Festo SFAM-62 Скачать руководство пользователя страница 2

· Compare  the  maximum  values  specified  in  these  operating  instructions  with

your  actual  application  (e.g.  operating  media,  pressures,  forces,  torques,
temperatures,  masses,  speeds,  operating  voltages,  flow  rates).

· Take  into  consideration  the  ambient  conditions  at  the  location  of  use.
· Please  comply  with  national  and  local  safety  laws  and  regulations.
· Remove  all  transport  packing  such  as  protective  wax,  foils  (polyamide),  caps

(polyethylene),  cardboard  boxes  (except  for  the  sealing  elements  of  the
pneumatic  connections).
The  packing  is  intended  for  recycling  (except  for:  oiled  paper  =  other  waste).

· Use  the  product  in  its  original  state.  Unauthorized  modification  is  not  permitted.

4

Installation

4.1 Mechanical  assembly

The  mounting  position  is  horizontal 

±

5  %.  Fasten  the  SFAM  as  follows:

Fig.3

Note

Information  about  fitting  module  connectors,  sub−bases  and  mounting  brackets
can  be  found  in  the  operating  instructions  enclosed  with  the  relevant
accessories.

Combination  with  service  units  of  the  MS  series

The  SFAM  may  only  be  combined  with  service  units  of  the  MS  series  which  have  a
pneumatic  connection  of  at  least 

½

".

If  combined  with  an  existing  service  unit  of  the  MS  series:
1. Please  note  the  direction  of  flow.
2. Install  the  SFAM  only  after  service  units  which  conform  with  the  degree  of

filtration  (air  quality  class  5.4.3.:  40m  residual  dust,  +3°C  pressure  dew  point,
1mg/m´  residual  oil  content).

Note

The  SFAM  must  not  be  installed  directly  behind  a  pressure  regulator  or  filter
control  valve  to  comply  with  the  set  accuracies.
· Install  after  an  MS

Ū

−LFR  filter  control  valve  or  MS

Ū

LR  pressure  control  valve

an  MS

Ū

−FRM−1/2  distribution  before  the  SFAM.

3. Remove  the  cover  cap,  if  fitted,  from  the  side  to  be  combined  (push  upwards).
4. Place  the  module  connectors  type  MS

Ū

−MV  in  the  grooves  of  the  individual

units.  There  must  be  a  seal  between  the  individual  units.

5. Fasten  the  type  MS

Ū

−MV  module  connectors  with  2  screws.

4.2 Pneumatic  connection

The  air  mass  flow  is  routed  to  the  connection  where  the  sieve  cartridge  (on  type
SFAM−

Ū

−M)  or  the  starting  stretch  (on  type  SFAM−

Ū

−T)  is  situated.  The  air  mass

flow  is  taken  from  the  opposite  connection.
In  order  to  maintain  the  accuracy  of  the  specifications,  the  SFAM  must  be  supplied
via  an  inner  connection  diameter  of  at  least  10mm  or  via  a  pneumatic  connection
of  at  least 

½

".

Fig.4

4.3 Electrical  connection

Warning

Use  only  power  units  which  guarantee  reliable  electrical  isolation  of  the
operating  voltage  as  per  IEC/DINEN60204−1.  Observe  also  the  general
requirements  for  PELV  power  circuits  as  per  IEC/DINEN60204−1.
Switch  power  packs  are  permitted,  providing  they  guarantee  reliable  isolation  in
accordance  with  EN60950/VDE0805.

Note

Long  signal  cables  reduce  the  immunity  to  interference.
· Make  sure  that  the  signal  cables  are  shorter  than  10m.

Note

The  binary  outputs  at  pin2  and  pin4  can  be  wired  as  PNP  or  NPN  connections  as
needed.
· Make  sure  that  you  also  configure  the  binary  outputs  according  to  your  wiring

è

  Setting  special  menu  [SPEC]  section.

· Wire  the  SFAM  as  follows:

Pin

Assignment

Core  colours 

1)

Plug 

2)

1

DC  +24V  operating  voltage

brown  (BN)

5−pin  M12

2

Binary  outputsB  (OutB)

white  (WH)

1

3

0V

blue  (BU)

2

4

4

Binary  outputA  (OutA)

black  (BK)

5

2

4

5

Analogue  outputC  (OutC) 

3)

grey  (GY)

5

3

1)

With  use  of  the  connecting  cable  from  the  electrical  accessories 

è

chapter1.2Characteristics

2)

The  tightening  torque  for  the  union  nut  at  the  plug  is  max.  0.5Nm.

3)

Voltage  U  or  current  I 

è

  chapter  11,  Technical  specifications

Fig.5

Circuit  diagrams

SFAM−

Ū

−2SA

SFAM−

Ū

−2SV

Fig.6

5

Commissioning

1.

Switch  on  the  operating  voltage.

2.

Establish  the  desired  switching  behaviour  of  the  binary  outputs.

· With  flow  measurement  [FLW]:  Switching  points  [SP]  and  hysteresis  [Hy]

è

Fig.7.

· With  accumulated  air  consumption  measurement  [ConS],  only  with  OutA,

consumption  switch  impulse  [CI] 

è

Fig.8.

Switching  point  and  hysteresis  with  flow  measurement  for  OutA  /  OutB

Threshold  comparator

Window  comparator

Switch  element  function  NO  (closer)

q

1

0

Hy

OUT

SP

[l/min]

Hy

Hy

q

1

0

OUT

SP Lo

SP Hi

[l/min]

Switching  element  function  NC  (normally  closed)

q

1

0

SP

Hy

OUT

[l/min]

q

1

0

OUT

SP Lo

SP Hi

Hy

Hy

[l/min]

Fig.7

Содержание SFAM-62

Страница 1: ...tion SFAM T or combination with service units of the MS series SFAM M Measurement is carried out by means of a thermal procedure The amount of heat which is drawn from a heated surface of the sensor b...

Страница 2: ...ed to the connection where the sieve cartridge on type SFAM M or the starting stretch on type SFAM T is situated The air mass flow is taken from the opposite connection In order to maintain the accura...

Страница 3: ...pressing Edit button for 3 seconds or passage of a monitoring time timeout 1 Switch on the operating voltage The SFAM is in RUN mode 2 Check the settings of the SFAM chapter 5 3 SHOW mode 5 1 Symbols...

Страница 4: ...e CI switching element function no nc closer opener minimum flow value F Lo Flow Low In order to delete the minimum value press the EDIT button briefly maximum flow value F Hi Flow High In order to de...

Страница 5: ...Hy flashes 8 Set the value for the hysteresis Hy with the A B buttons 9 Press the Edit button to confirm the set value no or nc flashes 10 Select the switching element function no nc with the A B but...

Страница 6: ...oothing to d6 maximum smoothing With increasing smoothing the switch on switch off time of the switch outputs rises With d OFF the response time of the analogue output equals the set response time Sig...

Страница 7: ...be compared e g operating volume flow amount supplied by a compressor measured values of a flow sensor from another manufacturer refer to the same basic conditions After the power supply is switched...

Страница 8: ...Electronics Operating voltage range DC V 15 30 Protection against polarity reversal For all electrical connections Electromechanics Electrical connection Straight plug M12x1 5 pin Max length of connec...

Отзывы: