ECONCEPT SOLAR ST
50
EN
cod. -- - 11/2010 (Rev. 00)
User settings
The settings for Heating, such as max. delivery temperature, external probe curve (with optional external probe con-
nected to boiler), weekly time programming, etc., are independent for each zone; these are modified through the Re-
mote Control of the corresponding temperature zone. In case of direct zones, make sure to set a similar max. delivery
temperature for all the temperature zones. With Room Chronothermostats, on closing of the contact the delivery tem-
perature is adjusted to the max. value set by the zone controller. The settings relevant to DHW such as Domestic Hot
Water temperature, weekly time programming (with boiler prearranged: see relevant documentation), etc., are managed
in parallel; these are modified through the temperature zone Remote Controls. In case of DHW weekly time program-
ming, the zone controller overlaps programmes coming from the single Remote Controls.
Conversion of low temperature zone to high temperature zone
The low temperature zone can become a high temperature zone. Follow the instructions given below (also refer to the
table of parameters FZ4B):
1. Parameter 2 card FZ4B 40°C to 70°C ÷ 80°C
2. Parameter 3 card FZ4B 10°C to 0°C
3. Disconnect the safety thermostat (317A) from the delivery pipe.
4. Do not disconnect or bypass the mixing valve (ref. 315a)