Calculation example
Here we give an example of the calculation for a separate
fume outlet. We recommend inserting a condensate trap on
long vertical sections to prevent condensation getting onto
the burner and damaging it. If monitoring the condensate trap
is not guaranteed, it must be fitted with a suitable drain pipe
and air trap, which in its turn must be appropriately connected
to a suitable drain.
Ref.
1
2
3
4
5
6
No.Pieces
1
1
1
1
36
1
Air bend 80
Horizontal air pipe 80
Windproof end piece
Condensate collection cup coupling
Vertical fume pipe 80
Outlet flue + coupling
Description
Equivalent
loss
1.5 m
1.0 m
2.0 m
3.0 m
36.0 m
4.0 m
47.5 m
Total
1
2
3
4
5
6