EN
TROUBLESHOOTING
FAULTS
POSSIBLE CAUSES
REMEDIES
The pump does not start
No supply voltage
Check the electric connections
and the fuses
Incorrect supply voltage
Check the data on the plate and
apply the correct voltage
Faulty capacitor
(single-phase motors)
Change the capacitor
Rotor blocked by deposits on
the bushes
Select the maximum speed
and/or free the rotor with a
screwdriver
The system is noisy
Flow rate too high
Select a lower speed
Air in the system
Bleed the system
The pump is noisy
Air in the pump
Bleed the pump
Intake pressure too low
Increase the intake pressure
The pump starts and then
stops after a short time
Dirt or scale between the
rotor and the stator lining or
between the impeller and the
pump body
Check that the shaft is turning
freely. Remove any dirt and/
or scale
TECHNICAL PARAMETERS
Model
25-40 130 25-40 180 25-60 130 25-60 180 32-60 180 25-80 180 32-80 180
Operating range
0,2 - 3,5 m³/h
0,2 - 4,5 m³/h
0,1 - 10,5 m³/h
Head pressure
max. 3,8 m
max. 5,5 m
max. 8 m
Fluid temperature
min. +2°C, max. +110°C
Type of pumped
fluid
drinking water
Maximum
pressure
1,0 MPa (10 bar)
Protection class
IP 44
Insulation class
H
Cable gland
PG 9
Installation
with the shaft axis in a horizontal position and with the terminal
box fitted arbitrarily, but not under the pump
Voltage
50-60 Hz, ~230 V
Power
consumption
(I,II,III)
35/45/65 W
55/70/100 W
135/190/245 W
Terminal spacing
130 mm
180 mm
130 mm
180 mm
Terminal
1 1/2”
2”
1 1/2”
2”
Ambient
temperature
min. +2°C, max. +40°C
Содержание GPD 25-40 130
Страница 17: ...RU 8 1 2 a 3 15 F 3 x 0 75 2 5 3 10 7 9...
Страница 19: ...RU 1 FERRO S A Ferro 24 2 3 4 FERRO 5 6 7 8...
Страница 23: ...BG 8 1 2 3 TH 15 F 4 3 0 75 2 5 3 6 7 8 9 10...
Страница 25: ...BG 1 24 Ferro 6 2 3 4 5 6 7 200 c 2 8...
Страница 27: ...1 2 3 4 5 7 6 8 9 10...