ADJUSTMENT AND CONTROL
Timer scheduling
The scheduling allows to set weekly time zones to obtain a reduce in energy consumption when the cooling or heating demand
is lower.
There are 3 time zones each one with 4 events per hour.
For each event, you can set hours and minutes of start and stop, an operating mode (Stand-by or ON), a cooling set point and
a heating set point.
ATTENTION: you can not change the operating mode via scheduling. The operating mode (cooling or heating) will be
the same adopted before the enabling of time scheduling.
To enable time scheduling you must set up the date and time into the controller
The parameters for the scheduling can be accessed in the “
tE
” (time event) folder.
Enabling
The function can be enabled with the parameters
tE00
– Enabling scheduling
Management time
For each day of the week you can select one of the 3 time zone available
For each time zone you can associate 4 events.
The parameters involved in time events are described below:
Event hour start time
It determines the hour of the start of the event [0-23]
Event minute start time
It determines the minutes of the start of the event [0-59]
Operating Mode ON/Standby
It determines the operating mode during the event
• 0 = ON
• 1 = Stand-by
Set point Cool
It determines the set point in cooling mode that will be set if the unit is in cooling mode before time scheduling
Set point Heat
It determines the set point in heating mode that will be set if the unit is in heating mode before time scheduling
Parameters
Description
value
tE00
Enabling
scheduling
Scheduling disabled
0
Scheduling enabled
1
Parameters
day
Time zone
Time zone
Time zone
tE01
Monday
1
2
3
tE02
Tuesday
1
2
3
tE03
Wednesday
1
2
3
tE04
Thursday
1
2
3
tE05
Friday
1
2
3
tE06
Saturday
1
2
3
tE07
Sunday
1
2
3