DIVAtech D LN C
20
EN
cod. 3541P710 - Rev. 00 - 10/2018
Configuration Menu
The configuration Menu is accessed by pressing the DHW buttons together for 10 sec-
onds.
12 parameters
, indicated by the letter "b” and not modifiable from Remote Timer
Control, are available.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the change will
be automatically saved.
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.
Service menu
The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 sub-
menus are available: press the Heating buttons to select, in increasing or decreasing or-
der, "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means
Information Menu, "Hi" means History Menu: after selecting the submenu, press the Re-
set button again to access it; "rE" means History Menu Reset: see description.
“tS” - Transparent Parameters Menu
21
parameters indicated by the letter "P” are available, which are also modifiable from
Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the change will
be automatically saved.
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
3.
The Maximum Heating Power parameter can also be modified in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
“In” - Information Menu
9
pieces of information are available.
Press the Heating buttons to scroll the list of information in increasing or decreasing or-
der. Press the DHW buttons to display the value.
Notes:
1.
In case of damaged sensor, the card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu or exiting occurs automatically after 15 minutes.
"Hi" - History Menu
The card can store the last 11 faults: the History datum item H1: represents the most re-
cent fault that occurred; the History datum item H10: represents the least recent fault that
occurred.
The codes of the faults saved are also displayed in the corresponding menu of the Re-
mote Timer Control.
Press the Heating buttons to scroll the list of faults in increasing or decreasing order.
Press the DHW buttons to display the value.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"rE" - History Reset
Press the Eco/Comfort button for 3 seconds to delete all the faults stored in the History
Menu: the card will automatically exit the Service Menu, in order to confirm the operation.
Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs
automatically after 15 minutes.
4.2 Commissioning
Before lighting the boiler
•
Check the seal of the gas system.
•
Check correct prefilling of the expansion tank.
•
Fill the water system and make sure all air contained in the boiler and the system
has been vented.
•
Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
•
Check correct connection of the electrical system and efficiency of the earthing system.
•
Make sure the gas pressure for heating is that required.
•
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
B
IF THE ABOVE INSTRUCTIONS ARE NOT OBSERVED THERE MAY BE
RISK OF SUFFOCATION OR POISONING DUE TO GAS OR FUMES ES-
CAPING; DANGER OF FIRE OR EXPLOSION. ALSO, THERE MAY BE A
RISK OF ELECTRIC SHOCK OR FLOODING THE ROOM.
Checks during operation
•
Switch the unit on.
•
Check the tightness of the fuel circuit and water systems.
•
Check the efficiency of the flue and air/fume ducts while the boiler is working.
•
Make sure the water is circulating properly between the boiler and the systems.
•
Make sure the gas valve modulates correctly in the heating and domestic hot water
production stages.
•
Check correct boiler lighting by performing various tests, turning it on and off with
the room thermostat or remote control.
•
Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap. 5.
•
Make sure that with no demand for heating, the burner lights correctly on opening a
hot water tap. Check that in heating mode, on opening a hot water tap, the heating
circulating pump stops and there is regular production of hot water.
•
Make sure the parameters are programmed correctly and carry out any required
customisation (compensation curve, power, temperatures, etc.).
Contents Description
Range
Parameter
b01
Gas type selection
0=Natural Gas
0
1=LPG
b02
Boiler type selection
2
b03
Combustion chamber type selection
5=LOW NOx Open Chamber
(with fume thermostat)
5
b04
Primary Exchanger type selection
0 ÷ 13
4
(for model
C24
)
5
(for model C30)
b05
--
--
0
b06
Mains Voltage Frequency
0=50Hz
0
1=60Hz
b07
--
--
5
b08
Gas valve driver
0 = Standard, 1
0
b09
DHW demand type selection
1 = Flowmeter (190 imp/l)
1
b10
Flowmeter timing
0=Deactivated
1-10=seconds
0
b11
DHW mode activation flow rate
10 ÷ 100 L/min/10
15
b12
Enable Auto-Settings procedure
0 = Disabled
1 = Enabled
0
Contents Description
Range
DIVAtech
D LN C
P01
Ignition ramp Offset
0-40
20
P02
Heating ramp
1-20°C/minute
5
P03
Heating standby time
0-10 minutes
2
P04
Heating Post-Circulation
0-20 minutes
6
P05
Heating user max. setpoint
31-85°C
80
P06
Max. output in heating
0-100%
100
P07
Burner shutdown in DHW
0=Fixed
0
1=Linked to set point
2=Solar
3 = DO NOT USE
4 = DO NOT USE
P08
DHW standby time
0-60 seconds
30
P09
DHW user max. setpoint
50-65°C
50
P10
No effect on adjustment
--
0
P11
DHW Post-Circulation
0-60 Seconds
30
P12
Max. output in DHW
0-100%
100
P13
Absolute min. power
0-100%
0
P14
NOT AVAILABLE FOR THIS MODEL
P15
No effect on adjustment (b03=5)
--
P16
Exchanger protection activation
0=No F43
10
1-15=1-15°C/second
P17
Modulating pump max. speed - absolute
Operating at 100%.
Adjustable with optional cable.
100
P18
Modulating pump max. speed - post circulation
0-100% not operating.
Always at 100% in this model
60
P19
Solar deactivation temperature
0÷20°C
10
P20
Solar ignition temperature
0÷20°C
10
P21
Solar standby time
0-20 seconds
10
Contents
Description
Range
t01
NTC Heating sensor (°C)
between 05 and 125°C
t02
NTC Safety sensor (°C)
between 05 and 125°C
t03
NTC DHW sensor (°C)
between 05 and 125°C
t04
NTC External sensor (°C)
between -30 and 70°C (negative values flash)Without NTC = --
L05
Actual burner power (%)
00%=Min., 100%=Max.
F06
Actual Flame resistance (kOhm)
00-99 kOhm (-- = burner off)
St07
NOT AVAILABLE FOR THIS MODEL
F08
Actual DHW drawing (L min/10)
L min/10 over 99 flashing 3 figures
PP09
Actual modulating pump speed (%)
00-100% not working in this model