Festo — CPX-AP-A-EP-M12 — 2022-07
Parameterisation
35
Service
Name
Instance
Attribute
Data [0..1]
Data [2..n]
0x4F
Get Attribute
Single Conver-
sion / Get
Attribute All
Conversions
ISDU index
ISDU subindex
Slot
Conversion
data
0x50
Set Attribute
Single Conver-
sion / Set
Attribute All
Conversions
Conversion
data and values
Tab. 29: IO-Link service parameter object
8.1.15
Configuration assembly object
–
Object class: 0x8C
–
Services:
Tab. 31 Services for the configuration assembly object
Attribute
Access
Name
Data type
Description/value
Class attributes
1
Get
Revision
UINT
Revision of the object 1
2
Get
Max instances
UINT
Max. number of instances of the CIP
object
Dependent on the configuration of the
automation system
3
Get
Num instances
UINT
Number of instances of the CIP object
currently being created
Dependent on the configuration of the
automation system
6
Get
Max class attribute UINT
Max. number of class attributes 8
7
Get
Max instance
attribute
UINT
Max. number of class attributes 1
8
Get/Set
Descriptor
USINT
Actual total size of configuration
assembly instance data (configuration
assembly instance 140)