Field Controls 46229000 Скачать руководство пользователя страница 7

C

LASS 

B A

ND 

C

LASS 

L D

OUBLE 

W

ALL 

V

ENT 

P

IPE 

I

NSTALLATION

 

(Follow vent pipe manufacturer's listed or recommended clearances from 
combustible material.) 

5.  Using a hand crimper or a like device, crimp the inner pipe of the SWG 

power venter approximately 1" long. (See Figure 8) 

6.  Attach the vent pipe over the crimped end of the SWG power venter 

inner pipe. 

7.  Secure the vent pipe to the SWG power venter inner pipe with at least 

(3) three #8 sheet metal screws. Predrilling the holes through both pipes 
will allow easier fastening. 

WIRING 

NOTE:

 

Refer to appropriate control kit for proper installation instructions.

 

Wire the power venter motor and controls in accordance with the National Electric Code and applicable local codes. UNIT 
MUST BE GROUNDED. Check ground circuit to make certain that the unit has been properly grounded. The wiring 
should be protected by an over-current circuit device rated at 15 amperes. CAUTION MUST be taken to ensure that the 
wiring does not come in contact with any heat source. All line voltage and safety control circuits, between the power 
venter and the appliance, MUST be wired in accordance with the National Electrical Code for Class 1 wiring or equivalent. 

AIR FLOW ADJUSTMENTS 

In order to obtain proper system draft, the power venter has an airflow adjustment damper built-
in. When used in a system with a barometric draft control, this damper should be used to make 
coarse draft adjustments while the barometric should be used for finer adjustments. Loosen the 
locking screw on the air flow adjustment damper on the outer pipe of the power venter. (See 
Figure 9) Adjust the adjustment damper to the full open position. Follow appliance manufact-
urer's procedures for starting the heating appliance. Then adjust the thermostat to call for 
"Heat". After the system has operated for several minutes to stabilize flue gas temperatures, 
check for negative draft or up-draft at the heating appliance outlet or air flow into the draft hood. 
Use a draft gauge, velocity meter or match test procedure. Adjust the adjustment damper 
closed to obtain the minimum air flow required to maintain draft. Then increase air flow slightly 
(10% over minimum air flow rate) to ensure proper venting. For gas-fired power burners, adjust 
draft to proper over-fired draft. If using a barometric draft control, use the draft control to fine 
tune the system draft. If proper  draft has been established, tighten the adjustment locking 
screw. Shut off thermostat and check for residual heat spilling from draft hood. If this occurs, a 
post purge system may be required. If so, use a Field Controls PPC-5 Electronic Post Purge or 
a  Control Kit which includes one. Before installing, refer to the General Installation Inspection to check for negative 
pressure problems in the building. If sufficient combustion air for the burner is not provided, a flow reversal during the off 
cycle could occur within the venting system. This may cause combustion problems as well as condensation that could 
block the air pressure sensing tube. It may also contribute to premature motor failure. Combustion, and/or make-up air, 
should be supplied from outside the structure and the air inlet should be on the same wall as the power venter discharge. 
For example, tightly constructed homes and homes retro-fitted from electic heated systems are more likely to experience 
combustion and/or make-up air problems. For further information consult "The Field Report  - Effects of insufficient 
combustion air on draft and heating systems." Refer to the appropriate control kit installation instructions for pressure 
switch adjustment procedure and system checkout procedures before operating continuously. 

NOTE:

 

After proper venting 

has been established, it is recommended that a combustion test and a check for CO levels be performed to ensure 
maximum burner efficiency.

 

Figure 8

Figure 9

Page 7 

Содержание 46229000

Страница 1: ...ivates the power venter at the same time as the burner fires 3 After the heating requirement has been satisfied the thermostat circuit will open and de activate the burner and power venter circuit 4 For venting system equipped with a post purge device the power venter operates for a period of time after the burner has shut off to purge remaining flue gases CONTROL KITS CK 41 For operation with gas...

Страница 2: ...tained from combustible materials Class B Vent Pipe should be used for gas appliances and Class L Type Vent Pipe for oil appliances Refer to national or local codes for guidelines 5 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 6 This equipment is designed to overcome minor negative pressure conditions To ensure extreme negative pressure ...

Страница 3: ...zing based on appliance maximum input rate not actual firing rate Do not exceed maximum BTU HR input rating or maximum oil GPH input For multiple venting system applications add the input for each appliance Category I gas fired draft induced systems require an SWG 4 HD or larger Category III gas fired draft induced systems require an SWG 5 or larger PROCEDURE FOR CALCULATING TOTAL EQUIVALENT PIPE ...

Страница 4: ... insure that the motor and blower wheel rotate freely DO NOT install if any damage is apparent Refer to unit sizing chart to check proper venting sizing 2 Location of the termination of the venting system should be installed in accordance with the National Fuel Gas Code A N S I Z223 1 and or manufacturer s recommendations which are applicable See requirements below or refer to installation locatio...

Страница 5: ...ing should be cut so that the unit mounts directly on the wall board to provide a stable support If the siding is greater than 1 2 thick use a spacer plate or board behind the power venter mounting plate See Figure 4 NOTE If mounting the power venter through a combustible wall material and the flue gas temperature is above 400 F at the power venter inlet line the square hole with a piece of corros...

Страница 6: ...The horizontal section of the vent pipe should have a slight upward slope from the appliance to the power venter For clearances to combustible materials multiple appliance venting and other installation requirements refer to the National Fuel Gas Code A N S I Z223 1 and or any applicable local codes or appliance manufacturer s installation instructions INSTALLATION USING SINGLE WALL VENT PIPE INST...

Страница 7: ... stabilize flue gas temperatures check for negative draft or up draft at the heating appliance outlet or air flow into the draft hood Use a draft gauge velocity meter or match test procedure Adjust the adjustment damper closed to obtain the minimum air flow required to maintain draft Then increase air flow slightly 10 over minimum air flow rate to ensure proper venting For gas fired power burners ...

Страница 8: ... Fuel Gas Code A N S I Z223 1 or any applicable local codes for guidance 3 Place in operation the appliance being inspected Follow the lighting instructions and adjust thermostat so appliance will operate continuously 4 Determine that the pilot or burner is operating properly and that the main burner ignition operates satisfactorily by interrupting and re establishing the electrical power of the a...

Страница 9: ...er choke plate to insure it is secured in place Check the barometric draft control if installed to insure the gate swings freely 4 System Safety Devices With the heating system operating disconnect the pressure sensing tube from the pressure switch on the CK Kit This will stop the burner operation Re connecting the tube will relight the burner For 30 millivolt operating systems disconnect one lead...

Страница 10: ...e circular cover plate with the holes in the motor mount bracket on the motor assembly See Figure 12 2 Slide the motor assembly onto the protruding threaded studs on the venter body with the exhaust chute pointing downward and replace the four nuts securely to the threaded studs See Figure 12 3 Reattach the flexible conduit and wires to the motor and secure the cover on the electrical box 4 Instal...

Страница 11: ...Page 11 ...

Страница 12: ...PN 46229000 Rev A 08 00 ...

Отзывы: