REMOVAL AND INSTALLATION OF THE MOTOR ASSEMBLY 

R

EMOVAL

 

1.  Remove the motor enclosure cover by loosening the four screws. (See Figure 

10) 

2.  Open the electrical box on the motor and disconnect the conduit and wires from 

the motor. (See Figure 11)  

3.  Remove the four nuts securing the motor assembly, and pull the motor 

assembly straight off of the unit. (See Figure 12)  

4.  Clean off any build-up inside the blower wheel housing and the blower wheel. 

CAUTION:

 

Avoid applying excess pressure on the blower wheel when cleaning 

off any build-up of material. This will cause an imbalance of the blower wheel 
which will result in excessive vibration and premature motor failure.

 

I

NSTALLATION

 

1.  Align the holes in the circular cover plate with the holes in the motor mount 

bracket on the motor assembly. (See Figure 12) 

2.  Slide the motor assembly onto the protruding threaded studs on the venter body 

with the exhaust chute pointing downward, and replace the four nuts securely to 
the threaded studs. (See Figure 12) 

3.  Reattach the flexible conduit and wires to the motor and secure the cover on 

the electrical box. 

4.  Install the motor cover with the side louvers pointing downward. 

INITIAL BURNER AND VENTING SYSTEM OPERATIONAL INFORMATION 

List the following for each operating appliance on the sidewall venting system, as a 
guide for tune-up or service information annually. 

DATE:        

    

 

 

 

 

 

 

HEATING APPLIANCE BTU/HR. INPUT 

 

 

 

 

 

 

 

 

GAS VALVE OPERATION PRESSURE 

 

 

 

 

 

 

 

 

VENT SYSTEM DRAFT ABOVE DRAFT HOOD 
OR BEFORE BAROMETRIC DRAFT CONTROL 

 

 

 

 

 

 

 

 

CO

2

 MEASUREMENT 

 

 

 

 

 

 

 

 

CO MEASUREMENT 

 

 

 

 

 

 

 

 

EQUIPMENT OUTLET FLUE GAS TEMPERATURE   

 

 

 

 

 

 

 

 

Figure 10

Figure 11

Figure 12

Page 10 

Содержание 46229000

Страница 1: ...ivates the power venter at the same time as the burner fires 3 After the heating requirement has been satisfied the thermostat circuit will open and de activate the burner and power venter circuit 4 For venting system equipped with a post purge device the power venter operates for a period of time after the burner has shut off to purge remaining flue gases CONTROL KITS CK 41 For operation with gas...

Страница 2: ...tained from combustible materials Class B Vent Pipe should be used for gas appliances and Class L Type Vent Pipe for oil appliances Refer to national or local codes for guidelines 5 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 6 This equipment is designed to overcome minor negative pressure conditions To ensure extreme negative pressure ...

Страница 3: ...zing based on appliance maximum input rate not actual firing rate Do not exceed maximum BTU HR input rating or maximum oil GPH input For multiple venting system applications add the input for each appliance Category I gas fired draft induced systems require an SWG 4 HD or larger Category III gas fired draft induced systems require an SWG 5 or larger PROCEDURE FOR CALCULATING TOTAL EQUIVALENT PIPE ...

Страница 4: ... insure that the motor and blower wheel rotate freely DO NOT install if any damage is apparent Refer to unit sizing chart to check proper venting sizing 2 Location of the termination of the venting system should be installed in accordance with the National Fuel Gas Code A N S I Z223 1 and or manufacturer s recommendations which are applicable See requirements below or refer to installation locatio...

Страница 5: ...ing should be cut so that the unit mounts directly on the wall board to provide a stable support If the siding is greater than 1 2 thick use a spacer plate or board behind the power venter mounting plate See Figure 4 NOTE If mounting the power venter through a combustible wall material and the flue gas temperature is above 400 F at the power venter inlet line the square hole with a piece of corros...

Страница 6: ...The horizontal section of the vent pipe should have a slight upward slope from the appliance to the power venter For clearances to combustible materials multiple appliance venting and other installation requirements refer to the National Fuel Gas Code A N S I Z223 1 and or any applicable local codes or appliance manufacturer s installation instructions INSTALLATION USING SINGLE WALL VENT PIPE INST...

Страница 7: ... stabilize flue gas temperatures check for negative draft or up draft at the heating appliance outlet or air flow into the draft hood Use a draft gauge velocity meter or match test procedure Adjust the adjustment damper closed to obtain the minimum air flow required to maintain draft Then increase air flow slightly 10 over minimum air flow rate to ensure proper venting For gas fired power burners ...

Страница 8: ... Fuel Gas Code A N S I Z223 1 or any applicable local codes for guidance 3 Place in operation the appliance being inspected Follow the lighting instructions and adjust thermostat so appliance will operate continuously 4 Determine that the pilot or burner is operating properly and that the main burner ignition operates satisfactorily by interrupting and re establishing the electrical power of the a...

Страница 9: ...er choke plate to insure it is secured in place Check the barometric draft control if installed to insure the gate swings freely 4 System Safety Devices With the heating system operating disconnect the pressure sensing tube from the pressure switch on the CK Kit This will stop the burner operation Re connecting the tube will relight the burner For 30 millivolt operating systems disconnect one lead...

Страница 10: ...e circular cover plate with the holes in the motor mount bracket on the motor assembly See Figure 12 2 Slide the motor assembly onto the protruding threaded studs on the venter body with the exhaust chute pointing downward and replace the four nuts securely to the threaded studs See Figure 12 3 Reattach the flexible conduit and wires to the motor and secure the cover on the electrical box 4 Instal...

Страница 11: ...Page 11 ...

Страница 12: ...PN 46229000 Rev A 08 00 ...

Отзывы: