TROUBLE SHOOTING HINTS
1. Main burner does not fire when thermostat calls for heat with venter operating.
a. Check pressure switch adjustment.
b. Check fuel flow.
c. Check wiring connections between pressure switch and burner.
d. Check pressure switch for continuity across terminals, during venter operation.
2. Venter does not activate when thermostat calls for heat.
a. Jump wire the terminals L1 and M to ensure motor operation.
b. Check wiring.
3. Flue gas odor.
a. Check system draft.
b. Check post purge venting time.
c. Check for negative pressure in building.
MAINTENANCE
1.
Motor:
Inspect motor once a year; the motor should rotate freely.
2.
Wheel:
Inspect venter wheel annually, for oil fired heating systems, clear any soot, ash or coating which inhibits either
rotation or air flow. Remove all foreign material before operating.
3.
Vent System:
Inspect all vent pipe connections annually for looseness and for evidence of flue gas leakage. Seal or
tighten pipe connections if necessary.