Festo VIFB13−..− 0208c English
14
2
Configuration
Please note
The cover is connected to the internal PC boards via the
operating voltage cable. It cannot therefore be removed
completely.
Caution
The components of the valve terminal contain elements
which are liable to damage by electrostatic charges.
The components can also be destroyed if the contact
surfaces of plug connectors are touched, or if the re
gulations for handling electrostatically vulnerable com
ponents are not observed.
Please observe the following when configuring:
1. Switch off the operating voltage.
2. Open node (screws are liable to be lost).
3. Set fieldbus address.
4. Activate voltage monitoring, if desired.
5. Close node.
6. If the valve terminal to be connected is at the end of
the PROFIBUS, the terminating resisitor in the Festo
Sub−D plug must be activated.