Commissioning the System and User information
8.1
Filling the Cylinder
Open a hot water tap, and then open the cold water inlet valve. Allow the cylinder to
fill until through-flow is obtained at the hot water tap. Close the hot water tap. The
cylinder is now filled. N.B Flush system before filling.
8.2
Filling the Solar Circuit
A.
Remove the expansion relief valve assembly by removing the M8 screw.
B.
Attach a clean water supply to the filler nozzle. Turn the valve on the filling
manifold through 90
°
, and begin to fill the system.
A
B
C
D
C.
When water begins to flow from the fill level indicator at the bottom of the filling
manifold, turn the fill valve back through 90
°
and detach the water source.
D.
Replace the expansion relief valve assembly and secure in place with the supplied
screw.
Fill cap
Fill cap