     Installation & Operating Instruction -Technical Manual  

 

 Edition  03/2018 Rev.7 

6.

 

MAINTENANCE  

 

6.1.

 

Battery care 

 
GASES GIVEN OFF BY BATTERIES ON CHARGE ARE 
EXPLOSIVE! 
DO  NOT  SMOKE  OR  PERMIT  OPEN  FLAMES  OR  DO  
ANYTHING TO CAUSE SPARKS NEAR BATTERIES. 

 

 

1.

 

Keep the battery and surroundings clean and dry. 

2.

 

Make  sure  that  bolted  connections  are  properly 
tightened (INSTALLATION paragraph). 

3.

 

Usually  it  is  not  necessary  to  apply  grease  on  the 
bolts  and  connectors,  in  any  case  "No-oxide"  grease 
increase the protection against corrosion. 

4.

 

Should  any  corrosion  of  the  connections  occur 
because  of  spilled  acid,  etc.,  carefully  remove 
corrosion  materials,  thoroughly  clean  and  neutralize 
with diluted ammonia or baking soda. 

5.

 

Keep the battery at the recommended charge voltage 
(see CHARGING section).  

6.

 

The room in  which  the battery is installed should be 
well  ventilated  and  its  temperature  as  close  as 
possible to 20°C. 

7.

 

Do not try to open the cover valve.  
 

6.2.

 

Cleaning 

 
When  necessary,  batteries  could  be  cleaned  using  a  soft 
dry  antistatic  cloth  or  water-

moistened  soft  antistatic 

cloth  paying  attention  not  to  cause  any  ground

 

faults. 
No  detergent  or  solvent-based  cleaning  agents  or 
abrasive  cleaners  should  be  used  as  they  may  cause  a 
permanent  damage  to  the  battery  plastic  container  and 
lid. 

 

6.3.

 

Voltage checks 

 
All  voltage  measurements  should  be  made  when  the 
whole  battery  has  stabilized  on  floating,  at  least  7  days 
after  battery  installation  or  after  a  discharge/charge 
cycle. To facilitate voltage reading in the correspondence 
of  each  block  terminal  protection  covers  are  designed 
with  a  safe  and  proper  hole.  Measure  and  record 
individual  block  voltages  on  float  once  a  year.  The 
blocks/cells  should  be  within  ±4%  of  the  average  at 
20°C. 
No corrective action is required in this case. Maintaining 
a correct battery charging voltage is extremely important 
for the reliability and life of the battery. So it is advisable 
to  carry  out  a  periodical  checking  of  the  overall  float 
voltage  to  verify  any  possible  defect  of  charger  or 
connections. 
 

6.4.

 

Cell appearance 

 
Any  cells  showing  corrosion,  container  bulging,  high 
temperature  than  the  other  cells,  should  be  regarded  as 
suspect.    Such  cells  should  be  carefully  examined  and, 
expert advice should be obtained immediately from FET. 
 

6.5.

 

Pilot Cell 

 

 
For  regular  monitoring  of  the  battery  condition,  select 
one  or  more  cells  of  the  battery  as  a  "pilot"  cell(s);  for 
batteries  comprising  more  than  60  cells,  select  one  pilot 
cell for every 60 cells.  
 

6.6.

 

Periodic Inspections 

 
Written records must be kept of battery maintenance, so 
that  long-term  changes  in  battery  condition  may  be 
monitored.  The  following  inspection  procedures  are 
recommended: 
 
EVERY SIX MONTHS:  

 

Visual  inspection  on  cells/racks  (appearance, 
cracks or corrosion signs, electrolyte leakage...) 

 

Check and record the overall float voltage at the 
battery terminals (not at the charger!), 

 

Measure and record the pilot cell(s) voltage. 

 

room ventilation  
 

YEARLY:  

 

all the controls indicated at six months  

 

Check and record the voltage of all cells. 

 

Make sure all connection are torqued according 
to  connection  torque  table;  in  case  of  frequent 
high discharge current please consider to check  

 

Visual inspection on cells/rack (corrosion signs, 
etc…) 

 

clean the cells  
 
 

7.

 

APPLICABLE STANDARDS 

 

FET  Valve  Regulated  Lead  Acid  Batteries  comply 
with: 
 

 

IEC  60896  –Part  21  Stationary  lead-acid  battery 
Valve Regulated Type – Methods of tests;  

 

 

IEC 60896 –Part 22 S Stationary lead-acid battery 
Valve Regulated Type - Requirements 

 

 

EN  50272-2  Safety  requirements  for  secondary 
batteries  and  battery  installations  Part  2:  Stationary 
batteries. 

