SUN G20 1S
29
Cod. 3540G302 - Rev. 01 - 02/2015
EN
VE
G
P
fig. 10a
VE
G
P
fig. 10b
3.2 Commissioning
Checks to be performed on first ignition, and after all maintenance operations that involve the discon-
nection of the appliance from systems or intervention on the safety devices or parts of the burner:
Before igniting the burner,
• Check that the burner is correctly fastened to the boiler, and the preliminary adjustments described
previously have been performed.
• Make sure that boiler and the system have been filled with water or diathermic oil, that the valves in
the water circuit are open and that the flue gas exhaust pipe is free and correctly sized.
• Check that the boiler door is closed, so that the flame only propagates inside the combustion cham-
ber.
• Fit the pressure gauge and the vacuometer to the pump (removed before operation).
• Open the gate valves in the oil pipes, making sure that there is fuel in the tank and that the return
pipe is not blocked.
Attention:
Blockages may cause the pump seal device to break.
Igniting the burner
• Connect electrical power by closing the main switch upstream of the burner
• Close the thermostat line (boiler/room)
• Reset the appliance (pressing the red button)
• Operation will start according to Figs. 10a and 10b and the diagram in Fig. 9:
1
The burner motor will start turning, together with the pump: the oil fed in is completely sent to the
return (Fig. 10a). The ignition transformer is activated at the same time.
2
The following phases are performed: pre-ventilation of the furnace, pre-washing of part of the oil
circuit, pre-ignition, with discharge between the tips of the electrodes.
3
At the end of the pre-washing phase, the appliance opens the electromagnetic valve (Fig. 10b): the
oil reaches the nozzle, from where it is sprayed. Contact with the discharge between the electrodes
ignites the flame. At the same time, the safety time starts, within which the photo cell must detect
the flame.
4
If the photo cell does not detect the flame, the burner shuts-down (the red light comes on).
Wait around 15 seconds, reset and repeat the ignition cycle.
In particular, with single-tube systems, if the fuel inlet pipe is initially empty, the air contained in the
pipe must be vented for the fuel pump to be primed. It is recommended, before igniting the burner,
to loosen the pressure gauge connection screw on the pump and then perform the ignition cycle.
When the oil comes out of the screw, the pump is primed. Switch off the burner and tighten the screw.
fig. 9
PRE
TS
PRE
TS
TR
TA - TC
VE
FR
MB
Tm
SB
PRE
TS
Shut-down signal
Thermostats
Preheater
trigger thermostat
Burner motor
Ignition transformer
Electromagnetic valve
Photo cell
Содержание SUN G20 1S
Страница 84: ...SUN G20 1S 84 Cod 3540G302 Rev 01 02 2015 RU 1 85 2 86 3 93 4 98 CE Ferroli CEE 92 42 2006 95 2004 108...
Страница 85: ...SUN G20 1S 85 Cod 3540G302 Rev 01 02 2015 RU 1 1 1 SUN G20 1S Ferroli SUNG201S CO NOx 1 2 10 C 1 3 3 1 4 15 1...
Страница 86: ...SUN G20 1S 86 Cod 3540G302 Rev 01 02 2015 RU 2 2 1 2 2...
Страница 91: ...SUN G20 1S 91 Cod 3540G302 Rev 01 02 2015 RU F L 5 3 5 6 5 C D F E B A I I 1 A 2 B 3 C 4 D 5 6 F 7 G 8 I 5...
Страница 92: ...SUN G20 1S 92 Cod 3540G302 Rev 01 02 2015 RU 2 5 4 230 50 6 L 5 3 5 6 5...
Страница 95: ...SUN G20 1S 95 Cod 3540G302 Rev 01 02 2015 RU 10 O2 O2 3 0 5 O2 3 3 10 A B E F D G C 11 G A B C D E F...
Страница 96: ...SUN G20 1S 96 Cod 3540G302 Rev 01 02 2015 RU 10 14 2 3 5 3 4...
Страница 97: ...SUN G20 1S 97 Cod 3540G302 Rev 01 02 2015 RU 10 14 10 14...
Страница 100: ......
Страница 101: ......
Страница 102: ......
Страница 103: ......
Страница 104: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it...