Festo KBS-FEC FC30- 0206NH English
35
Digital inputs
Number
12 / 2 groups; 1 x 4 inputs, 1 x 8
inputs; both groups electrically
isolated from one another. The in-
puts in a group should be either
current-sinking or current-sourc-
ing.
Number of inputs that can be
used as high-speed counters
(max. 2 kHz)
2
Input voltage / current
24 V DC, input current 7 mA
1)
Value for TRUE
15 V DC min.
Value for FALSE
5 V DC max.
Input signal delay
typically 5 ms
Electrical isolation
yes, optocoupler
Permitted length of connecting
cable
max. 30 m
Status display with LED
yes
Insulation resistance against in-
ternal system voltage
Rated voltage of insulation: 50 V
AC
1)
The input voltages should be generated from electrical circuits from protection class
III. This requirement is fulfilled if the sensor supply voltage is used.