Festo CPV...−GE−ASI−8E8A−...−CE 0703NH English
16
2
Connecting and display elements
1 2 3
4
5
6
7
8
9
aJ
aB
aA
1
AS−Interface bus connection
2
Earth connection
3
Name plate
4
LED status display for inputs
(green)
5
Addr. selector button with LED (red)
6
Sensor connections (PNP)
7
Inscription fields for addresses
8
LED status display for
valves (yellow)
9
Valve plates slave
2
aJ
Valve plates slave 1
aA
Load voltage
connection for valves
aB
PWR LED (power, green),
Fault LED (fault, red)
PWR LED
Fault LED
Meaning
on
out
AS−Interface voltage applied, no fault
out
out
No AS−Interface voltage on the bu
s
flashes
on
AS−Interface address not set (= 0)
on
flashes
Short circuit/overload at the inputs or
address selector button actuated
on
on
Bus communication failed (watchdog expired)