![FGD FlameSpec IR3-HD Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/fgd/flamespec-ir3-hd/flamespec-ir3-hd_user-manual_2285567030.webp)
FlameSpec
IR3-HD
User Manual
F101V0020.05
For more information & Technical support: (+1) 714-671-8500 · [email protected]
25
6.8
Approvals
Note: All items are designed and tested to meet the relevant requirements.
•
Explosion proof:
o
ATEX: II 2 G D
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C<Ta<75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -55°C<Ta<85°C
o
IECEx:
Ex db IIB T5 Gb -50°C
≤
Ta
≤
75°C
Ex db IIB T4 Gb -50°C
≤
Ta
≤
85°C
o
FM & FMC:
Class I, Div. 1, Groups B, C & D; T4
Class I, Zone 1, AEx/Ex db IIB T4 Gb
T4 -50°C
≤
Ta
≤
85°C
T5 -50°C
≤
Ta
≤
75°C
•
Performance:
o
ANSI FM 3260
o
EN 54-10
•
Functional safety: Complies to SIL 2 per IEC 61508
•
DNV GL
Designed to meet Standard DNVGL-CG-0339 for open deck locations
Temperature class D; Vibration Class A, B and C
•
EAC CU TR
6.9
Electromagnetic Compatibility
The detector fully complies with EMC directive 2014/30/EU and protected against interference caused by RFI
and EMI. The cables to the detector must be shielded and the detector must be grounded in order to comply