Network status [NS]
1)
LED
(green,
red,
orange)
Meaning
Remedy
Off
The automation system CPX-E is offline.
No IP address assigned or no IP address
received from DHCP server.
Check network connection.
Check IP addressing settings.
1) The behaviour of the LED display depends on the network protocol used.
Tab. 12 Network Status [NS]
Connection/data traffic [XF1]/[XF2]
LED
(green)
Meaning
Remedy
Lights up
Network connection OK
–
Flashes
1)
Data traffic activity (traffic)
–
Off
No network connection
Check network connection.
1) The flashing frequency depends on the traffic.
Tab. 13 Connection/Data Traffic [XF1]/[XF2]
12
Disposal
ENVIRONMENT!
Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations
è
13
Technical Data
13.1
General Technical Data
General technical data
General technical data
Automation system CPX-E
Description of automation system CPX-E
è
Dimensions
(length × width × height)
1)
[mm]
125.8 × 37.8 × 76.5
Product weight
2)
[g]
145
Mounting position
Vertical/horizontal
Ambient temperature with
vertical mounting position
[°C]
–5 … +60
3)
Ambient temperature with
horizontal mounting position
[°C]
–5 … +50
3)
Storage temperature
[°C]
–20 … +70
Humidity (non-condensing)
[%]
0 … 95
Module code (CPX-E-specific)
222/36
Module identification
E-EP
Degree of protection in accordance with
EN 60529
IP20
The degree of protection is not UL-tested.
Protection against electric shock
(Protection against direct and indirect
contact in accordance with IEC 60204-1)
through the use of PELV circuits
(protected extra-low voltage)
Electromagnetic compatibility
to EN 61000-6-2/-4 and NE 21
Assigned address space (inputs/outputs)
Without diagnostics
[bit]
–/–
With status bits
[bit]
8/–
With I/O diagnostics inter-
face
[bit]
16/16
1) not including linking element
2) Including linking element
3) for non-conforming technical data see UL operating conditions table UL
Tab. 14 General Technical Data
Power supply
Operating power supply
U
EL/SEN
[V DC]
24
_
25%
Intrinsic current consumption
at nominal operating voltage
24 V from U
EL/SEN
[mA]
70
Reverse polarity protection
24 V U
EL/SEN
against 0 V
U
EL/SEN
Yes
Power supply
Mains buffering time
[ms]
20
Tab. 15 Power Supply
Network-specific Data
Protocol
EtherNet/IP, Modbus TCP
1)
Specification
EtherNet/IP
Transmission rate
[Mbps]
10/100 (full duplex/half duplex)
Crossover detection
Auto-MDI/MDI-X
Maximum cable length per
segment
[m]
100
2)
Cable specification
Cable type
Ethernet twisted pair cable, shielded
Transmission class
Category Cat 5/Cat 5e (link class)
Cable diameter
[mm]
6 … 8
Wire cross section
[mm
2
]
0.14 … …0.75; 22 AWG
3)
1) based on the Ethernet protocol IEEE 802.3
2) at a transmission rate of 100 Mbps
3) required for maximum connection length between network participants
Tab. 16 Network-specific Data
13.2
Technical Data UL/CSA Certification
Ambient conditions UL/CSA
Pollution degree
3
Installation site
for indoor use only
Max. installation height
[m]
2000
Tab. 17 Ambient Conditions UL/CSA
Ambient temperature
Mounting position
Vertical
Horizontal
Operating power supply U
EL/SEN
via XD
Ambient temperature, max. current rating
of terminal strip
£
4 A
[°C]
–5 … +60
–5 … +50
Ambient temperature, max. current rating
of terminal strip
>
4 … 8 A
[°C]
–5 … +50
–5 … +40
Operating voltage U
EL/SEN
with feed via both connections [XD]
1)
Ambient temperature, max. current rating
of terminal strip
>
4 … 8 A
[°C]
–5 … +60
–5 … +50
1) see chapter 'Product design' or 'Connection elements'
Tab. 18 Ambient temperature ranges