background image

Display and operating components

2

1

1

LED (green) POWER

2

LED (red) ERROR

Fig. 20

8

Maintenance and care

For cleaning:
 Switch off the following energy sources before cleaning the exterior of the

device:
– operating voltage
– compressed air

 If the VPPM is dirty, clean the exterior with a soft cloth.
The permitted cleaning agents are mild soapy water (max. +50 °C) or all non-abras­
ive media.

9

Disassembly

For disassembly:

 Switch off the following energy sources:

– operating voltage
– compressed air

 Disconnect the relevant connections from the VPPM
 Remove the VPPM from the mounting surface/H-rail.

10

Accessories

è

 www.festo.com/catalogue

11

Safety setting

Wire break

IO-Link

Data communication

The last value is saved. In the medium term, the pressure at the
output can increase or diminish.

Supply voltage

The last value is saved. The outlet pressure is maintained unregu­
lated. In the medium term, the pressure at the output can increase
or diminish.

Fig. 21

12

Error messages

 Cause

Status of the LED indicators

LED (green) POWER

LED (red) ERROR

Communication inactive

Lights up

Off

Communication active

Flashes 1 Hz (9:1)

Off

Error / diagnostics

Off

è

 Fig. 23

Internal error

Off

Flashes (5 Hz)

Fig. 22

Error number

Manual

Status of the red LED indicators
ERROR

0x5100

Undervoltage < 18 V

Lights up

0x8CA1

Lower limit undershot

Off

0x8CA2

Upper limit exceeded

Off

0x8C42

Condition counter limit value ex­
ceeded

Off

0x6320

Error in parameterisation upper/
lower value

Lights up only if parameterised:
– Lower limit < 0
or
– Upper limit < lower limit

Fig. 23

Malfunction

Possible cause

Remedy

VPPM does
not react

Supply voltage not applied, POWER
LED does not light up

Check connection of the 24 V DC
supply voltage.

Data communication lacking

Check control unit and connection.

Flow rate too low

Restriction of the flow cross section
due to connection technology (swivel
fittings), POWER LED lights up

Use alternative connections.

Malfunction

Possible cause

Remedy

Pressure rise
too slow

Large cylinder volume and long tube
length

Select another parameter set.

Pressure
constant
despite
modified
setpoint
specification

Break in supply cable 
The last outlet pressure set remains
unregulated. In the medium term, the
pressure at the output can increase or
diminish.

Replace supply cable.

Inlet pressure too low p1

Increase inlet pressure.

Failure of data communication

Replace data transmission line.

Fig. 24

13

Technical data

VPPM

2 bar
29 psi

6 bar
87 psi

10 bar
145 psi

Design

Propor tional pressure regulator

Mounting position

Any, preferably flat (display components facing upwards)

Operating medium

Compressed air in accordance with ISO 8573-1:2010 [7.4.4],
with use of ester oil, compressed air in accordance with
ISO 8573-1:2010 [-:-:2]

Inert gases

Pressure ranges

– Supply pressure p1

[bar]

Max. 4

Max. 8

Max. 11

– Control range

(output pressure)
p2

[bar]

0.02 … 2

0.06 … 6

0.1 … 10

The inlet pressure p1 must be at least 1 bar higher than
the outlet pressure p2.

Total leakage when new

[l/h]

< 5

Ports

G

x

", G

¼

" , G

½

"

Nominal size

– Pressurisation

[mm]

Size 

x

": 6

Size 

¼

": 8

Size 

½

": 12

– Venting

[mm]

4.5 (at 

x

"), 6 (at 

¼

"), 12 (at 

½

")

Degree of protection

IP 65 when mounted, with tightened mounting screws,
in combination with plug socket according to accessories.

Permissible temperature range

– Environment

[° C]

0 … +60

– Medium

[° C]

+10 … +50

– Storage

[° C]

–10 … +70

Electrical connection

Pin contact M12x1, 5-pin

Permissible operating
voltage

[V DC]

18 … 30 (permissible residual ripple 1.3 Vpp (IEC61131-9)

Max. electrical power consumption

– Size 

x

 

and

 

¼

[W]

7

– Size 

½

[W]

12

Max. perm. supply and
signal line length

[m]

20

Overall accuracy
– Class S1

(1 %) +0.5 x hysteresis

[bar]

0.025

0.075

0.125

Hysteresis

0.5 % full scale

IO-Link type VPPM-...-LK-S1
– Cable characteristics

Observe IO-Link-specific data

IO-Link specification

Associated IO-Link IODD (

è

 www.festo.com/sp)

– V1.0

V1.1

– V  1.1

V1.1

Data rate

Suppor ts all IO-Link data transmission rates

Electromagnetic Compatibility 

1)

– Emitted interference
– Interference immunity

See declaration of conformity 

è

 www.festo.com

CE conformity for industrial installations fulfilled

Vibration and shock

The following specifications do not apply for mounting
the VPPM in-line valve to the bracket VAME-P1-A.

– Vibration

Tested in accordance with DIN/IEC 68/EN 60068 parts 2-6;
for wall mounting: Path 0.35 mm at 10 ... 60 Hz, 5 g
acceleration at 60 ... 150 Hz

– Shock

Tested in accordance with DIN/IEC 68/EN 60068 parts 2-27;
for wall mounting: ±30 g at 11 ms duration; 5 shocks
per direction

Materials

– Housing

Wrought aluminium alloy: PAXMD6 GF50/gr-P

– Seals

Nitrile rubber

– Lubrication

Silicone-free

Weight

– Size 

x

[g]

400

– Size 

¼

[g]

560

– Size 

½

[g]

2050

Data of the UL certification

– Altitude of use

Up to 2000 m

1)

The valve is intended for use in an industrial environment. Outside of industrial environments,
e.g. in commercial and mixed-residential areas, actions to suppress interference may have to be
taken.

Fig. 25

Содержание VPPM-...-LK Series

Страница 1: ...ns Ensure that the compressed air is properly prepared è Technical data Pressurize your entire system slowly There will then be no uncontrolled movements Range of application and certifications In combination with the UL mark on the product the information included in this section is also applicable for compliance with the certification requirements of Underwriters Laboratories Inc UL for USA and ...

Страница 2: ...mand to ISDU parameter 0x0048 COM3 03 COM2 02 For I Port the data rate is always set to COM3 Power supply with 24 V DC is provided through the IO Link master Pressurize the VPPM with an input pressure at least 1 bar higher than the max imum desired output pressure An outlet pressure p2 proportionate to it is then set The following outlet pressure is then assigned to the setpoint value signal Type ...

Страница 3: ...tting x value is unimportant for this setting Fig 13 Valve parameter Condition counter solenoid coil Parameter no 8 11 Condition counter limit Manual A limit value for a counter condition counter can be set for the internal solenoid coil in the pilot control of the pressure regulator A message is displayed if the limit value is exceeded which is sent to the IO Link master Bytes 11 or 8 High byte o...

Страница 4: ...t pressure Failure of data communication Replace data transmission line Fig 24 13 Technical data VPPM 2 bar 29 psi 6 bar 87 psi 10 bar 145 psi Design Proportional pressure regulator Mounting position Any preferably flat display components facing upwards Operating medium Compressed air in accordance with ISO 8573 1 2010 7 4 4 with use of ester oil compressed air in accordance with ISO 8573 1 2010 2...

Отзывы: