5.2.2

Product variants

Characteristic

Type code

Description

Basic function

VEAB

Piezo proportional-pressure
regulator

L

In-line valve

Valve type

B

Sub-base valve

Valve function

26

2x 3/2-way valve, normally
closed

D2

0 … 2 bar

D7

0 … 1 bar

D9

0 … 6 bar

D12

0 … 0.2 bar

D13

–1 … 1 bar

D14

–1 … 0 bar

D15

–0.5 … 0.5 bar

Pressure range

D18

–1 … 5 bar

F

Flange/sub-base

Pneumatic connection

Q4

Push-in connector 4 mm

V1

Voltage variant 0 … 10 V

Setpoint value input and actual
value output

A4

Current variant 4 … 20 mA

Nominal operating voltage

1

24 V DC

Electrical connection

R1

Plug M8, 4-pin

Tab. 2 Product variants

6

Transport and storage

Store the product in a dry, UV- and corrosion-protected environment.

Ensure short storage times.

7

Mechanical installation

1. Make sure there is sufficient space for the connecting cable and tubing con-

nections.

Ä

In this way you will prevent the connecting lines and the tubes from kink-
ing.

2. Place the valve as close to the consumer as possible.

Ä

This leads to improved control precision and shorter response times.

Mounting options of the valve:

Through-hold mounting of the in-line valve through 3 lateral through-holes

Mounting of the in-line valve to H-rails using H-rail mounting VAME-P7-T

è

 1 Further applicable documents

Mounting of the in-line valve to the mounting plate VAME-P7-Y

è

 1 Further applicable documents

Mounting of the sub-base valve using 2 through holes using the sub-base
VABM-.... 

è

 1 Further applicable documents

8

Installation

8.1

Pneumatic installation (in-line valve)

Valves for standard operation (overpressure)

1. Attach tubing to the following connections:

Compressed air connection (1) 

è

 Fig.3

Air connection (2) 

è

 Fig.2

2. Mount a silencer to the exhaust port (3) or remove the exhaust air with ducts

è

 Fig.3.

Valves for vacuum operation (reversible operation)

1. Attach tubing to the following connections:

Vacuum connection (3) 

è

 Fig.3

Air connection (2) 

è

 Fig.2

2. Mount silencer to the compressed air connection (1), to protect the valve from

coarse dirt particles 

è

 Fig.2.

Operating medium

NOTICE!

Pay attention to compressed air quality.

Damage to property or loss of function from lubricated compressed air.

Operate product only with unlubricated compressed air.

Observe the requirements for compressed air quality 

è

 Technical data.

8.2

Electrical installation

WARNING!

Risk of injury due to electric shock.

For the electric power supply, use only PELV circuits that ensure a reliable
electric disconnection from the mains network. 

Observe IEC 60204-1/EN 60204-1.

1. If a screened cable is used: earth the shield at the cable end farther away

from the valve.

2. Install electrical connecting cable without squeezing, kinking or stretching.
3. Screw electrical connecting cable onto the M8 plug connector. Tightening

torque maximum 0.3 Nm

Connection

Pin

Allocation

Wire colour

1)

(NEBU-M8...)

1

+ 24 V DC

BN

2

Setpoint value (+)

WH

3

GND

BU

4

Actual value (+)

BK

1) in accordance with IEC 757

Tab. 3 Pin allocation for plug M8, 4-pin

9

Commissioning

1. Check the operating conditions and limit values 

è

 Technical data.

2. Switch on compressed air supply.
3. Check pneumatic connection points for tightness.
4. Connect valve to a setpoint signal.
5. Switch on operating voltage.

10

Cleaning

1. Switch off the following energy sources to clean the outside:

Compressed air

Operating voltage

2. Clean the outside of the product with a soft cloth. Do not use aggressive

cleaning agents.

11

Malfunctions

11.1

Diagnostics

LED
indicator

Status and meaning

LED illuminates green:

Operating voltage is present and within the permissible range.

No error is present.

Setpoint signal lies in the permissible range (0 … 10.8 V or 2.5 … 20.5 mA).

LED flashes red:

Operating voltage lies above the permissible range (

>

29 V).

LED flashes alternately red and green:

Setpoint signal lies above the permissible range (

>

10.8 V or 

>

 20.5 mA).

Setpoint signal lies below the permissible range (

<

 2.5 mA).

LED is off:

No operating voltage applied.

Operating voltage lies below the permissible range (

<

 19 V).

Tab. 4 LED

11.2

Fault clearance

Fault description

Cause

Remedy

Operating voltage not applied 

Check operating voltage con-
nection.

No setpoint voltage 

Check controller and connec-
tion.

Valve does not react.

Compressed air supply not
present/insufficient

Check compressed air supply.

Flow rate is too low.

Restriction of the flow cross
section due to connection tech-
nology (swivel fittings).

Use alternative connection
technology.

Pressure remains constant des-
pite modified setpoint specific-
ation.

Supply cable breakage; the last
outlet pressure set is main-
tained but not regulated. Slow
pressure drop due to leakage.

Replace supply cable.

Setpoint value is not reached.

Inlet pressure p1 is too low.

Increase inlet pressure p1.
Maintain permissible maximum
operating pressure

è

 14 Technical data.

Tab. 5

12

Dismounting

1. Switch off setpoint voltage.
2. Switch off operating voltage.
3. Switch off compressed air supply.
4. Remove electrical connecting cables.
5. Remove compressed air lines.
6. Dismantle the product.