Control system CECC
Festo AG & Co. KG
Postfach
73726 Esslingen
Germany
+49 711 347-0
www.festo.com
Brief description
8031102
1305a
[8031103]
Original: de
Control system CECC
English
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Caution
Damage to the device as a result of electric current and electrostatic discharge.
• Switch off the power supply before mounting/dismantling the device.
• Do not touch any components. Observe the handling specifications for elec-
trostatically sensitive devices.
• Only use power sources which guarantee reliable electrical isolation of the
operating voltage per IEC/EN 60204-1. Also observe the general requirements
for PELV power circuits as per IEC/EN 60204-1.
Note
Prior to commissioning the device
• Read the detailed description.
This can be found online at
www.festo.com/sp.
4
5
6
1
2
3
7
8
9
aJ
1
Ethernet interface
2
USB interface
3
Functional earth
’
4
CECC-LK: load voltage supply
infeed for IO-Link,
CECC-S: load voltage supply infeed
for IO-Link and encoder power
supply
5
Status LEDs
6
Communication interfaces:
CECC-LK: IO-Link
CECC-S: ENC, RS232, RS422,
RS485 and IO-Link
7
CANopen interface
8
Infeed for I/O power supply
9
I/O interfaces
aJ
Device power supply
Fig. 1 CECC-LK (example)
1
Intended use
The device is intended for
– use in an industrial environment
– installation in a control cabinet
• Please observe the additional information regarding intended use in the de-
tailed description
www.festo.com/sp.
2
Scope of delivery
– 1 CECC control system (variant D, LK or S)
– 1 plug connector, 4-pin
– 1 brief description
Software for the device can be found online at
www.festo.com/sp.
3
Accessories
Please select the appropriate accessories from our catalogue
www.festo.com/catalogue.
4
Installation
The device can be mounted on a H-rail or on a wall.
Caution
Damage to the device as a result of electric current.
• Switch off the power supply and loosen the cable joints before mounting/dis-
mantling the device.
• Mount the device in such a way that there is sufficient space for heat dissipa-
tion. Observe the temperature limit values (
9 Technical data).
aA
81
122.2
aB
aB
aA
Clip
aB
Mounting holes
Fig. 2
4.1 H-rail mounting
3. Insert the device into the H-rail.
4. Press the device in the direction of the arrow until it audibly engages.
4.2 Dismantling the H-rail
1. Unlock the device via the clip (Fig. 2
aA
).
To do this, use a suitable tool such as a screwdriver.
2. Remove the device from the H-rail.
4.3 Wall mounting
Note
Damage to the device caused by mounting on uneven or flexible surfaces.
• Only mount the device on an even, torsionally rigid surface.
1. Make sure there is sufficient clearance for the power supply cables.
2. Drill two 4.5 mm diameter mounting holes
aB
in the mounting surface (spacing
Fig. 2 hole pattern).
3. Secure the device to the mounting surface by using two M4 screws (max. tight-
ening torque: 0.8 Nm, max. screw head diameter: 7 mm).
4.4 Dismantling from the wall
1. Undo the two M4 screws.
2. Remove the device from the mounting surface.
5
Commissioning
Information regarding commissioning can be found in the detailed description
www.festo.com/sp.
6
Status LEDs
The device is equipped with the following status LEDs
Fig. 1
5
:
Status LED
Meaning
Status LED
Meaning
Run
Status of the application
Net
Device detected
Error
Error
Mod
Reserved
Fig. 3
7
Power supply
7.1 Device power supply
Pin
Signal
Comment
X1.1
24
U+ electronics
X1.2
0
U– ground
X1.3
’
Functional earth
X1.4
n.c.
not connected
Fig. 4
7.2 I/O power supply
Pin
Signal
Comment
X5.1
24
U+ I/O supply
X5.2
0
U– ground
Fig. 5