FlameSpec
IR3-HD
User Manual
F101V0020.05
For more information & Technical support: (+1) 714-671-8500 · [email protected]
10
3
Configuration options
Some functions of the detector can be configured using an RS-485 modem connected to a computer
with
the “FDG
communicator”
software. These configuration options are listed in the following table
along with their factory default values.
T
ABLE
1:
D
ETECTOR
C
ONFIGURATION
O
PTIONS
Function
Options
Default Setting
Sensitivity
Low, Medium, High, Extreme
Medium
Ultra-fast detection
Disabled, Enabled
Disabled
Alarm delay
0, 5, 10, 20 or 30 seconds
0 seconds (no delay)
Alarm latch
Disabled, Enabled
Disabled
Window heater
Disabled, Enabled
Enabled
Video module
Disabled, Enabled
Enabled
Post alarm video recording duration 1, 2 or 3 minutes
1 minute
Video analog output
Disabled, NTSC, PAL
Disabled
Modbus address
1
–
247
1
Manual BIT
–
Alarm Output Test
Disabled, Enabled
Disabled
•
Note:
Medium sensitivity setting allows detection of a 1x1ft
2
(0.1m
2
) N-heptane pan fire at a
distance of 100ft (30m).