ENERGY TOP B
69
EN
cod. 3540S738 - Rev. 00 - 01/2014
Direct connection of Ø80 terminals code 041013X0
Each single module can be connected directly to the terminal kits 041013X0 as given in
, even with fig. 33 connection in bank.
Each kit comprises a Ø80 terminal with grille (ref. 3), a seal (ref. 1) and a centring ring
(not used in this model). For models
ENERGY TOP B 160 - 250
use 2 kits per
ENERGY
TOP B 80 - 125
module, and 1 kit for models .
fig. 33
B
Before installing the flues, fill the trap with approx. 0.5 l. of water through the
flue connections.
B
For outside installations make the seal 1 adhere perfectly to the top part of the
cabinet, to prevent possible infiltration of rain and atmospheric agents.
Connection with manifolds
To connect one or more modules in bank to a single flue, it is advisable to use the special
manifolds (optionals) given in the table. The choice of diameter must be made according
to the total power of the bank of units, respecting that given in the table. Use a starting
kit for each bank (containing manifold plug and trap) and a suitable number of manifolds
(one for each ENERGY TOP B 80 - 125 and two for each ENERGY TOP B 160 - 250).
90° bends and manifold extensions are also available for the flue connection.
Installation examples with modules in line
fig. 34
fig. 35
A - 041026X0
- Starting kit Ø200
B - 041027X0
- Starting kit Ø300
C - 041028X0
- Manifold kit Ø200 in line
D - 041029X0
- Manifold kit Ø300 in line
Installation examples with opposed modules
fig. 36
Bank
heating capacity
Manifold
diameter
Starting
kit
Manifold
kit
L=500
Manifold
extension
M/F
L=1000
90° bend
manifold
Up to 500 kW
200 mm
in line
041026X0
C
041028X0
041019X0
041016X0
opposed
E
041030X0
Up to 1000 kW
300 mm
in line
041027X0
D
041029X0
041036X0
041035X0
opposed
F
041031X0
1
3
(
(
(
Ø.200
(
A
Ø.300
6
B
6
6
6
6
,
Ø.200
A