK 20FV junction box mount the flexible conduit connector onto a 2 x 4 installer supplied junction box 2 Fasten the flexible conduit from the SWG Venter into the condui...

Страница 3: ...om of the pipe tee See Figure 4 3 Install the gas pressure switch into the side of the pipe tee The gas pressure switch is supplied with a restrictor orifice in the inlet and outlet ports With these o...

Страница 4: ...n accepted wiring enclosure See Figure 6 NOTE Draft spillage switches must be mounted 90 degrees apart and mounted opposite from the vent outlet direction See Figure 7 3 Mount the two spillage switche...

Страница 5: ...be protected by an overcurrent circuit device rated at 15 amperes CAUTION must be taken to ensure that the wiring does not come into contact with any heat source All line voltage and safety control ci...

Страница 6: ...diagram Wire the venter motor and controls in accordance with the National Electrical Code manufacturer s recommendations and or applicable local codes Units must be grounded Check ground circuit to m...

Страница 7: ...ll for heat with the venter inoperative Allow approximately 2 minutes of flue gas spillage for the spillage switches to sense the spillage and disrupt the thermocouple circuit halting the gas flow to...

Страница 8: ...0 Rev K 01 18 This manual may be downloaded and printed from the Field Controls website www fieldcontrols com WARRANTY For warranty information about this or any Field Controls product visit www field...

Отзывы: