CONNECTIONS

Expansion tank setting

All the storage version units (VA) come complete with expansion tank and safety valve. The expansion tank prefilling pressure
must be adequate for the total volume of the plumbing system to which the unit is connected.
The factory setting (p

VE

= 2 bar g) corresponds to the minimum value necessary for avoiding negative pressure zones inside the

water circuit and the risk of pump cavitation, in the event no users are located above the level on which the unit is installed. In
this case the prefilling pressure must be increased according to the level of the highest user according to the following
relationship :

p

VE

: expansion tank prefilling pressure

[bar g]

H

max

:

height difference between the highest user and the unit installation level

[m]

When the prefilling pressure increases the maximum volume of the system supported by the expansion tank supplied standard
decreases. If the actual volume of the system is greater than that maximum value, an additional expansion tank of adequate
capacity must be installed.

,5ƒ&

,3ƒ&

S

9(

>EDUJ@

@O>

9

For units operating with water and glycols calculate the maximum value, applying the correction factors given in the following
table to values obtained from the graph.

The maximum expansion tank prefilling pressure corresponds to the safety valve setting value (6 bar g).
After the water circuit is filled, the pressure at the expansion tank must not be higher than the prefilling pressure.
In case of users located at levels below that on which the unit is installed, make sure the user can take the maximum pressure
generated.

glycol %

Ethylene glycols

Propylene glycols

10%

20%

30%

40%

10%

20%

30%

40%

IR (10-40°C)

0.738

0.693

0.652

0.615

0.700

0.608

0.543

0.494

IP (10-60°C)

0.855

0.811

0.769

0.731

0.814

0.718

0.647

0.593

Содержание RXA

Страница 1: ...RXA AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS TECHNICAL MANUAL...

Страница 2: ...2...

Страница 3: ...ICAL DATA 9 NOMINAL PERFORMANCE IR 10 NOMINAL PERFORMANCE IP 10 PERFORMANCE IN COOLING IR AND IP 11 PERFORMANCE IN HEATING IP 12 WEIGHTS OF UNITS 13 ELECTRICAL DATA 13 NOISE LEVELS 13 PRESSURE LOSSES...

Страница 4: ...4...

Страница 5: ...temperature in cooling mode and with high outdoor temperature in heating mode as well as to reduce noise emissions in such operating conditions All three phase power supply units are provided with a p...

Страница 6: ...e and to limit heat loss to the outside It is protected against the risk of ice forming by an antifreeze heating element activated according to the water temperature and by a differential pressure swi...

Страница 7: ...rface are accessible from the outside by opening a hermetic door The main components are main switch thermal magnetic microprocessor controller with user interface and incorporated phase cut card comp...

Страница 8: ...also substitute the tank antifreeze heating element accessory RAG Remote control CR The remote control is suitable for wall mounting and has all the control and display functions available on the unit...

Страница 9: ...ion speed 900 rpm Total installed power 0 15 0 21 0 42 kW Plate type heat exchanger Type braze welded plates Quantity 1 n Water content 0 29 0 29 0 46 0 46 0 46 0 46 0 53 0 72 l Finned coil Type coppe...

Страница 10: ...15 6 65 kW Total EER VB E 2 79 2 49 2 49 2 49 2 55 2 55 2 64 2 57 Water delivery 1032 1221 1582 1582 1823 1823 2339 2941 l h Pressure losses VB E 26 35 25 25 32 32 39 34 kPa Useful head VP VA 75 62 17...

Страница 11: ...pplied to the nominal performance values air 35 C bs air 12 7 C for obtaining the real performance values in the chosen operating conditions 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1 30 1 40 15 20 25 30 35...

Страница 12: ...he nominal performance values air 7 C bs 6 C bu water 40 45 C for obtaining the real performance values in the chosen operating conditions 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1 30 1 40 15 10 5 0 5 10 1...

Страница 13: ...8 5 8 5 8 6 7 6 7 8 4 10 1 kW M I C Total max peak current 49 8 68 8 89 1 48 1 121 1 51 1 67 1 70 1 A Supplementary electrical heating elements 3 3 kW F L A Total max absorbed current 14 3 14 3 14 3 4...

Страница 14: ...00 1500 2000 2500 3000 3500 4000 Portata l h Perdite di carico kPa 0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 500 1000 1500 2000 2500 3000 3500 4000 Portata l h Prevalenza residua kPa 7 1 6 1...

Страница 15: ...cellation of the product warranty contract Thermal head of water treated by the unit Minimum 3 C Maximum 8 C 10 5 0 5 10 15 20 25 30 35 5 0 5 10 15 20 25 30 35 40 45 50 55 Tbs aria esterna C T acqua p...

Страница 16: ...me 1 2 3 U M Model 6 1 7 1 9 1 11 1 14 1 17 1 Version VB VP VA VB VP VA VB VP VA A 903 1153 1453 mm B 509 759 1059 mm C1 570 820 1120 mm C2 545 646 946 mm C3 799 928 1228 mm D 839 1089 1389 mm E 142 9...

Страница 17: ...the refrigerating capacity input water delivery and pressure losses 3 Keep the unit electrically connected throughout the winter The plate type exchanger is protected by the antifreeze heating element...

Страница 18: ...efilling pressure increases the maximum volume of the system supported by the expansion tank supplied standard decreases If the actual volume of the system is greater than that maximum value an additi...

Страница 19: ...ed Protection upstream An automatic switch suitable for ensuring protection against overcurrents and indirect contacts must be installed upstream Coordination between the line and switch must be carri...

Страница 20: ...Cod 3QE23691...

Отзывы: