PowerWizard 1.0 & 2.0 Control Systems User Manual

4.2  Technical Operation

4.2.1  Engine Starting Sequence

1.  The PowerWizard receives an engine start signal. The signal will be one of four:
  •  The operator presses the Run key
  •  The control is in auto and the remote initiate digital input becomes active
  •  The control receives a start command via the RS-485 SCADA Data Link (PowerWizard 2.0 only)
  •  The control has a program cycle timer (PCT) configured that becomes active (PowerWizard 2.0 only).

2.  The PowerWizard checks the system before beginning the cranking sequence. The PowerWizard checks that there   
  are no shutdown events present and that all previous shutdown events have been reset. 

3.  If the engine is equipped with a form of start aid such as thermostart it will enter a pre-start sequence.

4.  The PowerWizard begins the crank sequence by activating the engine crank relay and the fuel control relay:
  •  If the engine reaches the setpoint for crank terminate speed the engine is deemed running and the engine crank  
    relay will be deactivated
  •  If the engine fails to start within a preset duration (normally seven seconds) the PowerWizard will stop cranking   
    and wait for a pre-set time (normally seven seconds) before attempting to start again 
  •  If the PowerWizard fails to start within a pre-set number of crank attempts (normally three) the PowerWizard will  
    activate a “Fail to Start shutdown”.

4.2.2  Engine Stopping Sequence

1.  The PowerWizard receives an engine stop signal. The signal will be one of four:
  •  The operator presses the Stop key
  •  The control is in auto and the remote initiate digital input becomes inactive
  •  The control receives a stop command via the RS-485 SCADA Data Link (PowerWizard 2.0 only)
  •  The control has a program cycle timer (PCT) configured that becomes inactive (PowerWizard 2.0 only).

2.  The PowerWizard begins the cool-down period. In order to bypass the cool down hold down the Stop key for three 
  seconds.  The options “PRESS ENTER TO BYPASS” and “PRESS ESCAPE TO CONTINUE” will be shown on the 
  display. Press the Enter key to bypass the cool down sequence or press the Escape key to continue the cool down 
  sequence.

3.  After the cool down cycle, the PowerWizard stops the engine by turning off the fuel control relay.

4.2.3  Event System

The PowerWizard module uses the J1939 standard format for events, whereby an event is defined as a combination of 
a suspect parameter number (SPN) and a failure mode identifier (FMI). The SPN defines what is at fault and the FMI 
defines how it is at fault (e.g. SPN = Oil Pressure, FMI = Low Shutdown would mean the set has shutdown on a low 
oil pressure fault). 

PowerWizard modules have separate event logs for events raised by the module itself and those raised by ancillaries 
such as the engine ECM.

13

Содержание PowerWizard 1.0

Страница 1: ...PowerWizard 1 0 2 0 Control Systems User Manual PowerWizard 1 0 2 0 Control Systems User Manual...

Страница 2: ...rmation Most accidents that involve product operation maintenance and repair are caused by failure to observe basic safety rules or precautions An accident can often be avoided by recognizing potentia...

Страница 3: ...owerWizard Menu Trees 11 4 1 1 PowerWizard 1 0 Menu Tree 11 4 1 2 PowerWizard 2 0 Menu Tree 12 4 2 Technical Operation 13 4 2 1 Engine Starting Sequence 13 4 2 2 Engine Stopping Sequence 13 4 2 3 Even...

Страница 4: ...wo versions PowerWizard 1 0 and PowerWizard 2 0 These two versions are based on different features This guide is intended to cover the PowerWizard Generating Set Control and its application in generat...

Страница 5: ...ta Link SCADA RS485 Modbus Remote Monitoring and Control 1 2 Applications The PowerWizard range of generating set control systems is designed for use in a variety of applications The control systems c...

Страница 6: ...ard Control Module Description Figure 2 PowerWizard Control Module Description Display screen AC overview hot key DC overview hot key Warning lamp Shutdown lamp Alarm acknowledge Lamp test Run Auto St...

Страница 7: ...rWizard 1 0 2 0 Control Systems User Manual 7 2 Basic Operation 2 1 START Mode 2 2 STOP Mode 2 3 AUTO Mode Figure 3 Basic Operation Start Stop and Auto Modes Press START Key Press STOP Key Press AUTO...

Страница 8: ...Control Systems User Manual 8 Figure 4 Basic Operation Fault Alarm Reset Process 2 4 Fault Alarm Reset Process 2 Fault Alarm Reset 3 Fault Alarm Reset 4 Fault Alarm Reset The display will show 1 Fault...

Страница 9: ...ng If the Escape key is pressed during setpoint programming none of the changes made on screen will be saved to memory Scroll Right The Scroll Right key is used during setpoint adjustment During numer...

Страница 10: ...re are acknowledged shutdown events active If there are any active shutdown events the red light will change from flashing red to solid red after the Alarm Acknowledge key is pressed Any condition tha...

Страница 11: ...2 1Hrs STOPPED AVG 481 V L L 324V 60 2Hz OR OR CONFIGURE SECURITY SETPOINTS ENG OPERATE HRS CONTROL AUTOMATIC START STOP AVR DESIRED VOLTAGE GOV DESIRED ENG SPD ENG MONITOR PROTECT BATTERY VOLT MON EN...

Страница 12: ...IG PRESSURES TEMPERATURES LEVELS OTHERS ENG PROTECT CONFIG PRESSURES TEMPERATURES LEVELS OTHERS WARNING AUTO RESET ENABLED STATUS ENABLED GEN MON PROTECT GEN AC MONITOR GEN AC PWR MONITOR GEN OVER CUR...

Страница 13: ...within a pre set number of crank attempts normally three the PowerWizard will activate a Fail to Start shutdown 4 2 2 Engine Stopping Sequence 1 The PowerWizard receives an engine stop signal The sig...

Страница 14: ...s first active events next and inactive events last Within these classifications they are ordered by engine run hours or real time clock on PowerWizard 2 0 4 Press Enter after highlighting an event to...

Страница 15: ...vel is displayed Within the security menu are the following options DROP TO MINIMUM LEVEL used to return the current security level to the lowest level set up Highlight and press Enter to drop to mini...

Страница 16: ...es with Electronic Fuel Lift Pump Certain engines fitted with an electronic fuel pump do not have a manual priming feature on the engine In these circumstances the PowerWizard can be used to energise...

Страница 17: ...run the generating set Output 2 can be used to drive relay output 8 4 6 1 PCT Status The status of the PCTs can be found within the menu structure at MAIN MENU CONTROL PROG CYCLE TIMER The top row di...

Страница 18: ...enerating sets at rest or storage for prolonged periods should either have the battery charger or isolator switch option fitted Remote Annunciation of Faults The PowerWizard Annunciator is used in rem...

Отзывы: