Festo CPV...−GE−ASI−8E8A−...−CE 0703NH English
2
1
3.4 Connecting sensors (PNP inputs)
Use cable type NEBU−... or KM8−M8−GSGD−... and plug
with union nut and M8x1 thread for connecting sensors.
Fasten the plugs/sockets with the aid of the union nut in
order to prevent unintentional loosening, e.g. due to
shock. Seal unused sensor connections with the protective
caps type ISK−M8.
O
nly in this way can you comply with
protection class IP65.
Note
The inputs have been designed in accordance with
IEC 1131−
2
type0
2
.
The inputs are short−circuit proof. In the event of a
short circuit the slave will be switched off. The
AS−Interface master then regards this slave as
missing. The slave reports back as functioning once
the short circuit has been eliminated.
1
Inputs of the first
slave
2
Inputs of the second
slave
3
Pin allocation:
1:
2
4 V
3:
0 V
4:
Input Ix
0
1
2
3
4
5
6
7
1
2
3
1
4
3