REPLACEMENT ITEMS 

The following items are available for replacement.  Refer to Figure 
4 for guidance in locating and assembling replacement parts. 

PART NUMBER 

DESCRIPTION 

46297800 

Main Float and Switch Assembly 

46297900 

Overflow Float and Switch Assembly 

46298000 

Check Valve* 

46298100 

Impeller Assembly 

*NOTE:

 

The Check Valve includes an O-ring.

 

TROUBLESHOOTING 

I

F THE UNIT DOES NOT  FUNCTION PROPERLY

REFER TO THE 

FOLLOWING

 

1. 

Unit does not run: 
a. 

Check the power supply. 

b. 

Check the appliance to see if condensation is actually 
being generated. 

c. 

Check to make sure the pump float mechanism moves 
freely and clicks the activation switch when moved up 
and down. 

d. 

The motor is protected by a thermal overload device, 
which may have tripped.  This may be verified by 
measuring the resistance through the motor coil.  An 
open circuit reading indicates that the motor has 
overloaded, and the unit must be replaced. 

e. 

Check the drain line(s) into the pump for obstructions.  
Note: If these lines are clogged and remain clogged, the appliance may eventually be damaged. 

2. 

Pump makes loud noises when running: 
a. 

Check the tank for debris and clean if necessary.  The impeller may also be cleaned, if needed.  Refer to the 
maintenance section above for cleaning instructions. 

3. 

Unit runs but does not pump liquid out: 
a. 

Check the activation float to be sure it is not stuck in the up position. 

b. 

Check the height of the discharge tubing to be sure it does not exceed 20 vertical feet. 

c. 

Check the discharge tube for obstructions and clear if needed. 

d. 

Check the check valve for obstructions.  Refer to the maintenance section above for cleaning instructions. 

4. 

Liquid drains back into pump from discharge line: 
a. 

Check valve may have debris in it.  Refer to the maintenance section above for cleaning instructions. 

b. 

If the discharge line is plumbed so the highest point is less than 5 feet above the pump, the check valve may 
allow liquid to drain out of the line.  This is normal and will not damage the pump. 

5. 

Liquid leaks from around the check valve: 
a. 

If the check valve is too tight or too loose it may leak around the O-ring.  Check that the valve is hand tight, then 
tighten an additional 1/2 turn with a 9/16" wrench. 

b. 

If the O-ring under the check valve is damaged, replace with a 1/2" ID X 11/16" OD X 3/32" width O-ring, or 
purchase a replacement check valve, which includes an O-ring.  

Figure 4

Содержание 20+

Страница 1: ...RT NUMBER DESCRIPTION 20 UL 115VAC 60Hz 1 45 Amps 46296901 Base Model 20 ULS 115VAC 60Hz 1 45 Amps 46296902 Base Model with Overflow Safety Switch 20 ULT 115VAC 60Hz 1 45 Amps 46296903 Base Model with...

Страница 2: ...ible tubing or rigid pipe but must be no larger than 3 8 I D Extend the discharge line straight up from the pump to the highest point possible without exceeding the head GPH capacity of the pump befor...

Страница 3: ...ble insulated product is marked with the words DOUBLE INSULATION OR DOUBLE INSULATED If the unit does not perform as stated in the above tests remove the two screws holding the cover from the deck and...

Страница 4: ...en running a Check the tank for debris and clean if necessary The impeller may also be cleaned if needed Refer to the maintenance section above for cleaning instructions 3 Unit runs but does not pump...

Страница 5: ...iliser un raccord en T pour joindre le tuyau de trop plein et le tuyau d vacuation principal avant qu ils p n trent dans la pompe Voir Le Sch ma 1 2 Brancher une ligne de d charge au clapet de retenue...

Страница 6: ...arme ENTRETIEN D UN APPAREIL DOUBLE ISOLATION Pour un produit double isolation deux syst mes d isolation sont fournis au lieu d une mise la terre Aucun dispositif de mise la terre n est fourni avec un...

Страница 7: ...ac e e V rifier s il y a obstruction de la des ligne s d vacuation dans la pompe Nota en cas d obstruction persistante il se peut que l appareil soit endommag 2 La pompe fait beaucoup de bruit lorsqu...

Страница 8: ...aporador o desde el generador es posible que sea necesario derivar el rebose y el desag e principal juntos antes de que entren en la bomba Ver Figura 1 2 Conecte una l nea de descarga a la v lvula de...

Страница 9: ...circuito de alarma SERVICIO A UN APARATO DE AISLAMIENTO DOBLE En un producto de aislamiento doble se suministran dos sistema de aislamiento en lugar de una puesta a tierra En un producto de aislamient...

Страница 10: ...r reemplazada e Verifique que no hayan obstrucciones en la s l nea s de desag e hacia la bomba Nota Si estas l neas est n tapadas y permanecen tapadas el aparato se perjudicar 2 La bomba hace mucho ru...

Страница 11: ...E LIMITE LA R PARATION OU AU REMPLACEMENT D UN PRODUIT D FECTUEUX SAUF SI LES DOMMAGES D COULENT DU FAIT QUE FIELD NE RESPECTE PAS LES LOIS F D RALES OU PROVINCIALES SUR LES GARANTIES FIELD N EST RESP...

Страница 12: ...Page 12 PN CONPUMP Rev C 08 00...

Отзывы: