FIAMM Energy Technology S.p.A           

     Installation & Operating Instruction -Technical Manual  

 

 Edition  03/2018 Rev.7 

these  instruments  will  be

 

different  to  the  values 

stated in FET Product Sheet.   

 

2.6.

 

Service life 

 

According to the main international standards a battery is 
considered  at  the  end  of  its  service  life  whenever 
delivering  less  than  80%  of  its  nominal  capacity.  The 
recommended  operating  temperature  range  is  between 
10°C  to  30°C  (FHT  range  peaks  up  to  45°C).  FET 
VRLA batteries can operate over a temperature range of 
–20 to +50°C and higher; operation at temperature higher 
than 20°C reduces life expectancy according to the graph 
in figure 4. 
 

 

Fig. 4: Expected service life vs. working temperature 

 

2.7.

 

Gassing 

 

All  Lead  Acid  Batteries  emits  gases  during  the  charge 
process. FET VRLA batteries have a high recombination 
efficiency  (>98%)  and  for  cells  operated  at  20°C  under 
normal  operating  conditions  venting  is  virtually 
negligible.  Laboratory  test  measurements  show  the 
following gassing rates: 

 

2 ml/Ah/cell/month at a float voltage of 2.27 V/cell 

 

10  ml/Ah/cell/month  at  a  recharge  voltage  of  2.40 
V/cell. 

The  quantity  of  gas  given  off  in  the  air  (it  basically 
consists  of  80-90%  hydrogen)  is  very  low  and  thus  it  is 
clear that FET VRLA batteries can be installed in rooms 
containing  electric  equipment  with  no  explosion  danger 
or  corrosion  problems  under  normal  conditions.  In  any 
case these rooms or cabinets must have natural or forced 
ventilation  and  not  be  fully  sealed.  Please  refer  to 
“VENTILATION”  for  information  on  required  air 
exchange. 
 
 
 
 
 

2.8.

 

Operation of batteries in parallel 

 

When  the  required  capacity  exceeds  the  capacity  of  a 
single  string  of  batteries,  it  is  possible  to  connect  more 
strings  in  parallel  paying  attention  to  the  following 
guidelines: 
 

 

in each string only cells or monoblocs of the same 
type,  model,  manufacturing  date  and  quantity 
should be used; 

 

a  symmetrical  layout  of  the  batteries  should  be 
designed  (i.e.  length  and  type  of  connector)  to 
minimize possible resistance variations; 

 

the  quantity  of  strings  in  parallel  should  be 
reasonable  in  terms  of  layout  and  application. 
Usually  4  strings  could  be  connected  in  parallel. 
However,  depending  on  strings  voltage  and 
cables length, a higher number of strings could be 
safely connected to reach required total capacity. 
 

2.9.

 

Open circuit voltage - State of charge 

 

The measurement of the open circuit voltage (battery has 
to  be  disconnect  from  charger  system  for  at  least  24 
hours) provides an approximate indication of the state of 
charge of the cells. 
 

 

Fig. 5: Approximate state of Charge versus Open circuit cell voltage 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

20

30

40

50

TEMPERATURE [°C]

0

20

40

60

80

100

120

B

a

tt

e

ry

 L

if

e

 (

%

)

1.95

2.00

2.05

2.10

2.15

0%

20%

40%

60%

80%

100%

O

pe

C

ir

cui

V

ol

ta

ge

 [

V

/c

e

ll.

]

State of Charge [%]

Содержание FET FG Series

Страница 1: ...Installation and Operating Instructions Technical Manual Valve Regulated Lead Acid Batteries AGM technology ...

Страница 2: ...erature 4 2 5 Internal impedance and short circuit current 4 2 6 Service life 5 2 7 Gassing 5 2 8 Operation of batteries in parallel 5 2 9 Open circuit voltage State of charge 5 3 CHARGING 6 3 1 Floating charge 6 3 2 Boost charge Recharge following a discharge 6 4 BATTERY INSTALLATION 7 4 1 Installation 7 4 2 Batteries installed into cabinet 7 4 3 Ripple 8 4 4 Battery room requirements 8 5 SAFETY ...

Страница 3: ...e internal pressure variations during battery operation This is further ensured by reinforced container walls and lids Handles have been designed for some batteries into the lids to facilitate handling 1 3 Separators The separators are made of glass microfiber mats by a special process which results in a high porosity with very small pore diameters to ensure maximum oxygen diffusion while maintain...

Страница 4: ...sed for FET battery range SLA FLB as well 1 8 Front Terminal Connections Suitable solid connectors made of copper thin or lead plated and covers made of ABS are provided to make a proper installation between blocs Designed for FET front terminal range FIT using a special L clamp SOLID CONNECTOR COVER L CLAMP 1 9 Remote Venting System RVS Most of FET AGM batteries are designed with an optional cent...

Страница 5: ... 12 FGL from 17 to 205 FIT from 40 to 195 FHT from 95 to 180 SLA from 25 to 2000 FLB from 26 to 235 2 4 Capacity in relation to the temperature The capacity available from a battery at any particular discharge rate varies with temperature Batteries which have to operate at temperatures different from the nominal 20 C need a higher or lower capacity as per the factor indicated in the following grap...

Страница 6: ...ity of gas given off in the air it basically consists of 80 90 hydrogen is very low and thus it is clear that FET VRLA batteries can be installed in rooms containing electric equipment with no explosion danger or corrosion problems under normal conditions In any case these rooms or cabinets must have natural or forced ventilation and not be fully sealed Please refer to VENTILATION for information ...

Страница 7: ...ltages to maximize the battery life over the range of temperatures between 20 and 60 C are shown in the figure 6 or using the formula 2 5mV cell C The normal float current observed in fully charged FET front terminal batteries at 2 27 VPC and a temperature of 20 C is approximately 0 3 mA Ah Because of the nature of recombination phenomena the float current observed in the case of the FET front ter...

Страница 8: ...s for connecting from one shelf to the one below will be applied once that all the blocs have been connected we would suggest to connect such inter shelf or inter row cable connectors at the final User s premises only 10 To ensure a good electrical contact between the bottom of each terminal and the connecting strap and at the same time to ensure that the threaded terminals are not damaged by exce...

Страница 9: ... provide easy access to each cell for inspection and general maintenance Suitable racks may be made of wood or metal with a coating of acid resistant paint If metal racks are used they must be fitted with rubber or plastic insulators to prevent the cells coming into contact with the metal To facilitate proper battery operation maintenance and care post a battery data card instruction table in a co...

Страница 10: ...ord individual block voltages on float once a year The blocks cells should be within 4 of the average at 20 C No corrective action is required in this case Maintaining a correct battery charging voltage is extremely important for the reliability and life of the battery So it is advisable to carry out a periodical checking of the overall float voltage to verify any possible defect of charger or con...

Страница 11: ...performances change decrease with battery age After switching off the rectifier discharge the battery for a time of 20 of that calculated discharge rate 4 During the discharge record at regular intervals cell block voltage battery temperature discharge current total battery voltage 5 For safety reason during the test assure that the total battery voltage remains above the minimum depending on disc...

Страница 12: ...d from harsh weather moisture and flooding Storage on a pallet wrapped in plastic material is permitted in principle However it is not recommended in rooms where temperature fluctuates significantly or if high relative humidity can cause condensation under the plastic cover With time this condensation can cause a whitish hydration on the poles and lead to high self discharge by leakage current Atm...

Страница 13: ...d an air outlet with a minimum free area of opening calculated by the following formula Q x 28 A with Q ventilation flow rate of fresh air m3 h A free area of opening in air inlet and outlet cm2 Note For the purpose of this calculation the air velocity is assumed to be 0 1 m s The air inlet and outlet shall be located at the best possible location to create best conditions for exchange of air i e ...

Отзывы: