Festo — CPX-F8DE-P — 2022-10d
Diagnostics and error handling
73
–
Safe shut-down if a single microcontroller detects the failure of a component that is required to run
the program.
–
Passivation as a result of the incorrect setting of a function mode.
The input module can only transmit certain error messages as a function of the selected function
mode.
No.
Error message
Function mode
0
1
2
3
4
5
6
7
8
9
10
02
Channel error short circuit 24 V
–
–
–
✓
✓
–
✓
✓
✓
–
–
02
Modul error short circuit 0 V at
clock output T1357
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
03
Channel error wire break
–
–
–
–
✓
–
–
✓
–
–
–
05
Module error undervoltage
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
29
Channel error configuration
e.g. invalid function mode
–
–
–
–
–
–
–
–
–
–
–
55
Channel error process value
–
–
–
–
–
✓
✓
–
✓
✓
✓
61
Module error overvoltage
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
65
Module error F_DEST_ADD dif-
ferent
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
66
Module error communication
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
67
Module error communication
timeout
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
68
Channel error cross circuit
–
–
–
✓
✓
–
✓
✓
✓
–
–
69
Module fault parameters
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
75
Module error overtemperature
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
80
Channel error channel function
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
145
Module error in self-test
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Tab. 34: Error messages