MOUNTING JUNCTION BOX

The junction box can be mounted at the venter or remotely mounted away from the venter. 
(See Figures 1 & 2)

1. 

Remove one of the knockouts from the side of the junction box. Install the fl exible conduit connector onto the 
CK-20FV junction box and secure with fastening nut. If remote mounting the CK-20FV junction box, mount the 
fl exible conduit connector onto a 2" x 4" installer supplied junction box.

2. 

Fasten the fl exible conduit from the SWG Venter into the conduit connector. Mount the CK-20FV junction box 
or installer supplied junction box onto the wall or fl oor joist without straining the fl exible conduit. Fasten the 
CK-20FV junction box through the four dimpled locations on the base of the box. (See Figure 1)

Figure 1

Figure 2

P/N 

46285000 

Rev K 01/18

Содержание CK-20FV

Страница 1: ...CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION Installation Date Installed By Phone SYSTEM CONTROL KIT Model CK 20FV ITEMS INCLUDED IN KIT 1 Junction box 1 Fan control gas pressure s...

Страница 2: ...ning nut If remote mounting the CK 20FV junction box mount the flexible conduit connector onto a 2 x 4 installer supplied junction box 2 Fasten the flexible conduit from the SWG Venter into the condui...

Страница 3: ...om of the pipe tee See Figure 4 3 Install the gas pressure switch into the side of the pipe tee The gas pressure switch is supplied with a restrictor orifice in the inlet and outlet ports With these o...

Страница 4: ...n accepted wiring enclosure See Figure 6 NOTE Draft spillage switches must be mounted 90 degrees apart and mounted opposite from the vent outlet direction See Figure 7 3 Mount the two spillage switche...

Страница 5: ...be protected by an overcurrent circuit device rated at 15 amperes CAUTION must be taken to ensure that the wiring does not come into contact with any heat source All line voltage and safety control ci...

Страница 6: ...diagram Wire the venter motor and controls in accordance with the National Electrical Code manufacturer s recommendations and or applicable local codes Units must be grounded Check ground circuit to m...

Страница 7: ...ll for heat with the venter inoperative Allow approximately 2 minutes of flue gas spillage for the spillage switches to sense the spillage and disrupt the thermocouple circuit halting the gas flow to...

Страница 8: ...0 Rev K 01 18 This manual may be downloaded and printed from the Field Controls website www fieldcontrols com WARRANTY For warranty information about this or any Field Controls product visit www field...