Unit description

GENERAL FEATURES

Unit identification code

This  series  of 

air-water

heat  pumps  satisfies  the  heating,

cooling  and  domestic  hot  water  production  requirements  of

residential plants of small and medium size.
All the units are suitable for outdoor installation and can be

applied to 

fan coil

plants, 

radiant

floor plants and high effi-

ciency 

radiators

plants.

The control system allows to manage not only the refrigerant

circuit but the whole plant with the possibility to choose diffe-

rent solutions both for the heating and cooling plant and for the

domestic  hot  water  management.  The  possibility  of  solar

panels or other heating sources integration is also available.
The 

heating

function  optimizes  the  flow  water  temperature

according both to the ambient temperature and to the outdoor

temperature through climatic curves adaptable to the building

features. It’s possible to manage a storage tank and two inde-

pendent circuits (a direct one and a mixed one).
The 

domestic hot water

management allows to control the

three  way  valve,  the  storage  tank  and  the  anti-legionella

cycles (if necessary).
The 

cooling

function can be realized through “active cooling”

(refrigerant circuit inversion). When the unit is used in radiant

floor plants, to avoid condensate generation, a room humidity

sensor can be installed.
The  internal 

programmer  clock

allows  to  define  different

daily switching programs for heating, cooling and domestic hot

water production.

The refrigerant circuit, contained in a compartment protected

from  the  air  flow  to  simplify  the  maintenance  operations,  is

equipped  with  rotary  or  scroll  compressor  (according  to  the

model)  mounted  on  damper  supports,  brazed  plate  heat

exchanger, thermostatic expansion valve, reverse cycle valve,

axial  fans  with  safety  protection  grilles,  finned  coil  made  of

copper pipes and aluminium louvered fins. The circuit is pro-

tected by high and low pressure switches and differential pres-

sure switch on the plate heat exchanger.
The plate heat exchanger and all the hydraulic pipes are 

ther-

mally insulated

in order to avoid condensate generation and

to reduce thermal dispersions.
All three-phase power supply units are provided with a phase

presence and correct sequence controller device.
All the units are accurately built and individually tested in the

factory. Only electric and hydraulic connections are required

for installation.

The codes that identify the units and the meaning of the letters used are described below.

Power supply

1

-  230V -  1  - 50 Hz

5

-  400V - 3N - 50 Hz

Refrigerant type

0

- R410A

Unit model

N° compressors

VB

- Base Version

Unit version

Unit type

IP

-  Units suitable for

hydronic plant installation

operating as reversible heat

pumps

HXA   IP   7.1   VB   AB   0 M 1

Operating range

M

- Medium temperature.

The unit is suitable to pro-

duce water at medium tem-

perature

AB

- Base setting up

Acoustic setting up

Содержание HXA SERIES

Страница 1: ...HXA AIR WATER HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL R410A ...

Страница 2: ...2 ...

Страница 3: ...TROL SySTEM 7 OPTIONS 8 ACCESSORIES 9 TECHNICAL DATA AND PERFORMANCES 10 TECHNICAL DATA 10 NOMINAL PERFORMANCES LOW TEMPERATURE PLANTS 11 NOMINAL PERFORMANCES MEDIUM TEMPERATURE PLANTS 11 HEATING PERFORMANCES 12 COOLING PERFORMANCES 13 PLANT SIDE HyDRAULIC PERFORMANCES 14 OPERATING LIMITS 16 ELECTRICAL DATA 17 NOISE LEVELS 17 WEIGHTS 18 OVERALL DIMENSIONS 18 MINIMUM OPERATING AREA 18 ...

Страница 4: ...4 ...

Страница 5: ...rnal programmer clock allows to define different daily switching programs for heating cooling and domestic hot water production The refrigerant circuit contained in a compartment protected from the air flow to simplify the maintenance operations is equipped with rotary or scroll compressor according to the model mounted on damper supports brazed plate heat exchanger thermostatic expansion valve re...

Страница 6: ...lizer allows the unit to adjust itself to the dif ferent operating conditions keeping steady the set superhea ting The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer 5 to restrain impurity and moistu re residuals that could be present in the circuit high and low pressure switches in order to assure the compressor to ope rate inside the permitted limits 4 way re...

Страница 7: ...d circuit pump and 3 way mixing valve management of a heating direct circuit only pump management of a storage tank for heating and or cooling management of electrical heaters for heating and dome stic hot water 3 steps logic solar panels integration room humidity control for cooling with radiant systems internal programmer clock for heating cooling and dome stic hot water digital input for electr...

Страница 8: ...ent The controller flexibility and the big number of options available allow to get for each model a lot of diffe rent configurations that integrate inside the heat pump many components of the plant and allow to realize compact and tested installations In order to select the right configuration it is neces sary to define the type of plant to which the heat pump will be connected both for what conc...

Страница 9: ...less transmitter Connected to the unit controller allows to communicate with wireless remote control and wireless outdoor temperature sensor Wireless repeater Extends wireless operating range Wireless adaptor for out door temperature sensor Allows to transform the wired outdoor temperature sensor standard for all the units in a wireless sensor Condensate sensor In cooling mode it allows the minimu...

Страница 10: ...il finned coil Quantity 1 1 1 1 1 1 n Frontal surface 0 60 0 60 0 77 0 77 0 98 0 98 m2 Fans Type axial axial axial axial axial axial Quantity 1 1 1 1 2 2 n Diameter 450 450 500 500 500 500 mm Maximum rotational speed 900 900 900 900 900 900 rpm Toatal installed power 0 15 0 15 0 21 0 21 0 42 0 42 kW Plant side hydraulic circuit Expansion vessel volume 10 10 10 10 10 10 l Plant pump standard option...

Страница 11: ...kW Power input 2 22 2 71 3 38 4 01 5 06 6 25 kW COP 3 05 2 90 2 94 2 92 3 04 2 91 Water flow rate plant side 1154 1339 1690 1981 2612 3090 l h Pressure drops plant side 18 24 35 45 48 43 kPa Heating A2W45 source air in 2 C d b 1 C w b plant water in 40 C out 45 C Heating capacity 5 60 6 50 8 21 9 61 12 7 15 1 kW Power input 2 19 2 68 3 33 3 94 4 97 6 16 kW COP 2 56 2 43 2 47 2 44 2 56 2 45 Water f...

Страница 12: ...in order to obtain the real performances in the selected opera ting conditions The reference nominal condition is A7W35 source air in 7 C d b 6 C w b plant water in 30 C out 35 C HEATING performances Outlet temperature plant side A 55 C B 45 C C 35 C D 25 C Heating capacity Inlet air temperature w b C Power input Inlet air temperature w b C 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 15 10 5 0 5 10 15 20 ...

Страница 13: ... air temperature d b C 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 15 20 25 30 35 40 45 50 EER Inlet air temperature d b C The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected opera ting conditions The reference nominal condition is A35W7 source air in 35 C d b plant water in 12 C out 7 C Outlet temperature plant ...

Страница 14: ...1 8 1 Pressure drops unit without options 0 10 20 30 40 50 60 0 500 1000 1500 2000 2500 3000 3500 4000 Flow rate l h Pressure drops kPa Pressure drops to be added unit with option Integrative electrical heaters 7 1 Plant side hydraulic performances The graphs are referred to units operating with water at the temperature of 10 C density 1000 kg m3 ...

Страница 15: ...side flow rate management Standard pump 0 20 40 60 80 100 120 140 160 180 0 500 1000 1500 2000 2500 3000 3500 4000 Flow rate l h Available static head kPa Available static head unit with option Plant side flow rate management High head pump 10 1 12 1 18 1 15 1 8 1 7 1 18 1 15 1 12 1 10 1 8 1 7 1 The graphs are referred to units operating with water at the temperature of 10 C density 1000 kg m3 ...

Страница 16: ...the correct working of the unit is guaranteed HEATING Inlet air temperature d b C Outlet temperature plant side C Operating limits 5 0 5 10 15 20 25 30 35 40 45 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 COOLING Inlet air temperature d b C Outlet temperature plant side C Temperature difference between unit inlet and outlet Plant side T max Maximum value 11 C T min Minimum value 3 C ...

Страница 17: ...230 1 50 230 1 50 230 1 50 230 1 50 V ph Hz F L A Maximum total current input 13 4 17 1 22 0 24 8 A F L I Maximum total power input 2 9 3 7 4 7 5 3 kW M I C Maximum total start current 82 112 141 174 A Maximum total start current with soft starter option 41 43 49 59 A Power supply 400 3N 50 400 3N 50 400 3N 50 400 3N 50 V ph Hz F L A Maximum total current input 8 1 9 0 11 1 13 9 A F L I Maximum to...

Страница 18: ...andard pump 7 7 7 7 14 14 kg High head pump 9 9 14 14 15 15 kg Integrative electrical heaters 5 5 5 5 5 5 kg Rispect the free area around the unit as shown in figure in order to guarantee a good accessibility and facilitate maintenance and control operations Minimum operating area Overall dimensions B C A A 400 mm B 600 mm C 200 mm 1 Plant return 2 Plant return with Plant side flow rate management...

Страница 19: ...s all the responsabilities regarding inaccuracies contained in this manual if due to printing or typing mistakes The manufacturer reserves the right to apply changes and improvements to the products at any time and without notice ...

Страница 20: ...Ferroli spa 37047 San Bonifacio Verona Italy Via Ritonda 78 A tel 39 045 6139411 fax 39 045 6100933 www ferroli it 3QE26662 ...

Отзывы: