Festo — CPX-4AE-4AA-H — 2021-06b
Commissioning
Allocation and values 4828 + m* 64 + 33 (m = module number)
Bit
7
6
5
4
3
2
1
0
HART variable 3, HART variable 4
x
x
x
x
x
x
0
0
Source of HART variable 3 = PV (default)
x
x
x
x
x
x
0
1
Source of HART variable 3 = SV
x
x
x
x
x
x
1
0
Source of HART variable 3 = TV
x
x
x
x
x
x
1
1
Source of HART variable 3 = QV
x
x
x
x
0
0
x
x
Channel of HART variable 3 = channel 0
(default)
x
x
x
x
0
1
x
x
Channel of HART variable 3 = channel 1
x
x
x
x
1
0
x
x
Channel of HART variable 3 = channel 2
x
x
x
x
1
1
x
x
Channel of HART variable 3 = channel 3
x
x
0
0
x
x
x
x
Source of HART variable 4 = PV (default)
x
x
0
1
x
x
x
x
Source of HART variable 4 = SV
x
x
1
0
x
x
x
x
Source of HART variable 4 = TV
x
x
1
1
x
x
x
x
Source of HART variable 4 = QV
0
0
x
x
x
x
x
x
Channel of HART variable 4 = channel 0
(default)
0
1
x
x
x
x
x
x
Channel of HART variable 4 = channel 1
1
0
x
x
x
x
x
x
Channel of HART variable 4 = channel 2
1
1
x
x
x
x
x
x
Channel of HART variable 4 = channel 3
Tab. 30: Allocation and values of “IEEE variable of HART variable 3, HART variable 4” channel
parameter
Module parameter: Fail-Safe channel 0 … 3
Function number
Access to this module parameter is made via protocol-specific functions
è
Description of the bus node.