 

 

BS  6290-4  Lead-acid  stationary  cells  and  batteries. 
Specification for classifying valve regulated types. 
 

 

BS  6290-1  Lead-acid  stationary  cells  and  batteries. 
Specification for general requirements 

 

 
 
 
 
 

Содержание FET FG Series

Страница 1: ...Installation and Operating Instructions Technical Manual Valve Regulated Lead Acid Batteries AGM technology ...

Страница 2: ...erature 4 2 5 Internal impedance and short circuit current 4 2 6 Service life 5 2 7 Gassing 5 2 8 Operation of batteries in parallel 5 2 9 Open circuit voltage State of charge 5 3 CHARGING 6 3 1 Floating charge 6 3 2 Boost charge Recharge following a discharge 6 4 BATTERY INSTALLATION 7 4 1 Installation 7 4 2 Batteries installed into cabinet 7 4 3 Ripple 8 4 4 Battery room requirements 8 5 SAFETY ...

Страница 3: ...e internal pressure variations during battery operation This is further ensured by reinforced container walls and lids Handles have been designed for some batteries into the lids to facilitate handling 1 3 Separators The separators are made of glass microfiber mats by a special process which results in a high porosity with very small pore diameters to ensure maximum oxygen diffusion while maintain...

Страница 4: ...sed for FET battery range SLA FLB as well 1 8 Front Terminal Connections Suitable solid connectors made of copper thin or lead plated and covers made of ABS are provided to make a proper installation between blocs Designed for FET front terminal range FIT using a special L clamp SOLID CONNECTOR COVER L CLAMP 1 9 Remote Venting System RVS Most of FET AGM batteries are designed with an optional cent...

Страница 5: ... 12 FGL from 17 to 205 FIT from 40 to 195 FHT from 95 to 180 SLA from 25 to 2000 FLB from 26 to 235 2 4 Capacity in relation to the temperature The capacity available from a battery at any particular discharge rate varies with temperature Batteries which have to operate at temperatures different from the nominal 20 C need a higher or lower capacity as per the factor indicated in the following grap...

Страница 6: ...ity of gas given off in the air it basically consists of 80 90 hydrogen is very low and thus it is clear that FET VRLA batteries can be installed in rooms containing electric equipment with no explosion danger or corrosion problems under normal conditions In any case these rooms or cabinets must have natural or forced ventilation and not be fully sealed Please refer to VENTILATION for information ...

Страница 7: ...ltages to maximize the battery life over the range of temperatures between 20 and 60 C are shown in the figure 6 or using the formula 2 5mV cell C The normal float current observed in fully charged FET front terminal batteries at 2 27 VPC and a temperature of 20 C is approximately 0 3 mA Ah Because of the nature of recombination phenomena the float current observed in the case of the FET front ter...

Страница 8: ...s for connecting from one shelf to the one below will be applied once that all the blocs have been connected we would suggest to connect such inter shelf or inter row cable connectors at the final User s premises only 10 To ensure a good electrical contact between the bottom of each terminal and the connecting strap and at the same time to ensure that the threaded terminals are not damaged by exce...

Страница 9: ... provide easy access to each cell for inspection and general maintenance Suitable racks may be made of wood or metal with a coating of acid resistant paint If metal racks are used they must be fitted with rubber or plastic insulators to prevent the cells coming into contact with the metal To facilitate proper battery operation maintenance and care post a battery data card instruction table in a co...

Страница 10: ...ord individual block voltages on float once a year The blocks cells should be within 4 of the average at 20 C No corrective action is required in this case Maintaining a correct battery charging voltage is extremely important for the reliability and life of the battery So it is advisable to carry out a periodical checking of the overall float voltage to verify any possible defect of charger or con...

Страница 11: ...performances change decrease with battery age After switching off the rectifier discharge the battery for a time of 20 of that calculated discharge rate 4 During the discharge record at regular intervals cell block voltage battery temperature discharge current total battery voltage 5 For safety reason during the test assure that the total battery voltage remains above the minimum depending on disc...

Страница 12: ...d from harsh weather moisture and flooding Storage on a pallet wrapped in plastic material is permitted in principle However it is not recommended in rooms where temperature fluctuates significantly or if high relative humidity can cause condensation under the plastic cover With time this condensation can cause a whitish hydration on the poles and lead to high self discharge by leakage current Atm...

Страница 13: ...d an air outlet with a minimum free area of opening calculated by the following formula Q x 28 A with Q ventilation flow rate of fresh air m3 h A free area of opening in air inlet and outlet cm2 Note For the purpose of this calculation the air velocity is assumed to be 0 1 m s The air inlet and outlet shall be located at the best possible location to create best conditions for exchange of air i e ...

Отзывы: