background image

ENERGY TOP B

74

EN

cod. 3540S738  -  Rev. 00  -  01/2014

Table of faults

Table. 6 - List of faults

Fault code Fault

Possible cause

Cure

A01

No burner ignition

EXCHANGER SAFETY THERMOSTAT ACTIVATED

CHECK THE BOILER SHELL AND CLEAN IT IF NECESSARY

Check the thermostat and replace it if necessary

Check the thermostat wiring

No gas

Check the regular gas flow to the boiler and that the air has been eliminated from the pipes

Ignition/detection electrode fault

Check the wiring of the electrode and that it is correctly positioned and free of any deposits

Faulty gas valve

Check the gas valve and replace it if necessary

Insufficient gas supply pressure

Check the gas supply pressure

Trap blocked

Check the trap and clean it if necessary

A02

Flame present signal with burner off

Electrode fault

Check the ionisation electrode wiring

Card fault

Check the card

A03

Overtemperature protection activated

Heating sensor damaged

Check the correct positioning and operation of the heating sensor

No water circulation in the system

Check the circulating pump

Air in the system

Vent the system

A04

Fume extraction duct safety device activated

Fault F07 generated 3 times in the last 24 hours

See fault F07

A05

Fan protection activated

Fault F15 generated for 1 hour (consecutive)

See fault F15

A06

No flame after ignition stage (6 times in 4 minutes)

Ionisation electrode fault

Check the position of the ionisation electrode and replace it if necessary

Flame unstable

Check the burner

Gas valve Offset fault

Check the Offset adjustment at minimum power

air/fume ducts obstructed

Remove the obstruction from the flue, fume extraction ducts and air inlet and terminals

Trap blocked

Check the trap and clean it if necessary

F07

High fume temperature

Flue partially obstructed or 
insufficient

Check the efficiency of the flue, fume extraction ducts and outlet terminal

Fume sensor position

Check the correct positioning and operation of the fume sensor

F10

Delivery sensor 1 fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

F11

Return sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

F12

DHW sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

F13

Fume sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

F14

Delivery sensor 2 fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

F15

Fan fault

No 230V power supply

Check the 3-pin connector wiring

Tachometric signal interrupted

Check the 5-pin connector wiring

Fan damaged

Check the fan

F34

Supply voltage under 170V

Electric mains trouble

Check the electrical system

F35

Faulty mains frequency

Electric mains trouble

Check the electrical system

F37

Flowswitch or pressure switch contact open

Insufficient system pressure or circulation

Check the system water pressure or for air in the system

Circulating pump not working

Check the circulating pump

Wrong card parameter setting

Check the card parameter and modify  it if necessary

F38

Flowswitch contact blocked closed

Flowswitch  dirty or blocked

Clean the flowswitch or replace it if necessary

F39

External probe fault

Probe damaged or wiring shorted

Check the wiring or replace the sensor

Probe disconnected after activating the sliding temperature

Reconnect the external probe or disable the sliding temperature

A41

Sensor positioning

Delivery sensor disconnected from the pipe

Check the correct positioning and operation of the heating sensor

A42

Heating sensor fault

Sensor damaged

Replace the sensor

F42

Heating sensor fault

Sensor damaged

Replace the sensor

F50

Cascade temperature sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

A61

Controller DBM12 fault

Controller DBM12 internal error

Check the earth connection and replace the controller if necessary.

A62

No communication between controller and gas valve

Controller not connected

Connect the controller to the gas valve

Valve damaged

Replace the valve

A63
A64
A65

F66

Controller DBM12 fault

Controller DBM12 internal error

Check the earth connection and replace the controller if necessary.

Содержание ENERGY TOP B 125

Страница 1: ...N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAKøM TALIMATLARø EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INSTALLATION ET D ENTRETIEN RO INSTRUCğIUNI DE UTILIZARE INSTALARE ùI ÎNTRETINERE RU ɊɍɄɈȼɈȾɋɌȼɈ ɉɈ ɗɄɋɉɅɍȺɌȺɐɂɂ ɆɈɇɌȺɀɍ ɂ ɌȿɏɈȻɋɅɍɀɂȼȺɇɂɘ UA ȱɇɋɌɊɍɄɐȱə Ɂ ȿɄɋɉɅɍȺɌȺɐȱȲ ɆɈɇɌȺɀɍ ɌȺ ɈȻɋɅɍȽɈȼɍȼȺɇɇə ...

Страница 2: ...uminium finned tube exchangers with steel premix burners housed in a vertical cabinet in epoxy powder coated steel resistant to atmospheric agents The plumbing circuits of the exchangers each equipped with its own local circulating pump run into system delivery and return manifolds inside the module The control sys tem has a microprocessor user interface with a large display and advanced cascade c...

Страница 3: ...a max of 90 C fig 8 DHW temperature adjustment with optional hot water tank installed Use the DHW buttons details 1 and 2 fig 1 to adjust the temperature from a min of 10 C to a max of 65 C fig 9 Room temperature adjustment with optional room thermostat Using the room thermostat set the temperature required in the rooms Room temperature adjustment with optional remote timer control Using the remot...

Страница 4: ...e Configurations in line fig 15 Configuration in line example with 4 modules Table 2 Configurations in line Heating temperature adjustment Adjustment can be made from the Remote Timer Control menu and the boiler control panel DHW temperature adjustment with optional hot water tank installed Adjustment can be made from the Remote Timer Control menu and the boiler control panel Summer Winter Switcho...

Страница 5: ...system characteristics In the presence of water harder than 25 Fr it is advisable to use suitably treated water in order to avoid possible scaling in the boiler caused by hard water or corrosion pro duced by aggressive water Due to its low thermal conductivity scaling even just a few mm thick causes significant overheating of the generator walls with consequent serious problems Water treatment is ...

Страница 6: ...Fit the bolts supplied on the flanges from inside the first module making them come out the flanges in the second module Partially tighten the nuts on the bolts from inside the second module Before tightening the nuts make sure all the seals are correctly positioned and fit the condensate drain pipes of the two modules see fig 49 Tighten the nuts and repeat the connection operations for the U pipe...

Страница 7: ...eans Transparent Param eters Menu In Information Menu Hi History Menu and rE History Menu Reset Se lect tS and press the RESET button The card has 29 transparent parameters also modifiable from Remote Control Service Menu Press the Heating buttons to scroll the list of parameters in increasing or decreasing or der Press the DHW buttons to modify the value of a parameter the change will be au tomat...

Страница 8: ... with a bipolar switch whose contacts have a minimum opening of at least 3 mm interposing fuses of max 3A between the boiler and the line It is important to re spect the polarities LINE brown wire NEUTRAL blue wire EARTH yellow green wire in making connections to the electrical line During installation or when changing the power cable the earth wire must be left 2 cm longer than the others B The u...

Страница 9: ... with the pro visions concerning the positioning of wall and or roof terminals and the minimum distanc es from windows walls ventilation openings etc Manifold ducts and flue must be suitably sized designed and made in compliance with the current standards They must be made of suitable materials i e resistant to heat and corrosion smooth on the inside and hermetic In particular joints must be conde...

Страница 10: ... the special manifolds optionals given in the table The choice of diameter must be made according to the total power of the bank of units respecting that given in the table Use a starting kit for each bank containing manifold plug and trap and a suitable number of manifolds one for each ENERGY TOP B 80 125 and two for each ENERGY TOP B 160 250 90 bends and manifold extensions are also available fo...

Страница 11: ... Fix the fume manifold brackets in the special holes arranged in the modules see fig 38 for side by side modules and fig 39 for opposed modules fig 38 fig 39 Arrange the height and slope of the manifold by means of the special holes in the brack ets fig 40 and fig 41 fig 40 fig 41 Couple together the fume manifolds and the trap cap using slippery agent or grease see fig 42 fig 42 Ø 300 B 2G 3G 1G ...

Страница 12: ... them on the fume manifold Then tighten screw D fig 47 fig 46 fig 47 3 6 Condensate drain B The boiler has an internal condensate drain trap connected to an internal con densate outlet manifold Condensate outlet connection using one generator fig 48 Condensate drain connection with one generator A Place the Ø40 pipe 1 not supplied on the side of the generator B Slide the pipe 2 towards the arrow s...

Страница 13: ...do the two fixing screws B and remove the fan assembly as indicated in fig 50 for the model ENERGY TOP B 80 160 and in for fig 51 the model ENERGY TOP B 125 250 fig 50 model ENERGY TOP B 80 160 fig 51 model ENERGY TOP B 125 250 6 Undo the screws C and remove fan D fig 52 only model ENERGY TOP B 125 250 fig 52 model ENERGY TOP B 125 250 7 Undo the fixing screws E fig 53 model ENERGY TOP B 80 160 an...

Страница 14: ...g Check the correct tightness and functionality of the condensate elimination system and trap Make sure the water is circulating properly between the boiler and the systems Make sure the gas valve modulates correctly in the heating and domestic hot water production phases Check proper boiler lighting by doing several tests turning it on and off with the room thermostat or remote control Using a co...

Страница 15: ...g shorted Wiring disconnected F11 Return sensor fault Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected F12 DHW sensor fault Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected F13 Fume sensor fault Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected F14 Delivery sensor 2 fault Sensor d...

Страница 16: ...ng pump not supplied 138 External probe not supplied 139 Remote timer control not supplied 154 Condensate drain pipe 179 Non return valve 186 Return sensor 191 Fume temperature sensor 193 Trap 196 Condensate tray 215 Air inlet reducer 220 Ignition card 252 3 way drain and shutoff cock 253 Shutoff cock 278 Double sensor Safety Heating 298 Cascade temperature sensor not supplied 299 Input 0 10 Vdc 3...

Страница 17: ...ain components Model ENERGY TOP B 80 125 fig 59 General view model ENERGY TOP B 80 125 Model ENERGY TOP B 160 250 fig 60 General view model ENERGY TOP B 160 250 10 7 11 10 7 11 193 32 196 82 220 44 29 215 36 16 278 252 253 154 179 14 186 114 38 81 345 191 10 11 7 10 11 7 ...

Страница 18: ... Water circuit Model ENERGY TOP B 80 125 fig 61 Water circuit model ENERGY TOP B 80 125 Model ENERGY TOP B 160 250 fig 62 Plumbing circuit model ENERGY TOP B 160 250 16 36 44 81 82 29 196 278 22 186 154 193 252 253 32 14 179 38 345 11 10 7 114 10 7 11 ...

Страница 19: ... 3 26 9 18 3 26 9 Efficiency Pmax 80 60 C 98 0 98 0 98 0 98 0 Efficiency Pmin 80 60 C 98 5 98 5 98 5 98 5 Efficiency Pmax 50 30 C 106 106 106 106 Efficiency Pmin 50 30 C 107 5 107 5 107 5 107 5 Efficiency 30 109 109 109 109 Gas supply pressure G20 mbar 20 20 20 20 Max gas delivery G20 m3 h 7 94 12 38 15 88 24 76 Min gas delivery G20 m3 h 1 8 2 65 1 8 2 65 Gas supply pressure G31 mbar 37 37 37 37 M...

Страница 20: ...n the terminal block J J 230V 50KL 16 278 191 186 16 32 V1 V2 44 X1 X3 X2 98 L N 1 2 3 4 5 7 8 9 10 11 12 1 2 3 4 5 1 2 3 4 5 7 8 9 10 M 3O15A J J 6BC12P 16 278 191 186 114 16 32 V1 V2 44 X1 X3 X2 A 25 2 27 28 29 30 1 2 3 4 1 2 3 4 5 6 D12 X01 X04 X03 X05 13 14 15 1 17 18 19 20 21 22 23 24 299 139 72 138 298 42 4 5 7 8 9 10 11 12 F F F F 300 301 95 302 130 307 72B 6BC12E 6BC12P 6BC12E 306 38 114 3...

Страница 21: ...ttiva Compatibilità Elettromagnetica 2004 108 Presidente e Legale rappresentante Cav del Lavoro Dante Ferroli IT Uygunluk beyani ømalatçi FERROLI S p A Adres Via Ritonda 78 a 37047 San Bonifacio VR bu cihazin asagida yer alan AET EEC yönergelerine uygunluk içinde oldugunu beyan etmektedir 2009 142 Gazla çalistirilan üniteler için Yönetmelik 92 42 Randiman Verimlilik Yönetmeligi Yönerge 2006 95 Düs...

Страница 22: ...ɤɬɢɜɚɦ CEE Ⱦɢɪɟɤɬɢɜɚ ɩɨ ɝɚɡɨɜɵɦ ɩɪɢɛɨɪɚɦ 2009 142 Ⱦɢɪɟɤɬɢɜɚ ɩɨ Ʉ ɉ Ⱦ 92 42 Ⱦɢɪɟɤɬɢɜɚ ɩɨ ɧɢɡɤɨɦɭ ɧɚɩɪɹɠɟɧɢɸ 2006 95 Ⱦɢɪɟɤɬɢɜɚ ɩɨ ɷɥɟɤɬɪɨɦɚɝɧɢɬɧɨɣ ɫɨɜɦɟɫɬɢɦɨɫɬɢ 2004 108 ɉɪɟɡɢɞɟɧɬ ɢ ɭɩɨɥɧɨɦɨɱɟɧɧɵɣ ɩɪɟɞɫɬɚɜɢɬɟɥɶ Ʉɚɜɚɥɶɟɪɟ ɞɟɥɶ ɥɚɜɨɪɨ ɩɨɱɟɬɧɵɣ ɬɢɬɭɥ ɩɪɢɫɭɠɞɚɟɦɵɣ ɝɨɫɭɞɚɪɫɬɜɨɦ ɡɚ ɡɚɫɥɭɝɢ ɜ ɪɭɤɨɜɨɞɫɬɜɟ ɩɪɨɦɵɲɥɟɧɧɨɫɬɶɸ Dante Ferroli RU DeclaraĠie de conformitate Producător FERROLI S p A Adresă Via Ritonda...

Страница 23: ......

Страница 24: ......

Страница 25: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...

Отзывы: