VOFA-L26-T32C-M-G14-1C1-...
52
Festo – VOFA-L26-T32C-M-G14-1C1-... – 1409NH English
6. Make sure that the “ISO” marking for unducted pilot exhaust air is visible for the inserted seal
(
Fig. 9).
If the “ISO” marking is visible: Re-insert the seal (
Fig. 9,
3
).
1
2
3
1
Inspection window on control side 12
2
The seal is visible in the inspection window
on control side 14
3
Identification label
When in the correct position, the “ISO”
marking is visible on the identification label.
Fig. 9
Position of the valve seal (here: Correct position for unducted pilot exhaust air)
7. Place the solenoid valve on the control block (
Fig. 10) and tighten the 2 mounting screws with an
Allen key (A/F 3) (permissible torque: 2 Nm ± 10 %).
8. Connect solenoid coils and proximity sensors (pin allocation
Tab. 2).
9. Carry out a performance test (
chap. 7) to ensure proper operation of the control block.