(V)PE-...-...(SW )
Festo (V)PE-...-...(SW) 2017-05c English
7
Electrical components
Using the (V)PE-... with screw terminals
2
and an operating voltage of ≥ AC/DC
50V:
Warning
You will receive an electric shock if you touch unprotected conductive compo
nents.
S
Make sure that the electrical connections are protected in accordance with IP
20 (as per EN 60529). A protective cap as per Accessories (see section 9) is
required here.
S
Wire the (V)PE-... as follows:
Connection
Screw ter
minal (see
Fig. 10)
Cable
co
lours
PE-...
VPE-...
Input
(common)
Input
(common)
1
black
(BK)
Normally-
closed
contact
Normally-
open
contact
2
grey
(GY)
Normally-
open
contact
Normally-
closed
contact
4
blue
(BU)
Fig. 11
Basic position PE-...
Basic position VPE-...
Fig. 12
The wire surface area of the connecting cable must be between 0.34 mm
2
and
1 mm
2
.
Fig. 10