![Festo CMMP-AS-***-M0 Series Скачать руководство пользователя страница 186](http://html1.mh-extra.com/html/festo/cmmp-as-m0-series/cmmp-as-m0-series_manual_2283119186.webp)
7
Operating modes
186
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
7.3
Positioning Operating Mode (Profile Position Mode)
7.3.1
Overview
The structure of this operating mode is evident in Fig. 7.3:
The target position (target_position) is passed on to the curve generator. This generates a setpoint
position value (position_demand_value) for the position controller, which is described in the Position
Controller chapter (Position Control Function, chapter 6). These two function blocks can be set inde
pendently of each other.
position_factor
(6093
h
)
polarity
(607E
h
)
control_effor t
(60FA
h
)
Trajectory
Generator
Position_
demand_value
(60Fd
h
)
position
Multiplier
Limit
Function
[position units]
target_position
(607A
h
)
target_position
(607A
h
)
Trajectory
Generator
Parameters
Position Control
Law Parameters
Position
Control
Function
position_range_limit
(607B
h
)
software_position_limit
(607D
h
)
home_offset
(607C
h
)
Fig. 7.3
Curve generator and position controller
All input variables of the curve generator are converted with the variables of the factor group
(
chap. 5.3) into the internal units of the controller. The internal variables are marked here with an
asterisk and are normally not needed by the user.