TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY

Tw=

Outlet water temperature °C 

kWf =

refrigerating power (kW).

kWa =

Power input of compressors (kW)

The standard performances refer to a 5°C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all fans at top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

Mod. 115-200

MOD.

Tw

OUTDOOR AIR TEMPERATURE (°C D.B.) 

20

25

30

35

40

45

50

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

115

5

128

24.9

119

28.7

113

31.6

106

34.8

98.5

38.4

91.3

41.8

83.8

45.2

6

131

25.1

123

28.9

116

31.9

109

35.1

101

38.7

93.8

42.2

86.1

45.7

7

135

25.4

126

29.2

119

32.2

112

35.5

104

39.1

96.5

42.7

88.6

46.1

8

139

25.7

130

29.5

123

32.6

115

35.9

107

39.6

99.2

43.1

-

-

9

143

25.9

133

29.8

126

32.9

118

36.3

110

40.0

102

43.6

-

-

10

147

26.2

137

30.1

129

33.2

121

36.6

113

40.4

105

44.0

-

-

11

150

26.5

140

30.4

133

33.5

125

37.0

116

40.7

107

44.4

-

-

12

154

26.7

144

30.7

136

33.9

128

37.3

119

41.1

110

44.9

-

-

130

5

144

28.4

134

32.7

127

36.0

119

39.7

111

43.8

103

47.7

94.3

51.6

6

148

28.7

138

33.0

130

36.4

122

40.1

114

44.2

106

48.2

96.9

52.1

7

152

29.0

142

33.3

134

36.7

126

40.5

117

44.6

109

48.7

100

52.6

8

156

29.3

146

33.7

138

37.1

130

40.9

121

45.1

112

49.2

-

-

9

161

29.6

150

34.0

142

37.5

133

41.4

124

45.6

115

49.7

-

-

10

165

29.9

154

34.4

146

37.9

137

41.8

127

46.0

118

50.2

-

-

11

169

30.2

158

34.7

149

38.3

140

42.2

130

46.5

121

50.7

-

-

12

174

30.5

162

35.1

153

38.6

144

42.6

134

46.9

124

51.2

-

-

145

5

163

31.6

152

36.3

144

40.0

135

44.1

126

48.6

117

53.0

107

57.3

6

168

31.9

157

36.7

148

40.4

139

44.5

129

49.1

120

53.5

110

57.9

7

173

32.2

161

37.0

152

40.8

143

45.0

133

49.6

123

54.1

113

58.5

8

178

32.6

166

37.5

157

41.3

147

45.5

137

50.1

127

54.7

-

-

9

182

32.9

170

37.8

161

41.7

151

46.0

141

50.6

130

55.2

-

-

10

187

33.2

175

38.2

165

42.1

155

46.4

144

51.2

134

55.8

-

-

11

192

33.5

179

38.6

170

42.5

159

46.9

148

51.7

137

56.3

-

-

12

197

33.9

184

39.0

174

42.9

163

47.3

152

52.2

141

56.9

-

-

160

5

180

35.4

168

40.8

159

44.9

149

49.5

139

54.6

129

59.5

118

64.3

6

185

35.8

173

41.2

164

45.3

154

50.0

143

55.1

132

60.1

122

64.9

7

191

36.1

178

41.6

168

45.8

158

50.5

147

55.7

136

60.7

125

65.6

8

196

36.5

183

42.0

173

46.3

162

51.1

151

56.3

140

61.4

-

-

9

202

36.9

188

42.5

178

46.8

167

51.6

155

56.8

144

62.0

-

-

10

207

37.3

193

42.9

183

47.2

171

52.1

159

57.4

148

62.6

-

-

11

212

37.6

198

43.3

187

47.7

176

52.6

164

58.0

151

63.2

-

-

12

218

38.0

203

43.7

192

48.2

181

53.1

168

58.5

156

63.8

-

-

180

5

205

39.3

192

45.2

181

49.8

170

54.9

158

60.5

147

66.0

135

71.4

6

211

39.7

197

45.6

186

50.3

175

55.4

163

61.1

151

66.6

138

72.0

7

217

40.1

203

46.1

192

50.8

180

56.0

167

61.7

155

67.3

142

72.8

8

223

40.5

209

46.6

197

51.4

185

56.6

172

62.4

160

68.0

-

-

9

230

40.9

214

47.1

203

51.9

190

57.2

177

63.0

164

68.7

-

-

10

236

41.3

220

47.5

208

52.4

195

57.8

182

63.7

168

69.4

-

-

11

242

41.7

226

48.0

213

52.9

200

58.3

186

64.3

173

70.1

-

-

12

248

42.1

232

48.5

219

53.4

206

58.9

191

64.9

177

70.8

-

-

200

5

228

44.1

213

50.7

202

55.9

189

61.6

176

67.9

163

74.0

150

80.0

6

235

44.5

219

51.2

207

56.4

194

62.2

181

68.5

167

74.7

154

80.8

7

241

44.9

225

51.7

213

57.0

200

62.8

186

69.2

172

75.5

158

81.6

8

248

45.4

232

52.3

219

57.6

206

63.5

191

70.0

177

76.3

-

-

9

255

45.9

238

52.8

225

58.2

211

64.1

197

70.7

182

77.1

-

-

10

262

46.3

244

53.3

231

58.7

217

64.8

202

71.4

187

77.8

-

-

11

269

46.8

251

53.8

237

59.3

222

65.4

207

72.1

192

78.6

-

-

12

276

47.2

258

54.4

244

59.9

229

66.0

213

72.8

197

79.4

-

-

Содержание RGA ST

Страница 1: ...RGA ST AIR COOLED WATER CHILLERS WITH AXIAL FANS 53 5 200 kW IN COOLING MODE INSTALLATION AND OPERATION MANUAL F R I G E R A N T G R E F R I G E R A N T G A S E C O FRIEND L Y E C O FRIEND L Y...

Страница 2: ...sschlie lichen Verantworfung da die genannte Maschine den Bestimmungen der folgenden EG Richtlinien entspricht Nous soussign s d clarons sous notre enti re responsabilit que la machine en objet est co...

Страница 3: ...NGER 22 MAXIMUM VOLUME OF WATER 23 MAXIMUM WATER VOLUME OF THE SYSTEM WITH HYDRONIC KIT 23 DIMENSIONAL DATA 24 OVERALL DIMENSIONS 24 DESCRIPTION OF THE COMPONENTS 25 MINIMUM SPACE REQUIRED FOR OPERATI...

Страница 4: ...rom failure of the information in this manual to correspond to the actual machine in your possession Proper uses this series of chillers is designed to produce cold or hot water for use in hydronic sy...

Страница 5: ...l fans with profiled blades to contain noise and with thermal protection built in on board electrical control panel equipped with control system to manage the main functions During the design of the u...

Страница 6: ...wer the auxiliary circuit 2c The microprocessor monitoring section includes User interfacing terminal with display On off key Operating mode selector key Compressor on off display LED Operational mode...

Страница 7: ...maximun protec tion against adverse weather conditions 5 Evaporator of the shell and tube heat exchanger type made of carbon steel and optimized for operation with R410A Features high efficiency groo...

Страница 8: ...it will block and can only be restarted by resetting via the user interface terminal 14 Water differential pressure switch This is standard supply and is installed on the connections between the water...

Страница 9: ...t ON OFF and to reset the alarms Mode ON OFF keys used to access and quit the various menu levels UP key scrolls forwards through the menu items or increases the value of a parameter Tasto DOWN scroll...

Страница 10: ...3 98 4 04 3 96 3 95 4 00 3 95 3 94 3 92 3 90 3 93 3 94 Water flow rate 1 2 56 2 80 3 29 3 76 4 35 4 87 5 35 6 02 6 83 7 55 8 60 9 56 l s Water pressure drops 1 29 35 45 60 50 31 37 53 70 82 57 40 kPa...

Страница 11: ...0 7 15 4 75 3 17 7 71 2 19 5 66 9 21 5 62 2 23 7 57 6 25 8 52 9 27 9 7 83 1 15 5 77 5 17 9 73 3 19 7 68 8 21 7 64 0 23 9 59 3 26 1 54 5 28 2 8 85 4 15 7 79 7 18 1 75 4 19 9 70 7 21 9 65 8 24 2 61 0 26...

Страница 12: ...68 31 9 157 36 7 148 40 4 139 44 5 129 49 1 120 53 5 110 57 9 7 173 32 2 161 37 0 152 40 8 143 45 0 133 49 6 123 54 1 113 58 5 8 178 32 6 166 37 5 157 41 3 147 45 5 137 50 1 127 54 7 9 182 32 9 170 37...

Страница 13: ...flow rate 1 2 48 2 71 3 19 3 65 4 21 4 71 5 21 5 83 6 64 7 31 8 31 9 27 l s Water pressure drops 1 27 33 42 57 47 29 35 50 66 77 53 38 kPa Compressor Heat Exchanger Coil Water Storage Tank SAA accesso...

Страница 14: ...7 49 9 28 8 6 78 2 16 0 73 0 18 4 69 1 20 3 64 8 22 4 60 3 24 7 55 8 26 9 51 3 29 1 7 80 5 16 2 75 2 18 6 71 1 20 5 66 7 22 6 62 1 25 0 57 5 27 2 52 8 29 4 8 82 8 16 4 77 3 18 8 73 1 20 8 68 6 22 9 6...

Страница 15: ...8 113 55 4 104 59 9 6 163 33 3 152 38 3 144 42 2 135 46 5 126 51 3 116 55 9 107 60 5 7 168 33 6 157 38 7 148 42 6 139 47 0 129 51 8 120 56 5 110 61 1 8 173 34 0 161 39 1 152 43 1 143 47 5 133 52 4 123...

Страница 16: ...1 2 56 2 62 2 53 2 68 2 55 2 53 2 52 2 53 2 53 2 51 2 52 ESEER 3 61 3 53 3 61 3 50 3 69 3 52 3 49 3 47 3 49 3 49 3 47 3 48 Water flow rate 1 2 42 2 65 3 12 3 56 4 12 4 60 5 06 5 69 6 45 7 17 8 12 9 03...

Страница 17: ...7 2 48 8 29 4 6 76 5 16 4 71 4 18 8 67 5 20 7 63 4 22 9 58 9 25 2 54 6 27 5 50 1 29 7 7 78 7 16 5 73 5 19 0 69 5 21 0 65 2 23 1 60 7 25 5 56 2 27 8 51 6 30 0 8 80 9 16 7 75 6 19 2 71 4 21 2 67 0 23 4...

Страница 18: ...9 110 56 6 101 61 2 6 158 34 0 148 39 1 140 43 1 131 47 5 122 52 4 113 57 1 104 61 8 7 163 34 4 152 39 5 144 43 6 135 48 0 126 52 9 116 57 7 107 62 4 8 168 34 7 156 40 0 148 44 0 139 48 6 129 53 5 12...

Страница 19: ...22 1 38 Percentage Of glycol in mass volume 0 0 10 8 9 20 18 1 30 27 7 40 37 5 Freezing point C 0 3 2 8 14 22 Cooling capacity CCPF Power input CCPA 1 00 0 99 0 98 0 97 0 95 Compressor power input CC...

Страница 20: ...83 3 80 4 76 8 68 3 59 0 96 86 67 59 54 145 94 2 91 9 89 4 85 3 81 0 74 6 67 0 58 6 97 87 68 60 55 160 94 2 91 9 89 4 85 3 81 0 74 6 67 0 58 6 97 87 68 60 55 180 92 4 90 1 88 6 86 0 83 2 77 8 71 2 62...

Страница 21: ...ead limit values of the unit OPERATING RANGE Thermal Water Head Limit value Minimum C 3 Maximum C 8 Note Make sure the water flow is within the minimum and maximum pressure drop as reported water pres...

Страница 22: ...ration range Unit Size 50 60 70 80 90 100 115 130 145 160 180 200 UM NOTES Graph reference 1 2 3 4 5 6 Q Water flow rate p Water pressu re drop Lower limit value Q 1 50 1 50 1 50 1 50 1 94 2 77 2 77 2...

Страница 23: ...3 x100 kPa NOTE In case A make sure that the user s lowest point is able to withstand the global pressure Tab 1 NOTE If the unit operates with brine calculate the real volume of the system by taking i...

Страница 24: ...5 256 1849 375 169 234 70 1754 176 1 1 1 6 7 2 8 2 8 2 8 6 7 6 7 4 3 5 3 5 3 5 4 4 4097 6 7 4 3 5 1 2 8 169 234 70 1104 2193 25 1047 25 1097 502 1550 4076 1661 363 Mod 50 60 70 80 Mod 90 100 Mod 115 1...

Страница 25: ...1600 2000 1 Access panel to electric panel s power section 2 Access panel to compressor compartment 3 Vibration damper fixing holes 4 pcs 4 Coil protection grilles accessory 5 65 mm lifting holes 6 22...

Страница 26: ...vibration dampening materials should be inserted under the bearing points The unit can be supplied with the rubber or spring vibration dampening accessory This must be mounted by the installer Area of...

Страница 27: ...682 90 467 1235 920 484 1249 940 100 449 1180 1002 465 1195 1023 115 463 1199 1115 482 1215 1145 130 458 1187 1143 476 1203 1172 145 457 1175 1198 475 1191 1227 160 470 1185 1247 470 1185 1260 180 46...

Страница 28: ...220 696 417 935 286 110 85 222 703 90 465 1263 364 185 135 263 947 481 1277 360 187 145 276 968 100 447 1208 422 195 131 284 1032 462 1222 416 198 141 298 1052 115 461 1224 453 216 154 323 1147 479 12...

Страница 29: ...e in between to separate the truck from the unit in order to prevent the surfaces of the bank or electric panel from being damaged if the unit has to be moved sideways Fig 1 Do not allow the unit or a...

Страница 30: ...casing protected against adverse weather conditions They can be inspected through the screen printed front door The door is locked by the door locking mechanism of the main circuit breaker The poweri...

Страница 31: ...connected straight to the ground screw identified by code PE which ensures the equipotential connection of all metal grounding points and structural parts of the machine Neutral conductor The neutral...

Страница 32: ...o make sure that the air venting valves can be accessed through the insulation Do not forget to install or at least allow for the installation of pressure and temperature reading instruments on the in...

Страница 33: ...n the plumbing system In the same way he must install a water drain valve in order when necessary to drain the unit s plate exchanger completely espe cially during the winter in order to prevent freez...

Страница 34: ...esuperheater see diagram the graph on the right shows the type of adjustment to use QA QAB 30 c 0 35 c QB 100 Desuperheater INLET temperature WATER FLOW RATE Plumbing connection with Victaulic couplin...

Страница 35: ...eal on the back on the side flanks and on the inner lips that contact the pipe Work in conditions of the utmost cleanliness as particles of dirt could damage the seal Always and only use synthetic gre...

Страница 36: ...ESSURE SOCKET 1 4 SAE WITOUT CORE LIQUID BALL VALVE COMPRESSOR OUTLET BALL VALVE WATER INLET PROBE LIQUID PROBE PLATE HEAT EXCHANGER WATER OUTLET PROBE CHARGING TUBE FAN Description PRESSURE SOCKET 1...

Страница 37: ...tself and obtained by pressing the button an associated function indicated on the front of the instrument at the corresponding button and obtained by prolonged pressing 3 seconds of the button a combi...

Страница 38: ...mat 24 00 Centigrade degrees Red Unit of measure of selected parameter Bar Red not used Relative humidity Red not used Menu Red Menu browsing Users Compressor 1 Amber User activated Safety timing Comp...

Страница 39: ...n direct function Ai AiL1 Display input AI1 AiL2 Display input AI2 AiL3 Display input AI3 AiL4 Display input AI4 AiL5 Display input AI5 Di DiL1 Display input DI1 DiL2 Display input DI2 DiL3 Display in...

Страница 40: ...nt in heating tr21 Minimum set point in heating tr22 Maximum set point in heating tr23 Hysteresis in heating tr25 Differential set point in heating Pi Pi01 Interval of inactivity pump anti lock Pi03 M...

Страница 41: ...tions profile 1 2 3 tE 32 60 88 Event 4 Minutes selections profile 1 2 3 tE 33 61 89 Event 4 Operation mode selections On Standby profile 1 2 3 tE 34 62 90 Event 4 Set point cool profile 1 2 3 tE 35 6...

Страница 42: ...nly be carried out by an authorised service centre or by competent personnel Digital inputs DI1 TC1 Thermal switch compressor 1 thermo statted delivery 1 high pressure switch Digital input with voltag...

Страница 43: ...rol of single phase fans in phase cut AO4 VE Fans signal 0 10V for control of three phase fans in phase cut AO5 MP1M Inverter pump signal 4 20mA for inverter control pump Digital outputs DO1 CP1 Compr...

Страница 44: ...shing and the Alarm digital output is disabled This operation does not affect the alarm in progress Number of events per hour The counting of events per hour is provided for some alarms if the number...

Страница 45: ...68 Outside air probe fault When the alarm is activated climate adjustment in heating and dynamic defrost are unavailable Er90 Maximum number of recordings in alarms history exceeded Indicates that the...

Страница 46: ...r Hi02 enables operation of the electrical elements supplementing the heat pump when it assumes value 1 The heating elements are activated according to a two step logic depending on the unit inlet wat...

Страница 47: ...nagement time For each day of the week you can select one of the 3 time zone available For each time zone you can associate 4 events The parameters involved in time events are described below Event ho...

Страница 48: ...C tE 28 40 set point heat 40 C EVENT 4 unit in stand by tE 31 18 hour tE 32 00 minutes tE 33 1 stand by unit is in stand by pay attention 0 ON 1 stand by tE 34 12 set point cool 12 C tE 35 40 set poin...

Страница 49: ...03 1 CL33 0 CL53 21 input active close contact close contact Demand Limit 50 Economy digital input CL03 1 CL33 0 CL53 22 input active close contact close contact economy AI5 S2 Not configured CL04 0 C...

Страница 50: ...0578 23 10 9152 43 5 1671 4 22 2115 24 10 5146 44 4 9774 5 21 3963 25 10 1287 45 4 7948 6 20 6110 26 9 7569 46 4 6188 7 19 8546 27 9 3988 47 4 4493 8 19 1259 28 9 0539 48 4 2860 9 18 4239 29 8 7216 4...

Страница 51: ...X 1 must appear in the message Some registers contain more than one piece of information in this case the bits representing the resource value are identified by means of the number of bits used Bit nu...

Страница 52: ...0 1 0 N 0 flag Er05 Alarm low pressure sequence meter fan thermal switch R 33104 5 H0150 1 5 N 0 flag Er10 Alarm compressor 1 thermal protection thermostatted delivery 1 High pressure R 33105 2 H0151...

Страница 53: ...l Clean the aluminium surface of the coil with a compressed air jet making sure to aim the jet with the direction of fins so as to avoid damage If the aluminium fins are damaged comb the coil with a s...

Страница 54: ...re listed in the following table along with the instruc tions on how to neutralize them Part in question Residue hazard Mode Precautions Compressor and delivery pipe Burns Contact with the pipes and o...

Страница 55: ...ated rooms Do not breathe vapours or aerosols Carefully close the containers and keep them in a cool dry and well ventilated place Keep in the original containers Incompatible products Explosives flam...

Страница 56: ...gh concentration Keep in a well ventilated place Do not breathe the gas The risk of suffocation is often underestimated and must be clearly explained during the training of operators Ensure compliance...

Страница 57: ...57...

Страница 58: ...58...

Страница 59: ...Cod 3QE29130 Ferroli spa 37047 San Bonifacio Verona Italy Via Ritonda 78 A tel 39 045 6139411 fax 39 045 6100933 www ferroli it...

Отзывы: