6. Multi I/O modules
6−5
Festo P.BE−CPX−EA−EN en 0705f
6.3
Installation
Warning
Sudden unexpected movement of the connected actuators
and uncontrolled movements of loose tubing can cause
injury to human beings or damage to property.
Before carrying out installation and maintenance work,
switch off the following:
the compressed air supply
the operating and load voltage supplies.
In the following sections you will find the pin assignments of
the multi I/O modules for the different sub−bases.
Instructions on connecting the cables and plugs to the sub−
bases can be found in section 3.2.3.
Power supply
The 24 V supply for the outputs is provided via the load
voltage outputs of the CPX terminal (V
OUT
).
The 24 V sensor supply for the inputs as well as the power
supply for the electronics of the multi I/O modules is pro
vided via the operating voltage supply for the electronics/
sensors (V
EL/SEN
).
Содержание VMPA...-FB-EPL Series
Страница 2: ......
Страница 22: ...Contents and general instructions XX Festo P BE CPX EA EN en 0705f ...
Страница 46: ...1 Pneumatic interfaces 1 24 Festo P BE CPX EA EN en 0705f ...
Страница 100: ...3 Overview and connecting technology I O modules 3 30 Festo P BE CPX EA EN en 0705f ...
Страница 101: ...Input modules 4 1 Festo P BE CPX EA EN en 0705f Chapter 4 Type CPX 4DE CPX 8DE CPX 8DE D CPX 16DE CPX M 16DE D CPX 8NDE ...
Страница 141: ...Output modules 5 1 Festo P BE CPX EA EN en 0705f Chapter 5 Type CPX 4DA CPX 8DA CPX 8DA H ...
Страница 171: ...Multi I O modules 6 1 Festo P BE CPX EA EN en 0705f Chapter 6 Type CPX 8DE 8DA ...
Страница 191: ...Technical appendix A 1 Festo P BE CPX EA EN en 0705f Appendix A ...
Страница 223: ...Index B 1 Festo P BE CPX EA EN en 0705f Appendix B ...
Страница 224: ...B Index B 2 Festo P BE CPX EA EN en 0705f Contents B Index B 1 ...