4.3 Dati tecnici unità
4.3 unit technical data
MODELLO /
moDEl
40 40 E 75 75 E 100 100 E 150 150 E 200 200 E 320 320 E 400 E 500 E
Portata aria nominale /
Nominal air flow
m3/h
400
400 750 750
1000 1000 1500 1500 2050 2050 3200 3200 3800 4700
Pressione statica utile nominale /
Nominal external
static pressure
Pa
160
160 120 120
130
130
160
160
120
120
180
180
200
200
Pressione statica utile massima /
Maximum external
static pressure
Pa
160
340 120 210
130
520
160
500
120
540
180
375
330 200
Alimentazione elettrica /
Electrical power supply
V/ph/Hz
230 / 1 / 50
230 / 1 / 50-60
Potenza assorbita massima totale /
Total full load
power input
kW
0.35 0.56 0.68 0.56
1.41
2.12 1.41
2.12
1.41
2.12 3.29
2.35
2.07 2.07
Corrente assorbita massima totale /
Total full load
amperage
A
1.5
2.4
2.9
2.4
6.0
9.0
6.0
9.0
6.0
9.0
14.0 10.0
8.8
8.8
LIMITI OPERATIVI /
WoRKING lImITs
Condizioni di temperatura - umidità limite esterne /
Outdoor temperature - humidity working limits
°C / %
-5 … +45 °C / 5 … 95%
Condizioni di temperatura - umidità limite esterne con
accessorio RMS /
Outdoor temperature - humidity
working limits with RMS option
°C / %
-15 … +45 °C / 5 … 95%
Condizioni di temperatura - umidità limite interne /
Indoor temperature - humidity working limits
°C / %
+10 … +35 °C / 10 … 90%
VENTILATORI /
FANs
40 40 E 75 75 E 100 100 E 150 150 E 200 200 E
320 320 E 400 E 500 E
Tipologia motore /
Motor typology
AC
EC
AC
EC
AC
EC
AC
EC
AC
EC
AC
EC
EC
EC
N° velocità /
Number of speeds
(1)
3 Multiple 3 Multiple
3
Multiple 3 Multiple 3 Multiple 3 Multiple Multiple Multiple
Controllo ventilazione /
Fan control
(1)
Man 0-10V Man 0-10V Man 0-10V
VSD Man
0-10V
VSD Man
0-10V
VSD Man
0-10V
VSD
0-10V
VSD
0-10V
VSD
Potenza assorbita nominale totale /
Total nominal
power input
kW
0.17 0.16 0.38 0.30
0.52
0.49 0.80
0.76
1.00
0.84
1.79 1.77
1.78 2.19
Corrente assorbita nominale totale /
Total nominal
load amperage
A
0.7
0.7
1.6
1.3
2.2
2.1
3.4
3.2
4.3
3.6
7.6
7.5
7.6
9.3
RECUPERATORE DI CALORE /
HEAT EXCHAN-
GER
40 40 E 75 75 E 100 100 E 150 150 E 200 200 E
320 320 E 400 E 500 E
Efficienza termica invernale /
Winter thermal effic.
(3)
%
83.6% 83.6% 82.9% 82.9% 81.6% 81.6% 83.3% 83.3% 83.7% 83.7% 86.8% 86.8% 84.1% 84.2%
Potenza termica recuperata /
Heating recovery capa-
city
(3)
kW
2.76 2.76 5.13 5.13
6.73
6.73 10.30 10.30 14.14 14.14 22.90 22.90 26.34 32.62
Temperatura aria mandata /
Supply air temperature
(3)
°C
15.9 15.9 15.7 15.7
15.4
15.4 15.8
15.8
15.9
15.9 16.7
16.7
16.0 16.1
Efficienza termica estiva /
Summer thermal effic.
(4)
%
75.5% 75.5% 75.9% 75.9% 74.5% 74.5% 75.1% 75.1% 75.6% 75.6% 78.0% 78.0% 75.0% 75.1%
Potenza frigorifera recuperata /
Cooling recovery
capacity
(4)
kW
0.61 0.61 1.15 1.15
1.50
1.50 2.27
2.27
3.12
3.12 5.02
5.02
5.73 7.10
Temperatura aria mandata /
Supply air temperature
(4)
°C
27.5 27.5 27.4 27.4
27.5
27.5 27.5
27.5
27.5
27.5 27.3
27.3
27.5 27.5
Efficienza termica a secco /
Dry thermal efficiency
(5)
%
75.9% 75.9% 76.4% 76.4% 75.0% 75.0% 75.6% 75.6% 76.0% 76.0% 76.3% 76.3% 75.5% 75.6%
Livello di potenza sonora irradiato dall'involucro /
Sound power level (LWA)
dB(A)
58
57
61
60
61
59
64
61
64
59
68
64
66
68
(1) Multiple = Multivelocità > 3
Man = Manuale da selettore o tastiera; 0-10V = Da potenziometro o tastiera;
VSD = A portata costante o modulazione da sensore qualità/umidità aria
(2) Livello di potenza sonora alle condizioni di funzionamento nominali
(3) Aria esterna -5°C 80% UR; aria ambiente 20°C 50% UR
(4) Aria esterna 32°C 50% UR; aria ambiente 26°C 50% UR
(5) Secondo regolamento UE 1253/2014: alla pressione nominale;
condizioni di temperatura e umidità riferite a EN 308
(1) Multiple = Multispeed > 3
Man = Manual by selector switch or control panel; 0-10V = By potentiometer or control
panel; VSD = Constant flow control or modulation by air quality or air humidity sensor
(2) Sound power level at nominal working conditions
(3) Outside air at -5° 80% RH; room air at 20°C 50% RH
(4) Outside air at 32° 50% RH; room air at 26°C 50% RH
(5) Refeer to EU 1253/2014 regulation: at nominal pressure; air conditions refer to EN
308 standard